INTRODUCTION
The ESL Detector Compatibility Index has been compiled in order to provide you with a simple cross reference of the many
compatibility listings that ESL or the panel manufacturers have obtained.Underwriters Laboratories,Inc.has confirmed that the
ESL,UL-Listed Fire Sensors are electrically compatible with the UL-Listed Control Units as shown in the tables.
The Index is organized alphabetically by control unit manufacturer.Each manufacturer's listing specifies a control unit,the
applicable loop style(formerly Class A or B wiring►,the control unit compatibility identification,the maximum number of ESL
detectors allowable per initiating circuit and the ESL Compatibility Identifier.
To use this index:
• First,look up the control unit and determine the ESL Compatibility Identifier.
• Next,turn to the Identifier Cross Reference List to determine the ESL detectors
(and Bases)which are compatible.
• We have provided the Identifier Cross Reference List sorted by both Identifier Number
and Detector Model Number for your convenience.
This listing should provide you with all the information you require for determination of compatibility. It should also be sufficient
information to answer any questions raised by the AHJ(Authority Having Jurisdiction►on any projects.Please have the name of
the control unit manufacturer and control unit description handy when you call Technical Services at 1-800-648-7424,so we can
provide you with the correct information.
fire Sensors and Control Units and their compatibility are subject to change without notice.
ESL has made every attempt to provide complete,accurate and up-to-date information.We are not responsible for omissions or
errors.If you would like ESL to add a new panel to its compatibility listings,please contact ESL Marketing at 1-800-547-2556.
Please have the name of the control unit manufacturer and control unit description handy when you call.
Note on Four-Wire Detectors:
Four-Wire Detector Compatability listings are not required by UL,therefore no Four-Wire Detectors are included in the
compatability index.A Four-Wire Detector is considered compatible if the voltage range of the detector equals or exceeds the
voltage range of the control panel power supply,and if sufficient current is available to insure the operation of all detectors.
Note on Carbon Monoxide Detectors:
Carbon Monoxide combatibility listings are not required by UL,therefore no Carbon Monoxide Detectors are included in the
compatability index.A Carbon Monoxide Detector is considered compatible if the voltage range of the detector equals or exceeds
the voltage range of the control panel power supply,and if sufficient current is available to insure the operation of all detectors.
ESL 505 Module
CleanMeT"' Interpreter and 2 to 4-Wire Input Converter Module
• '��e 505 Module serves as an interface between the ESL
'�'1 Series smoke detector and any UL Listed 12/24V DC
:�ntrol panel:*
• Interprets 521 CleanMeTM'signal for any panel
• • AI lows central station to be notified when detector needs
� to be cleaned
• Converts any current ESL 2-wire smoke detector to 4-wire
inputs of any panel
• 3 diagnostic LEDs
• Ensures 2-wire compatibility with any control panel
U� California State Fire Marshal Approved
usteo
Specifications
Operation Voltage 12V-33V DC
Standby Current 15mA+/-10%
AlarmCurrent 50mA+�-10°� SmokeOetectorTrouble �
Luop Trou61e
Power/Alarm
form A contacts 500mA C�36V DC(resistive) (Blinking Steadyl % 5'"
Form C contacts 2 Amps�28V DC or 120V DC(resistive� i L c � ' �
L J
Number of detectors/module 20 `— -
Operating Temperature -20°C to 55°C
Humidiry 0-95%non-condensing
RFI Immunity 20V/M @ 0-1 ghz
Static Immunity 25,000 V
Transient Immuniry 2,500 V�1.5J � � ���
�-
��-�%"�
Color whitelwhite � ��„
Mounting Mountable to 4°square,double gang boxes ��-� �J
�.,�. � i %
Material Flame retardant plastic cover IUL-94V-0) , � �
Field wiring size 12-24 AWG b `
�
Ordering Information
Model Description
Number
505 Module that interprets the 521's CleanMeT"^signal for any panel and can convert 2-wire
521 Series detectors to 4-wire inputs on these panels
CleanMe"is a trademark of GE Security and is protected under the following U.S.Patent No.:5,708,414.
