Loading...
HomeMy WebLinkAboutFax (fire rated enclosure)895 W.2ph Avenue, P.O. Box 2757 Oshkoch, Wl 609034157 TN (920)2353350 Fe�t (92D)2363419 -' •�� Building Solufions Sinte /S88 FACSIMILE TRANSMISSION FORM To: KBVin Bennef Company: Ciry ol Oshkosh Inspections Fax: 236 5084 D81B: 1/18/05 Reference: Banner Packaging Expension From: Brian Dobish THI9 TRANSMISSION IS 1 PAGE(S), INCIUDING THIS COVER SHEET MESSAGES/NOTES: ISavin: Per wur in�pectlon we understend Nat we will need to pmvids a flre 2ted enclosure at Me mezzanine level for the chase ihal enclased Me secontlarv conduit antl conductors ro tha switchpear WG wlll bB pfOVI(lillq tflB afIC�OBUfO D9l y0uf repUBSt We untlerstantl �hat wlth ihla aesurenCe vou vnll allow the service b be tumed on lor Construc�ion C.P. MlYER 4M 90N9 CONP�NV ��M F'Vf dy W ONYyI� - 01-1�06.%LS RlVISION t 1-t-06 TOTRL P.01 APPLETONFACII,ITY ... ..........'��� N10519Tnwcrb'IcwDr. Greenvillc,Wl 54942 920.959-1059 Fnx: Y21>959�IOSL JAN 2 1 2005 DEPARTMENT OF �74�s4UNlTY DEVELOPMENT January 13, 2W5 Keith Neuens Ba�ner Packaging Inc. 3550 Moser SVeet Oshkosh, WI54901 Re: Circuit Breaker Tcs[ing Square DjobiF 19569206-002 Dear Keith, Enclosed is [he test report for the Square D Powerpaet RJ 2000 circui[ breaker that was tes[ed a[ your faciliry located in Oshkosh, WI. The eirwi[ breaker passed both the visual/mechanical inspections and all electrieal [esls performed. The breaker was found to be in good working condi[ion and free of nny discrepancies. Thank you for allowing Square D Services to meet the electrical needs of Banner Packaging Ine. If you have any questions or concems regarding [his report or work performed please comact our sules representntive, Tom Ruegsegger,at877-737-7697. Regards, 7� �,�.�1 Terty Michels Square D Field Service Representative Emaih Terry.Michels@US.Schneider-Elee(riacom �sc�wae D Schneider Electnc LV Circuit Breaker l4viidiw�a \m YL.-im qb•A! (Manually Operated) Services Division 1-888-778-2733 REFERENCE INFORMATION Contac� Name: Keith Neuens 920303- FSR: Terry Michels Job No: 1 9 5692 06-002 2300 Customer Site: Banner 2004 Qea Customer Ref No: 0881691 OBID: 21-169060 Attn: Keith Oete: January 13, 2005 3550 MoserStreet Oshkosh, Wi 54901 IDENTIFICATION Sub Stetlon: NA Cus[omer Asset ID: Main Sub ID: NA Circuit ID: Service Enirance NAMEPLATE DATA Manufa<ture: Manufacture Date: Serial No: Type: Square D 2004 NA RJ 2000 Frame Size: Hetetl Amps: Sensor Rating: Reting Plug: 2000 Amps 2000 2000 2000 FuseType: FuseManufactu�e: Motlel/CaWlogNo: Rating: Unfusatl NA NA 0 Trip Unit Type: Trip Curve No: Interrupt Reting: Mounting: Micrologic6.OH 612-03 65000 Fixetl Number of Opera�ions: Number of Operetions: As Fauntl As Left INSPECTION CHECKLIST ITEM I1S LEFT ITEM AS LEFT SwitchCOndition: Acceptable Interlocks: NotApplicable Primary Discannects: Acceptable Over-Trevel Staps: Not Applicable Secontlary 0iscannecis: No� Applicable Mechanical Wear: Acceptable Grountl Cantects: Not Applicable Mechanical LubricaHOn: � Acceptabla Main Contects: Acceptable Control Wiring: Not Applicable Intermediate Contacis: Not Appliwble Con�rol Relay: Not Applicable Arcing Contacts: Acceplable Trip Free Test: Not Applicabla Pri.Current Pa�h Lubticetion Acceptable Manual Cbse Test: Acceptable Arc Chutes: Acceptable Spring Dlscharge: Not Applicable Interp�ase Barriers: Acceptable Insulated Linkages/Bracing Acceptable Gap / Wipe Settings: Not Applicable Contact Alignment / Not Applicable Sequence: INSULATION RESISTANCE TEST Test Equlpment ID: Callbratian Date: 1/6/04 FSR: 803 Test Volisge: 5 Meg-803 Tesis are pertormad with breaker Tests ara pertortnetl with breaker CLOSED and all unenergizetl poles grounded OPEN antl all unenergizad poles grounded AS FOUND AS LEFT AS FOUND AS LEFT A To B 40,000 mega 52 A LINE TO LOAD 40,000 mega 4 A To C 40,OOOmega 4 B LINE TO LOAD 40,000 mega R 8 To C 40,000 mega 4 C LINE TO LOAD 40,000 mega S2 A TO GROUND 40,000 mega n 8 TO GROUND 40,000 mega 4 7EMPERATURE 65 °F CTOGROUND 40,OOOmega4 HUMIDITY 45% CONTROL WIRING TEST Test Voltege: Kv As Found: As Lett: OVER CURRENT PROTECTION - TRIP UNIT DATA AND TEST Test Equlpmen� ID: FFTS-001 Callbretlon Date: 1/6/04 FSR: 803 Manufachre: Square D Trip Device Serial #: NA S�yle: Micrologic 6.OH Battery StaWS A5 Fountl: Pass As Leit: Pass .i2H�f196 CTCoiI Hetings:2,000 CTTap Ratings:2,000 Rating PIUg:2,000 As Found As Testetl As LeR As Faund As Tested As Lett Setting Se��ing Setting Setting Sening Setting Long Time Pickup 1 1 1 Instanlaneous Pickup 2 2 2 Long Time Delay 