FACSIMILE TRANSMISSION FORM
To: KBVin Bennef
Company: Ciry ol Oshkosh Inspections
Fax: 236 5084
D81B: 1/18/05
Reference: Banner Packaging Expension
From: Brian Dobish
THI9 TRANSMISSION IS 1 PAGE(S), INCIUDING THIS COVER SHEET
MESSAGES/NOTES:
ISavin: Per wur in�pectlon we understend Nat we will need to pmvids a flre 2ted
enclosure at Me mezzanine level for the chase ihal enclased Me secontlarv conduit antl
conductors ro tha switchpear
WG wlll bB pfOVI(lillq tflB afIC�OBUfO D9l y0uf repUBSt
We untlerstantl �hat wlth ihla aesurenCe vou vnll allow the service b be tumed on lor Construc�ion
C.P. MlYER 4M 90N9 CONP�NV ��M F'Vf
dy W ONYyI� - 01-1�06.%LS RlVISION t
1-t-06
TOTRL P.01
APPLETONFACII,ITY
... ..........'��� N10519Tnwcrb'IcwDr.
Greenvillc,Wl 54942
920.959-1059
Fnx: Y21>959�IOSL
JAN 2 1 2005
DEPARTMENT OF
�74�s4UNlTY DEVELOPMENT
January 13, 2W5
Keith Neuens
Ba�ner Packaging Inc.
3550 Moser SVeet
Oshkosh, WI54901
Re: Circuit Breaker Tcs[ing
Square DjobiF 19569206-002
Dear Keith,
Enclosed is [he test report for the Square D Powerpaet RJ 2000 circui[ breaker that was tes[ed a[ your faciliry
located in Oshkosh, WI.
The eirwi[ breaker passed both the visual/mechanical inspections and all electrieal [esls performed. The breaker
was found to be in good working condi[ion and free of nny discrepancies.
Thank you for allowing Square D Services to meet the electrical needs of Banner Packaging Ine. If you have any
questions or concems regarding [his report or work performed please comact our sules representntive, Tom
Ruegsegger,at877-737-7697.
Regards,
7� �,�.�1
Terty Michels
Square D Field Service Representative
Emaih Terry.Michels@US.Schneider-Elee(riacom
�sc�wae D
Schneider Electnc LV Circuit Breaker
l4viidiw�a \m YL.-im qb•A!
(Manually Operated)
Services Division
1-888-778-2733
REFERENCE INFORMATION
Contac� Name: Keith Neuens 920303- FSR: Terry Michels Job No: 1 9 5692 06-002
2300
Customer Site: Banner 2004 Qea Customer Ref No: 0881691 OBID: 21-169060
Attn: Keith Oete: January 13, 2005
3550 MoserStreet
Oshkosh, Wi 54901
IDENTIFICATION
Sub Stetlon: NA Cus[omer Asset ID: Main
Sub ID: NA Circuit ID: Service Enirance
NAMEPLATE DATA
Manufa<ture: Manufacture Date: Serial No: Type:
Square D 2004 NA RJ 2000
Frame Size: Hetetl Amps: Sensor Rating: Reting Plug:
2000 Amps 2000 2000 2000
FuseType: FuseManufactu�e: Motlel/CaWlogNo: Rating:
Unfusatl NA NA 0
Trip Unit Type: Trip Curve No: Interrupt Reting: Mounting:
Micrologic6.OH 612-03 65000 Fixetl
Number of Opera�ions: Number of Operetions:
As Fauntl As Left
INSPECTION CHECKLIST
ITEM I1S LEFT ITEM AS LEFT
SwitchCOndition: Acceptable Interlocks: NotApplicable
Primary Discannects: Acceptable Over-Trevel Staps: Not Applicable
Secontlary 0iscannecis: No� Applicable Mechanical Wear: Acceptable
Grountl Cantects: Not Applicable Mechanical LubricaHOn: � Acceptabla
Main Contects: Acceptable Control Wiring: Not Applicable
Intermediate Contacis: Not Appliwble Con�rol Relay: Not Applicable
Arcing Contacts: Acceplable Trip Free Test: Not Applicabla
Pri.Current Pa�h Lubticetion Acceptable Manual Cbse Test: Acceptable
Arc Chutes: Acceptable Spring Dlscharge: Not Applicable
Interp�ase Barriers: Acceptable Insulated Linkages/Bracing Acceptable
Gap / Wipe Settings: Not Applicable Contact Alignment / Not Applicable
Sequence:
INSULATION RESISTANCE TEST
Test Equlpment ID: Callbratian Date: 1/6/04 FSR: 803 Test Volisge: 5
Meg-803
Tesis are pertormad with breaker Tests ara pertortnetl with breaker
CLOSED and all unenergizetl poles grounded OPEN antl all unenergizad poles grounded
AS FOUND AS LEFT AS FOUND AS LEFT
A To B 40,000 mega 52 A LINE TO LOAD 40,000 mega 4
A To C 40,OOOmega 4 B LINE TO LOAD 40,000 mega R
8 To C 40,000 mega 4 C LINE TO LOAD 40,000 mega S2
A TO GROUND 40,000 mega n
8 TO GROUND 40,000 mega 4 7EMPERATURE 65 °F
CTOGROUND 40,OOOmega4 HUMIDITY 45%
CONTROL WIRING TEST
Test Voltege: Kv As Found: As Lett:
OVER CURRENT PROTECTION - TRIP UNIT DATA AND TEST
Test Equlpmen� ID: FFTS-001 Callbretlon Date: 1/6/04 FSR: 803
Manufachre: Square D Trip Device Serial #: NA S�yle: Micrologic 6.OH
Battery StaWS A5 Fountl: Pass As Leit: Pass
.i2H�f196
CTCoiI Hetings:2,000 CTTap Ratings:2,000 Rating PIUg:2,000
As Found As Testetl As LeR As Faund As Tested As Lett
Setting Se��ing Setting Setting Sening Setting
Long Time Pickup 1 1 1 Instanlaneous Pickup 2 2 2
Long Time Delay 0.5 0.5 0.5 Ground Fault Pickup 500 500 500