*CleanMeT""Compatible control panels that do not require use of the 505 module:
ADVENT(GE Security)Panels
DMPXR70
DMP XR20
DMP XR200
DMP XR5FUXR5SL
Napco Gemini 320012V Burg/Fire Panel
Napco Gemini 960012V Burg/fire Panel
Silent Knight SK4224 24V FACP
,
Contents
Identifier Cross Reference List(Sorted by IdentifierJ...............................................................................4
Identifier Cross Reference List(Sorted by Model Numberi.....................................................................4 �
Ademco.............................................................................................................................................................5
ADTSecurity Sysiems,Inc............................................................................................................................5 '
Advantor...........................................................................................................................................................5
AlisonControl Inc............................................................................................................................................6
AuthCompany..................................................................................................................................................6
Autocal!Corporation,A Division of Thorn Automated Systems..............................................................6 �
BurleIndustries...............................................................................................................................................7 `
C&K Systems,Inc..........................................................................................................................................7 ;
CerberusPyrotronics......................................................................................................................................7
DetectionSystems,Inc. .................................................................................................................................8
Digita/Monitoring Products,Inc.(DMP/.....................................................................................................8
Digital Security Controls/DSCI.....................................................................................................................9 '
Edwards(Edwards Systems Technolo9Y1...................................................................................................9
Ellenco,lnc.....................................................................................................................................................10
Faraday,Inc....................................................................................................................................................10 ;
FederalSignal Corporation..........................................................................................................................11
FireBurglary Instruments............................................................................................................................11 :
Firecom,Inc....................................................................................................................................................11
FireControl Instruments...............................................................................................................................11 :
Firelite..............................................................................................................................................................11
firstA/ert........................................................................................................................................................12
Gamewell........................................................................................................................................................12 ;
GE Securiry(Aritech,Caddx,ESL,ITI,Moose).........................................................................................12
HarringtonSignal..........................................................................................................................................13
Honeywell,Inc...............................................................................................................................................13 ;
JohnsonControls,Inc...................................................................................................................................14
Landis&GYR(MCC PowersJ.......................................................................................................................14
Mirtone............................................................................................................................................................14 .
NapcoSecurity Systems..............................................................................................................................15
NationalGua�dian.........................................................................................................................................15
Notifier............................................................................................................................................................16
OpTexMorse,Inc...........................................................................................................................................16
Pem-Ali Fire Extinguisher Corporation......................................................................................................16
PotterElectric Signal Company..................................................................................................................16
ProtectowireCompany.................................................................................................................................16
Radionics,Inc. ...............................................................................................................................................17
Safetech,Inc..................................................................................................................................................17
Scantronic(USAJ,Inc...................................................................................................................................17
Security/Ameritech.......................................................................................................................................18
Secuiron.........................................................................................................................................................18
Silent Knight Security Sysiems...................................................................................................................18
SpectronicsCorporation..............................................................................................................................18
Thorn...............................................................................................................................................................19
Tyco(Simplex-Grinnel,Wormald)...............................................................................................................19
WalterKidde...................................................................................................................................................ZO
Westec............................................................................................................................................................Z(I
Identifier Cross Reference List(Sorted by IdentifierJ
ESL Detector ESL Base Detector Compatib/e Base
Compatibility Identifier Compafibility Identi/ier Model Number
S09A NA 429AT NA
5216/BXT(SW 1 On) NA
S10A NA 429C NA
429CT NA
511 C NA
521 B/BXT(SW 1 Off) NA
521 NB NA
521 NBXT NA
521NCSXT NA
S10A S00 711U/UT 701E,701U,702E,702U
S10A S00 721U/UT 701E,701U,702E,702UN
S11A NA 429CRT NA
429CST NA
S11A NA 521CRXT NA
521NCRXT NA
521NCSRXT NA
SitA S00 731U 701U,702E,702RE,
702RU,702U
Identifier Cross Reference List(Sorted by Model NumberJ
Detector ESL Detector Compatible Base ESL Base
Model Number Compatibility Identifier Compatibility Identifier
429AT S09A NA NA
429C S10A NA NA
429CT S10A NA NA
429CRT S11 A NA NA
429CST S 11 A NA NA
511 C S 10A NA NA
5218/BXT(SW 1 On� S09A NA NA
5216/BXT(SW 1 Offl S10A NA NA
521CRXT S11A NA NA
521 NB/BXT S10A NA NA
521 NCSXT S10A NA NA
521NCSRXT S11A NA NA
521 NCRXT S11A NA NA
711U/UT S10A 701U,702E,702U S00
721U/UT S10A 701U,702E,702U S00
731U S11A 701U,702E,702RE,702RU,702U S00
Gf Security ESL Compatibility lndex-10/04 subject to change withoui notice Call FaxBack for latesi listings 800-483-2495
4
Ademco
Contro/Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
4120EC B Household Fire 5 S09A
4140XM B Household fire 10 S09A
414{1XM Series�4140XMP,4140XMPT,4140XMPT-2) B Household Fire 20 S09A
5140XM Series B A 20 S09A
FOCUS 200 PLUS B A 10 S09A
Vista-15P B Household Fire 20 S09A
Vista-20Nista-20P B Household Fire 20 S09A
Vista-40 B Household Fire 20 S09A
Vista-50 B Household Fire 20 S09A
Vista-50PNista-50PEN/Vista-50PUL B Household Fire 20 SD9A
Vlsta-100 B Household Fire 10 S09A
ADT Security Systems, Inc.