0.5 0.5 0.5 Ground Fault Pickup 500 500 500 ShoN Time Pickup 1.5 1.5 1.5 Grauntl Feult Delay 0.1 0.1 0.1 Shor1 Time Deley 0.1 0.1 0.1 CONTACT RESISTANCE TEST Test Equipment ID: Calibretlon Date: FSH: THROUGH PRIMARV DISCONNECT FINGERSAND/OR BVPASS PRIMARV DISCONNECT FINGENSANO/OR FUSES FUSES (IF APPLICABLE) (OR NO PRIMARY DISCONNECT FINGEHS AND/OH FUSES) AS FOUNO AS LEFT AS FOUND AS LEFT PHASE A micro n PHASE A micro Si PHASE B micro 4 PHASE B micm R PHASE C micm 4 PHASE C micm 4 Fa�c 7a Linda Trebiatowski Fax: 236-5933 Phone: � �%�Ql�i From: Kevin Benner Dale: 01/26I05 City of Oshkash Inspeclion Services Division 215 Church Avenue PO Bax 1130 Oshkosh W I 54903-1130 Re: 3550 Moser SI CC: Keith N. (Banner Packaging) ❑ Uryent ❑ For Review ❑ Please Comment ❑ Please Reply ❑ Please Reeyele • Comments: Attached are my inspection results for the Fire Pump Service and the 2000A 480 Distribution panel located on the mezzanine in the addition. Allyn also asked me attach a copy of fhe letter ihat he sent to Bob Fass (WPS). Any ques�ions or concems please feel free to contact myself @ 236-5046 or Allyn Dannhoff at 236-5045. Regards, Kevin Benner O CibofOshlvsM1 � D�dsiono(IwpcotianSemces 315 ChwchAVeoue Po Box 1130 O„ , �^ „ , OsAkosM1 WI54962-11]0 J F�.0 H Oflicc 920-D65050 Ox *H[ w�i[n Fax 930-2J650BG WISCONSIN PUBLIC SERVICE ROBERT A FASS PO BOX 19001 GREENBAY WI 54307-19001 Re: Electcical Petcnit and Contractor Requirements Deaz Mc Fass; January 24, 2005 This le[ter is to inform you of the City of Oslilcosh Electrical Peimit and Contractor requirements that aze applicable to work WPS was contracted to perfomi for Banner Packaging at 3550 Moser St. Specifically, it has been brought to our at[ention tha[ WPS was the contractor responsible for the installation of underground elecVical distribution lines and transformers at this property. Ordinadly, electrical work perfoRned by WPS is not subject to the Ci[y's Contractor License or Peimitting requirements. Oshkosh Municipal Code, section 11-3(B)(1) exempts "the installatioq alteration oc repair of electrical generation, transmission or distribution equipment but not utilization equipment, owned and operated by an electrical public utility or [he City." However, the work your company performed at Banner Packaging did not meet this exception because the electrical distribution lines installed on this property aze owned by Banner Packaging not by WPS or any other public utility. As a result a Licensed Electrica] Contractor must obtain an Elechic Permit for this work. Presently, WPS does not hold a City of Oshkosh Electrical Contractor License. You may apply for the required license if WPS employs a Master Electrician that has complete and unquestionable authority and supervision over all matteis �egulated by the Ci[y of Oshkosh Electric Code. Enclosed is an application for a City of Oshkosh Electrical Contractor License. Other items you should be awaze of relating to this recent installation: 1. All work is to be inspected prior to covering. Meaning inspection requests should have been filed for this installation prior to covering. Inspections still need to be azranged for your installation. 2. A person holding a S[ate of Wisconsin or City of Oshkosh Master Elec[rician or Joumeyman Electrician Credential must supervise the work conducted on site. We understand much of the wiring installation was subcontracted to another company. At this point we want to deteemine if your practices complied with [his requiremen[ and if no[, discuss options for compliance with future activity. 3. The ratio of credentialled electricians (Master or Journeyman) [o non-credentialled installers is limited to a 11 ratio. Again we simply want to de[emiine if your prac[ices aze in compliance wi[h our City code and if not, discuss what is required for compliance. Please contact Kevin Benner, Building Systems Inspector at 236-5046 to discuss these matters. At this point you must comply with the Electric Permit requiremen[. Please no[e we cannot issue you a pennit unless you hold a City of Oshkosh Electrical Conhac[or License. If you are not able to obtain the license, a licensed conVactoc may obtain the pennit for this installation if they aze willing to assume responsibility for this work. Please keep these issues in mind for future projects. If you have any questions, please call me at 236- 5045. Sincerely; All D off DireCtor of spection Service Enclosures cc: Kevin Benner, Building Systems Inspector Keith Neuens, Engineering Manager, Banner Packing