HomeMy WebLinkAboutHVAC 11/16/1981� � '.� ..
� +,t�'� " StStC Of WISCOIISIII \ Department o( Indushy, Labor and Human Relations
November 6, 1987
sncerv a sui�mmcs oivisiom
File Number E-99202
Mr. Rollin Benson
Marshall Nelson & Associates
2110 West Silver Spring Drive
Milwaukee� Wisconsin 53Z09
Dear Mr. Benson:
Factory/Warehouse Addition
Banner Packaging� Inc., Non Sowle� Owner
3550 Moser Street
Oshkosh� Winnebago County
Plan Number 81-09-0305-B
Volume: 405,000 Cubic Feet
$54 Inspection Fee Paid
Follin F. Benson� Supervising Engineer
201 E. WaSFinglon Avenue
P.O. Box ]969
Mudlson, W�rzconzin 53J0]
Heating and ventilating plans have been reviewed by the Department of Industry�
Labor and Human Relations for compliance with the important code requirements.
The plans are stamped "Conditionally Approved," and construction may proceed
subject to local regulations, but all items that are required to be changed by
this letter must be corrected before commencing that part of the work.
You are hereby advised that the owner as defined in Chapter 101.01 (2) (i) of
the Wisconsin State Statutes is responsible for all code requirements not
specifically cited herein. Code requirements are set forth in Chapters 50 thr�
64 of the Rules of the Department.
The building will be inspected during and after construction by a deputy of
this Department to insure complete compliance with Wisconsin Codes. The owner
may notify the state building inspector listed below if a final inspection is
desired before taking possession of the building.
Ind 50.15 Evidence of approval. The architect, professional engineer,
designer� builder or owner shall keep at the building� one set of plans bearing
the stamp of approval.
Ind 64.48 The infrared heaters shall be equipped with a type "B" vent whieh
extends at least 2 feet above the roof as well as 2 feet higher than a ridge�
peak or wall within 10 feet of a vent as specified in Ind 64.45.
3- vJ-�,�
DiLHF�5B0-5544
..,
� '
Mr. Rollin Benson
November 6, 1g81
Page 2
Ind 63.01(2) and SO.Oi(2)(e) The owner is respo�sible for the submittal of
illumination plans as required by Section Ind 63•o1(2). The illumination plans
shall be signed and sealed by a Wisconsin registered architect� engineer or
electrical tlesigner if the building contains more than 50�000 cubic feet 1❑
volume. Four copies of the Illumination Power Budget form (SBD-5315) may be
used i� lieu of four sets of plans on smaller projects without electrical
layouts. A fixture schetlule must accompany eaeh plan or form. An illumination
submittal requires a$35 fee when submittetl separately or a$10 fee when
submitted with other plans. A separate illumination submittal requires a
properly signed plan approval application form (SB-718).
Sincerely,
Jerry Albrecht
Staff Engineer
JA:TH0904
cc: R-3 Covill� phone 715-3�6-3�93, Friday a.m.
i'Oshkosh Building Inspector
Mr. Ron Sowle
Banner Packaging, Inc.
3550 Moser Street
Oshkosh� Wisconsin 549az