Contro!Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
4519-013,4519-313 A J1 10 S10A,S00
4520,Zone Model 4520-064 A G1 10 S10A,S00
4520,Zane Model 4520-084 B H1 13 S10A,S00
4520,Zone Model 4520-330 and/or A C1 15 S10A,S00
Zone Model 4520-331
4520,Zone Model 4520-130 A B1 15 S10A,S00
4520,Zane Model 4520-431 A A1 15 S10A,S00
4520,Zone Model 4520-230 A E1 15 S10A,S11A,S00
4520,Zone Model 4520-429 and/or D F1 10 S10A,S00
Zone Model 4520-529
4520,Zone Model 4520-430 and/or A D1 10 S10A,S11A,S00
Zone Model 4520-530
FOCUS 75 B A 20 S09A
MCFAP-2Z3,2Z6 D 20 S10A,S00
w or w/o(-220�,Zone Model BPAC or IDCA
MCFAP-1Z1,2Z1 B 20 S10A,S00
w or w/o(-220)
MCFAP-2Z3,2Z6 B 20 S10A,S00
w or w/a(-220�,Zone Model w or w/o 21DC
Unimode 2 Control Unit B,D A 18 S10A,S00
Unimode 4-16,Zone Model IZ-4 and/or B,D A 18 S10A,S00
Zone Model IZ-4A and/or Zone Model IZ8
Unimode 4-16/II,Zone Model IZ4;8 and/or IZM-8 20
Zone ID with or without IZE
Unimode 5 B,D 20 S10A,S00
Unimode 10 B,D 20 S10A,S00
Unimode 200,Zone Model M302 B,D 24 S10A,S11A,S00
Safewatch P3000 B 20 StOA/S11A/S00
Ad vantor
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit Identi/ier
Advantage A 16 S10A,S00
ULF-3000-24
GESecurity ESL Compatibility Index-10/04 subject to change without notice Call FaxBack for latesi listings 800-483-2495 :
5
Alison Control, Inc. �
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
A888-MXXX,Zane Mode1108800-2 B,D 002 25 S10A,S00
A888-MXXX,Zone Mode1108800-2 B,D 002 50 S10,SOO,S02
Aritech (see GE Security)
Auth Company
Conhol Unit Description Loop Contro/ Detectors ESL Compatibility
Sty/e Unit ID# Per Circuit Identifier :
AFC 100,Zone Madel PCB 160 B 026 30 S10A,S11A,S00
AFC 100,Zone Madel PCB 173 D 027 30 S10A,S1 tA,S00
AFC 100,Zone Madel PCB 175 B 025 30 S10A,S11A,S00
AFC 400C,Zone Madel SMD-2 B,D 024 30 S10A,S11A,S00
Autocall Corporation,
A Division of Thorn Automated Systems
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit lD# Per Ciicuit Identifier
AC-Ii,Zone Model 5130-074-21 D 01A 20 S10A,511A,S00
AC-II,Zone Model 5200-522 B 01A 20 S10A,S11A,S00
AC-II,Zone Models 5130-106-10 B 01A 30 S10A,S11A,S00
ar5200-433
AC-II,Zone Model 5200-432 D 01A 30 S10A,S11A,S00
AC-II,Zone Model 5200-521 B 01A 12 S10A,S11A,S00
AC-II,Zone Model 5130-521 B 01A 12 StOA,St tA,S00
CD-NA,Zone Model 5200-432 D 01A 30 S10A,S11A,S00
CD-NA,Zone Madel 5200-433 B 01A 30 S10A,St tA,S00
CD-TXA,Zone Model 5130-074-21 D 01A 20 StOA,S11A,S00
CD-TXA,Zone Madel 5200-522 B 01A 20 S10A,S11A,S00
CD-TXA,Zone Model 5130-106-10 B 01A 60 S10A,S11A,S00
or5200-433
CD-TXA,Zone Model 5200-432 D 01A 60 S10A,S11A,SO
CD-TXA,Zone Mode15200-521 B 01A 12 S10A,S11A,S00
CD-XA,Zone Made15200-522 B 01A 20 S10A,S11A,S00
CD-XA,Zone Mode15130-074-21 D OtA 20 S10A,S11A,S00
CD-XA,Zone Mode15200-521 B 01A 12 S10A,S11A,S00
CD-XA,Zone Madel 5130-106-10 B 01A 30 StOA,S11A,S00
CD-XA,51200-433 B 01A 30 S10A,S11A,S00
CD-XA,Zane Mode15200-432 D OtA 30 S10A,S11A,S00
MDK,Zone Madel 5130-044-02 B 01A 30 S10A,S11A,S00
MDK,Zone Madel 5130-044-03 B 01A 30 S10A,S11A,S00
MDK,Zone Model 5130-106-10 B 01A 30 S10A,S11A,S00
MD2K,Zane Model 5130-044-02 B 01A 30 S10A,S11A,S00
