May 3 , 1995
Jess Miller Dale Nelson
Miller Enterprises . Consolidated Construction Co .
606 Lime Kiln Rd. 4300 N. Richmond
Green Bay, WI 54301 Ap�leton, WI 54911
RE : 825 N. Wa�hbtirn
Interior Alterations/Cooler Addition
File #E3-68-495
Dear Sir:
Building plans have been reviewed by this office for compliance
with important code requirements . The drawings are stamped
"Construction may proceed, " All items that are required to be
changed by this letter must be corrected before commencing that
part of the work . This approval is not a Building Permit .
Necessary city permits must be secured before commencing work .
You are hereby advised that the owner, as defined in Chapter
101 , 01 ( i ) of the Wisconsin State Statutes , is responsible for all
code requirements not specifically cited herein. Code requirements
are set forth in Chapters 50 through 64 of the rules of the
Department of Industry, Labor and Human Relations .
The building will be inspected during construction and a final
inspection will be made after completion to insure complete
compliance with city and state codes .
The architect , professional engineer, builder or owner shall keep
at the building, as evidence of approval , one set of plans bearing
the stamp of approval .
ILHR 64 . 02 This ap�roval does not include heating and ventilating.
Such plans are required to be submitted and approved prior to
installation of such equipment .
ILHR 55 . 10 ( 1 ) (a ) The exit out of the kitchen shall not exceed 3 ' 6"
in width.
ILHR 51 . 15 Exit lights shall be provided.
ILHR 51 . 15 Maximum Occupancy in limited to 400 persons , based on
exit width. This was arrived at using a 42" wide door for exiting
out of the kitchen.
ILHR 55 . 06 (4 ) ( 11 and ( 2 ) Maximum Occupancy shall be posted at the
entrance .
_ '. .
ILHR 51 . 15 There shall be no hazardous kitchen equipment placed in
or near the exit path from the locker rooms to the north kitchen
exit door. (Present plan is acceptable, shows partition wall at
side of grill area . )
ILHR 51 . 15 All exit doors .;shall be capable of being pushed open--
no door knobs , levers allowed except for turn bolts which are
unlocked during operatiori hours .
Sincerely,
Allyn Dannhoff
Chief Building Inspector
cc : Lee Erdmann
HVAC Inspector