ShoN Time Pickup 1.5 1.5 1.5 Grauntl Feult Delay 0.1 0.1 0.1
Shor1 Time Deley 0.1 0.1 0.1
CONTACT RESISTANCE TEST
Test Equipment ID: Calibretlon Date: FSH:
THROUGH PRIMARV DISCONNECT FINGERSAND/OR BVPASS PRIMARV DISCONNECT FINGENSANO/OR FUSES
FUSES (IF APPLICABLE) (OR NO PRIMARY DISCONNECT FINGEHS AND/OH FUSES)
AS FOUNO AS LEFT AS FOUND AS LEFT
PHASE A micro n PHASE A micro Si
PHASE B micro 4 PHASE B micm R
PHASE C micm 4 PHASE C micm 4
Fa�c
7a Linda Trebiatowski
Fax: 236-5933
Phone:
�
�%�Ql�i
From: Kevin Benner
Dale: 01/26I05
City of Oshkash
Inspeclion Services Division
215 Church Avenue
PO Bax 1130
Oshkosh W I 54903-1130
Re: 3550 Moser SI CC: Keith N. (Banner Packaging)
❑ Uryent ❑ For Review ❑ Please Comment ❑ Please Reply ❑ Please Reeyele
• Comments: Attached are my inspection results for the Fire Pump Service and the 2000A 480
Distribution panel located on the mezzanine in the addition. Allyn also asked me attach a copy of fhe
letter ihat he sent to Bob Fass (WPS). Any ques�ions or concems please feel free to contact myself @
236-5046 or Allyn Dannhoff at 236-5045.
Regards,
Kevin Benner
O CibofOshlvsM1
� D�dsiono(IwpcotianSemces
315 ChwchAVeoue
Po Box 1130
O„ , �^ „ , OsAkosM1 WI54962-11]0
J F�.0 H Oflicc 920-D65050
Ox *H[ w�i[n Fax 930-2J650BG
WISCONSIN PUBLIC SERVICE
ROBERT A FASS
PO BOX 19001
GREENBAY WI 54307-19001
Re: Electcical Petcnit and Contractor Requirements
Deaz Mc Fass;
January 24, 2005
This le[ter is to inform you of the City of Oslilcosh Electrical Peimit and Contractor requirements that aze
applicable to work WPS was contracted to perfomi for Banner Packaging at 3550 Moser St.
Specifically, it has been brought to our at[ention tha[ WPS was the contractor responsible for the
installation of underground elecVical distribution lines and transformers at this property. Ordinadly,
electrical work perfoRned by WPS is not subject to the Ci[y's Contractor License or Peimitting
requirements. Oshkosh Municipal Code, section 11-3(B)(1) exempts "the installatioq alteration oc
repair of electrical generation, transmission or distribution equipment but not utilization equipment,
owned and operated by an electrical public utility or [he City." However, the work your company
performed at Banner Packaging did not meet this exception because the electrical distribution lines
installed on this property aze owned by Banner Packaging not by WPS or any other public utility. As a
result a Licensed Electrica] Contractor must obtain an Elechic Permit for this work.
Presently, WPS does not hold a City of Oshkosh Electrical Contractor License. You may apply for the
required license if WPS employs a Master Electrician that has complete and unquestionable authority
and supervision over all matteis �egulated by the Ci[y of Oshkosh Electric Code. Enclosed is an
application for a City of Oshkosh Electrical Contractor License.
Other items you should be awaze of relating to this recent installation:
1. All work is to be inspected prior to covering. Meaning inspection requests should have been
filed for this installation prior to covering. Inspections still need to be azranged for your
installation.
2. A person holding a S[ate of Wisconsin or City of Oshkosh Master Elec[rician or Joumeyman
Electrician Credential must supervise the work conducted on site. We understand much of the
wiring installation was subcontracted to another company. At this point we want to deteemine if
your practices complied with [his requiremen[ and if no[, discuss options for compliance with
future activity.
3. The ratio of credentialled electricians (Master or Journeyman) [o non-credentialled installers is
limited to a 11 ratio. Again we simply want to de[emiine if your prac[ices aze in compliance
wi[h our City code and if not, discuss what is required for compliance.
Please contact Kevin Benner, Building Systems Inspector at 236-5046 to discuss these matters.
At this point you must comply with the Electric Permit requiremen[. Please no[e we cannot issue you a
pennit unless you hold a City of Oshkosh Electrical Conhac[or License. If you are not able to obtain the
license, a licensed conVactoc may obtain the pennit for this installation if they aze willing to assume
responsibility for this work.
Please keep these issues in mind for future projects. If you have any questions, please call me at 236-
5045.
Sincerely;
All D off
DireCtor of spection Service
Enclosures