MD2K,Zone Model 5130-044-03 B 01A 30 S10A,S11A,S00
MD2K,Zone Model 5130-106-10 B OtA 30 S10A,S11A,S00
MDK,Zone Model 5130-044-04 B 01A 30 S10A,S11A,S00
GE Security ESL Compatibility lndex-10/04 subject to change withoui notice Cail FaxBack for latesi lisiings 800-483-2495
6
Autocall Corporation,
A Division of Thorn Automated Systems (continuedl
Contro/Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuii Identifier
MDK,Zone Model 5130-044-05 8 OtA 30 S10A,S11A,S00
MD2K,Zone Model 5130-044-04 D 01A 30 S10A,S11A,S00
MD2K,Zone Model 5130-044-05 D 01A 30 S10A,S11A,S00
MEALIN Control Unit,Zone Models B 01A 30 S10A,S11A,S00
5130-106-10 or5200-433
MERLIN Control Unit,Zone Models D 01A 30 S10A,S11A,S00
5130-432 ar5200-432
MP400,Zone Model 5130-074-21 D 01A 20 S10A,S11A,S00
MP400,Zone Model 5130-106-10 B 01A 30 S10A,S11A,S00
MP400,Zone Model 5200-433 B 01A 30 S10A,S11A,S00
MP400,Zone Madel 5200-432 D 01A 30 S10A,S11A,S00
MP400,Zone Madel 5200-521 B 01A 12 S10A,S11A,S00
FIREQUEST 100-12 B 10112A 7 S10A,S00
FIREQUEST 200,Zone Model 2ZX B,D 200A 22 S10A,S11A,S00
FIREQUEST 200,Zone Model 4ZX,4ZXD B 200A 22 S10A,S11 A,S00
or COMM CONT.AEV.W
FIREQUEST 200,Zone Model U B,D 200X 22 S10A,S11 A,S00
FIREQUEST 200,Zone Model MASTER HALON B,D 200A 22 S10A,S11 A,S00
FIREQUEST 200,Zone Model VSO B,D 200A 30 S10A,S11 A,S00
FIREQUEST 300,Zone Model with or w/o DIB B,D F2 S10A,S11 A,S00
K-101-24 B,D 10124A 30 S10A,S11A,S00
KDR-1000,Zone Madel AIZ or AIZ-2 D 1000A 30 S10A,S11A,S00
KDA-1000,Zone Model BIZ-t,BIZ-2,BIZ-5 B 1000A 30 S10A,S11A,S00
KDR-1000,Zone Model DZM B 10008 30 S10A,S11A,S00
KDR-1000,Zone Model MIZP B 1000C 30 S10A,S11A,S00
Burle Industries
All panels No 2-wire fire loops,use 4-wire models or ESL 505 2 to 4 wire converter module
C& K Systems �i�c.J
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit lD# Per Circuit Identi/ier
SYS238 Series B Household fire 12 S09A
SYS2316 Series B Household Fire 12 S09A
Cerberus Pyrotronics
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identi/ier
CP-2HR A,B,D CP-2HR 30 S10A,S11A,S00
CP-35 A,B,D CP-35 30 S10A,S11A,S00
CP-35,Zone Model ZU-35 A,B,D ZU-35 30 S10A,S1 tA,S00
CP-35,Zone Model ZU-35DS A,B,D ZU-35DS 30 S10A,S1 tA,S00
CP-35,Zone ModeIZU-35TS A,B,D ZU-35TS 30 S10A,S11A,S00
CP-400 B CP-400 30 S10A,S11A,S00
CP-400,Zone Model ZNE-404 B ZN-4�4 30 S10A,S11A,S00
GE Security ESL Compatibility lndex-10/04 subjeci to change without notice Call FaxBack for latest lisiings 800-483-1495
7
Cerberus Pyrotronics (Continued.) :
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circait ldentifier
CP-400,Zone Model ZNE-404/S B ZNE404/S 30 S10A,S11A,S00
CP-400,Zone Model 405A D 405A 30 S10A,S11A,S00
CTI-1,Zone Model 30774-02 B 30774-02 25 S10A,S11A,S00
CTI-1,Zone Model 30774-03 B 30774-03 25 S10A,S11A,S00
IXL with CZI-H2S B P/N-02,P/N-03 25 S10A,S00
IXL with CZI-H4S D P/N-01,30774 25 S10A,S00
MX-316 A,B,D MX-316 30 StOA,S11A,S00
MXL,with CZA-1,CZR-4 B,D CZM-1 20 S10A,S00
CZM-4 20 S10A,S00
SXL with or without SZE-4R B Model No. 25 S10A,S00
XL-3,Zone Mode�ZNX-3 A,B,D ZNX-3 30 S10A,S11A,S00
Detection Systems, lnc.
Conhol Unit Description Loop Controi Detectors ESL Compatibility
SYyle Unit ID# Per Circuit Identifier
D7024 Series with D7014/DS9411 D B 20 S10A,S11 A,S00 :
DS7090 Series 8 Household Fire 16 S09A
DS7090i Series;and DS7090TMi B B1 20 S10A,S00
DS7100 Series B B 16 S09A
DS7100 Series with DS7110 B B1 16 S09A
DS7400 Series with DS7433 B C 20 S10A
DS9400 Series with D7014/DS9411 D B 20 S10A,S11A,S00
Digital Monitoring Products, Inc. (DMPJ
. Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
1512 control,Zone Madel 715,or Zone 5 A A 12 S09A
1812A,Zone Mode1705 B CI-1 10 S10A,S00
1812B,Zone Model 705 B CI-1 10 S10A,S00
1812C,Zone Mode1705 B CI-1 10 S10A,S00
1812D,Zone Mode1705 B CI-1 10 S10A,S00
1812E,Zone Model 705 B CI-1 10 S10A,S00 .
1912 control,Zone Model 715,or Zone 5 A A 12 S09A
1912XR control,Zone Model 715,or Zone 5 A A 12 S09A
XR5SL,Zone Model 2-5 on XR5SL control tCleanMe A A 12 S09A
XR5FC,Zone Model 2-5 on XR5FC control A A 12 S09A
XR20,Zone Model 715,715-8,715-16 A A 12 S09A
or zone 10 on XR20 control �CleanMe
XR10,Zone Model 715,715-8,715-16 wCeanMe A A 12 S09A
or zonel0 on XR10 control � ����••�••�
XA200,Zone Model 715,715-5,715-16 A A 12 S09A
or zone 9&10 on XR200 NC�eanMe
GESecurity ESL Compatibility Index-10/04 subject to change wiihout notice Call FaxBack ior latest lisiings 800-483-1495
8
Digital Security Controls �oscl
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit lD# Per Circuit Identifier
4020CF B 30 S09A
PC5010 B 15 S09A
PC4010CF B FM-1 30 S09A
PC4020CF B FM-1 30 S09A
PC50101Power832) B PC5.1 30 S09A
PC1575 B PC15.1 30 S09A
Edwards (Edwards Systems Technology)
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Ci�cuit Identi/ier
12118 B,D 001 15 S10A,S11A,S00
12126 B,D 001 15 S10A,S11A,S00
12148 B 001 15 S10A,S11A,S00
2400(2412,2414,2418) B 20 S10A,S00
Zone Model 2400-21DC(2400-2101)
2400(2412,2414,2418) D 20 S10A,S00
Zone Model 2400-2BPA or 2400-IDCA
(2400-2104,2400-2105)
57218,Zone Model 5703B-105,or 5703B-405 D 001 20 S10A,S11A,S00
5721 B,Zone Model 5703B-122, B 001 20 S10A,S11 A,S00
or5703B-402,or5703B-406
5751B B,D 001 20 S10A,S11A,S00
5752B,Zone Model 5750B-102 B 001 20 S10A,S11A,S00
57526,Zone Model 57506-105 D 001 20 S10A,S11A,S00
5753B,Zone Model 57506-102 B 001 20 S10A,S11A,S00
5753B,Zone Model 57506-105 D 001 20 S10A,S11A,S00
57548 B 001 20 S10A,S11A,S00
57548-2Z B 001 20 S10A,S11A,S00
5756B B,D 001 20 S10A,S11A,S00
57828 8,D 001 20 S10A,S11A,S00
5800,Zone Model 5703-R2,5703-R5 B,D 001 25 S10A,S11A,S00
6602-B201 B 660201 30 S10A,S11A,S00
6604-B201 B 660201 30 S10A,S11A,S00
6602-B201,Zone Mode16602-B102 D 660201 30 S10A,S11A,S00
6604-B201,Zone Mode16602-6102 D 660201 30 S10A,S11A,S00
6616,Zone Model 6616-301,or 6616-303 B 660201 18 S10A,S11A,S00
6616,Zone Model 6616-304 D 660201 18 StOA,S11A,S00
6632,Zone Mode16616-301,or6616-303 B 660201 18 S10A,S11A,S00
6632,Zone Mode16616-304 D 660201 18 S10A,S11A,S00
8500,Zone Model 8501-X341,or 8501-X381 B 85001 20 S10A,S11A,S00
8500,Zone Model 8501-X342,or 8501-X382 D 85002 20 S10A,S11A,S00
8500,Zone Model 8501-X343,or 8501-X383 8 85003 20 S10A,S11A,S00
8570-ESAC,Zone Model 8572-X201 B 857001 30 S10A,S11A,S00
8570-ESAC,Zone Mode18572-X202 D 857002 30 S10A,S11A,S00
IRC-1,Zone Model 130022 B,D 5876 30 S10A,S11A,S00
IRC-3,Zone Model 130108 or 240113,or 240119 B 3289B 30 S10A,S11A,S00
IRC-3,Zane Mode1130082 B,D 3289A 30 S10A,S11A,S00
GE Security ESL Compatibility Index-10/04 subject to change without notice Call FaxBack for latesi listings 800-483-7495
9
Edwards (Edwards Systems Technology)(Continuedl
Control Ueit Description Loop Conho/ Detectors ESL Compatibility
Style Unit 1D# Per Circuit ldentifier
IRC-3,Zone Model 240205 B 5389 24 S10A,S11A,S00
LSS1,Zone Model 4CLA,4ZEXP B,D 0.0 30 S10A,S00
LSS4,Zone Model 4CLA,4ZPXP B,D 0.0 30 S10A,S00
LSS1/12,Zone Model 4CLA,4ZEXP B,D 0.0 30 S10A,S00
LSS4/12,Zone Model 4CLA,4ZEXP B,D 0.0 30 S10A,S00
RZ812-6MFC,Zone Model 240205 B 5389 24 StOA,S11A.S00
ESL(see GE Security)
Ellenco Inc.
Cantrol Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit /dentifier
PMS,Zone Model MCP-1 B ZEI-01 15 S10A,S00 '
PMS,Zone Model ZE-2A B,D ZEI-04 15 S10A,S00
PMSJR-1 B,D ZEI-03 15 S10A,S00
PMSJA-2 B,D ZEI-03 15 S10A,S00
ECP-2000,Zone Model 401310/401311/401312 B 30 S10A,S00
Farada y, Inc.
Contro/Unit Description Loop Controf Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
FA200 B,D 30 S10A,S1 tA,S00
852 B FOS1 30 S10A,S11A,S00
854 B FOS1 30 S10A,S11A,S00
MPC-2000,Zone Model ZN-1,ZN2 and ZN-3 B,D D 15 S10A,S00
7800,Zone Mode17836 B,D B 40 S10A,S11A
12400 B G 25 S10A.S00
1Z500,Zone Model 12503 B M 30 S10A,S00
13200 B F 30 S10A,S00
13400 B G 30 St0A,S00
15108A,151086 B,D A 30 S10A,S11A,S00
15108AL,15108BL B,D FOS2 15 S10A,S11A,S00
15112A,15112B B,D A 30 S10A,S11A,S00
15112AL,151126L B,D fOS2 15 S10A,S11A,S00
15116A,15116B B,D A 30 S10A,S11A,S00
15116AL,15116BL B,D FOS2 30 S10A,S11A,S00
15220A B C 30 S10A,S00
15240A B C 30 S10A,S00
19000A B,D B 30 S10A,S11A,S00
19000A,Zone Model 401126 or 401127 B,D B 40 S10A,S11A,S00
19000A EVAC,Zone Madel 401126 B,D B 30 S10A,S11A,S00
GE Security ESL Compatibiliry Index-10/04 subjeci to change without notice Call FaxBack for latesi listings 800-483-2495
10
Federal Signal Corporation
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
Firelarm 2000 B CP01 25 S10A,S00
Firelarm 3000 B MF24A 30 S10A,S11A,S00
4000,Zone Model 5130-044-02 or 5130-044-03 B 01A 30 S10A,S11A,S00
4000,Zone Model 5130-044-04 or 5130-044-05 D 01A 30 S10A,S11A,S00
6000,Zone Model 5130-044-02 or 5130-044-03 B 01A 30 S10A,S11A,S00
6000,Zone Model 5130-044-04 or 5130-044-05 D 01A 30 StOA.S11A,S00
8000,Zone Model 5130-044-02 or 5130-044-03 B 01A 30 S10A,S11A,S00
B000,Zone Model 5130-044-04 or 5130-044-05 D 01A 30 S10A,S11A,S00
Fire Burglary Mstruments �Fa�il
All panels No 2-wire fire loops,use 4-wire models or ESL 505 2 to 4 wire converter module
Firecom, Inc.
Contiol Unit Description Loop Control Detectors ESL Compatability
Style Unit ID# Per Ci�cuit Identi/ier
8500,Zone Mode1791A D 021 15 S10A,S11A,S00
8500,Zane Mode1791VA D 022 15 S10A,S11A,S00
8500,Zone Mode1791B B 020 30 S10A,S11A,S00
8500,Zone Mode1791VB B 023 30 S10A,S11A,S00
Fire Control Instruments
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
FC-72,Zone Model VZM A,B VZM01 25 S10A,S11A,S00
FC-72,Zone Model ZDM A,B ZDM01 25 S10A,S11A,S00
FC-72,Zone Model ZDM-D A,B ZDMD01 25 S10A,S11A,S00
FC-72,Zone Model VZM D VZM01Z 20 S10A,S11A,S00
FC-72,Zone Model ZDM D ZDMD01 20 S10A,S11A,S00
FC-72,Zone Model ZDM-D D ZDMD01 20 S10A,S11A,S00
FC-ID,Zone Model CPD-ID A,B CPDID-1 1 S10A,S11A,S00
FC-ID,Zone Model SLM A,B SLMOt 10 S10A,S11A,S00
SBP-2,Zone Model SBP-2 A,B SBP01 25 S10A,S11A,S00
SBP-4,Zone Model SBP-4 A,B SBP01 25 S10A,S11A,S00
Firelite
Control Unit Description Loop Control Detectors ESL Compatibility
Sty/e Unit ID# Per Circuit Identifier
AE-1 or AE-2 with Zone Model ZAB B,D A 12 S10A,S11A,S00
MP-12 B A 20 S10A,S00
MP-24 B A 20 S10A,S11A,S00
MP-4424 B,D A 20 S10A,S00
MRF-4424 B,D A 20 S10A,S00
MS-124,MS-424 B A 20 S10A,S11A,S00
MS-4024 B A 20 S10A,S11A,S00
GESecurity ESL Compatibility Index-10/04 subjec[to change without notice Call FaxBack for latesi lisiings 800-483-2495
11
Firelite (Continued)
Contiol Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
MS-424A,Zone Model ANC-2B,CUG2 or WFC B,D A 25 S10A,S11A,S00
MS-4412B B A 20 St0A,S00
MS-4424B B,D A 20 S10A,S00
MS-4824,Zone Model IZ424 B,D A 20 S10A,S11A,S00
MS-5012 B A 20 S10A,S00
MS-5024 B A 20 S10A,S00
MS-5024UD:with or w/o CAC-10F B,D A 20 S10A,S00
MS-5210UD,Zone Model:with or w/o CAC-10F B,D A 20 S09A,S10A,S00,S11A,
MS-5224UD,Zone Madel B,D A 20 S10A,S00
MS-9200,Zone Model M302 B,D A 24 S09A,StOA,S00,S11A
Sensiscan 2000,Zone Model IZF-S or IZE-A B,D A 30 S10A,S11A,S00
Sensiscan 2000,Zone Model IZ-8F, B,D A 20 S10A,St 1A,S00
or IZE-AF,IZ-4F,IZ-4AF
5000,Zone Model IZ-BF or IMZ-A B,D A 25 S10A,S11A,S00
First Alert
Control Unit Description Loop Contro/ Detectors ESL Compatability
Style Unit ID� Per Circuit Identifier
FA200C B Household Fire 5 S09A,S10A,S11A
FA1200C B Household Fire 20 S09A,S10A,S11A
FA1500C B Household Fire 20 S09A,S10A,S11A
Gamewell
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit ldenfifier
FLEX 300,Zone Model Z2V D Z2V 25 S10A,S11 A,S00
FLEX 300,Zane Model Z3A D Z3A 25 S10A,S11 A,S00
FLEX 300,Zone Model Z46 B Z4B 25 S10A,S11A,S00
iNS-2,Zone Model 30774-02,or 30774-03 B Model No. 25 S10A,S11A,S00
ZANS 400,Zone Model Z1 B,D 30635 25 S10A,S11 A,S00
GE Security
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit ldentifier
Aritech-D 5000 B D5000A 20 S09A,S10A,S00
Aritech-D3000,OEM 48 A 20 S09A,S10A,S00
ESL 1501,Zone Model BMB,VTW ar ZEM B,D C01A 20 S10A,S11A,S00
ESL 1503,Zone Model BMB,VTW or ZEM B.D COtA 20 S10A,S11A,S00
ESL 1505,Zone Model BMB,VTW or ZEM B,D COtA 20 S10A,S11A,S00
ESL 1501,Zone Model BMB,VTW ar ZEM B,D COt 20 S10A,S11A,S00
ESL 1503,Zone Model BMB,VTW or ZEM B,D C01 20 StOA,St tA,S00
ESL 1505,Zone Model BMB,VTVU or ZEM B,D C01 20 S10A,S11A,S00
ESL 2500,Zone Model 2501 Zone 1 D 2500 20 S09A,S10A,S00
ESL 2500,Zone Model 2502-ZEM �CleanMe D 2500 20 S09A,S10A,S00
GE Security ESL Compatibility Index-10/04 subjeci fo change withoui notice Call FaxBack for latesi lisiings 800-483-1495
12
GE Security(Continued)
Control Unit Description Loop Control Defectors ESL Compatibility
Style Unit ID# Per Ciicuit Identi/ier
ESL 2500,Zone Model 2504-ZEM A 2500 20 S09A,S10A,S00 '
ESL 505,2 to 4 wire Converter Module �CleanMe B 20 S09A,S10A,S11 A,S00
Concord Hybrid,Zone Model 8Z Expander A 60-734 10 S09A
SnapCard 60-757 or 4A Input/2Z Output 60-756 ;
Concord AF16,Zone Mode18Z Expander A 60-792-95R-16Z 10 S09A
SnapCard 60-757 or 4A Input/2Z Output 60-756
Concord AF32,Zone Mode18Z Expander A 60-792-95R-32Z 10 S09A
SnapCard 60-757 or 4A Input/2Z Output 60-756
Concord Commercial,Zone Model 8Z Expander A 60-801 10 S09A
SnapCard 60-757 or 4A Input/2Z Output 60-756
Concord Express,Zane Model 8Z B 60-806-95R,60-806 10 S09A
SnapCard 60-757 or 4A Input/2Z Output 60-756
Concord Hybrid,Zone Model 8Z Expander with SnapCard A 60-734 10 StOA
60-757 or 10 60-756 and with 60-S10A-MOD
Concord RF16,Zone Model 8Z Expander with SnapCard A 60-792-95R-16Z 10 S10A
60-757 or 10 60-756 and with 60-S10A-MOD
Concord RF32,Zone Model 8Z Expander with SnapCard A 60-792-95R-32Z 10 S10A
60-757 or 10 60-756 and with 60-S10A-MOD
Concord Commercial,Zone Model 8Z Expander with A 60-801 10 S10A
SnapCard 60-757 or 10 60-756 and with 60-S10A-MOD
Concord Express,Zone Model 8Z Expander with B 60-806-95R,60-806 10 S10A
SnapCard 60-757 or 10 60-756 and with 60-S10A-MOD
Advent,Zone Model A 60-562 10 S09A
60-757,60-758,60-756 or 60-767 �CleanMe
Advent,no Zone Models �C1eanMe A 60-562 20 S09A
Advent w/Zone Models 60-757,60-758, A 60-562 10 S10A
60-756 or 60-767 and with 60-S10A-MOD �mleanMe
Advent,no Zone Models with a 60-S10A-MOD aCleanMe A 60-562 20 S10A
Moose-Z1200 B Z1200A 20 S09A,S10A,S00
Moose-Z2000 B Z2000A 20 S09A,S10A,S00
Moose-Z1250 A Z1250 20 S09A,S10A,S00
Moose-ZX200/210 A ZX200/210 10 S09A,S10A,S00
Maose-ZS300/310 A ZX300/310 10 S09A,S10A,S00
Moose-Z2000,Madel Z2000,Z1200 A ZX2000 20 S09A,S10A,S00
Moose-ZX400/410 A ZX400/410 20 S09A,S10A,S00
Moose-Model ZXEXP A 10 S09A,S10A,S00
NetworX NX-4 B 3800-0001 20 S09A
NetworX NX-6 B 3800-0001 20 S09A
NetworX NX-8&NX-S-CF B 3800-0001 20 S09A
NetworX NX-8E B 3800-0001 20 S09A
NetworX 8900 EUL B 3800-0001 20 S09A :
Harrington Signal
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unff ID A� Per Circuit Identi/ier
HS-2200 B,D 25 S10A
HS-2400 B,D 25 S10A
HS-3000B,with 281,481,BIN,BX,BXIN B 30 S10A
HS-3000V,with 261,4BI,BIN,BX,BXIN B 30 S10A
GE Security ESL Compatibility lndex-10/04 subject fo change without notice Call FaxBack for latest listings 800-483-2495
13
Honeywell, Inc.
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
DELTANET F&S,Zone Model AA A,B,C 001 25 S10A,S11A,S00
DELTANET F&S,Zone Madel AB D,E 001 25 S10A,S11A,S00
SENTARA 324,Zone Model W1065A A,B,C 006 20 S10A,S11A,S00
SENTARA 324,Zone Model W1065A D,E 006 20 S10A,S11A,S00
5900 Series A A 12 S09A
7000 Series B 7K8 10 S09A
ITI(see GESecuriryl
Johnson Controls, Inc. :
Control Unit Description Loop Control Detectors ESL Compatibilily
Style Unit ID# Per Circuit ldentifier
MULTIPLEX 5000,Zone Madel UZM D VZM01 25 S10A,S11A,S00
MULTIPLEX 5000,Zone Model ZDM D ZDM01 25 S10A,S11A,S00
MULTIPLEX 5000,Zone Model ZDM-D D ZDMD01 25 S10A,S11A,S00
MULTIPLEX 5000,Zone Model VZM A,B VZM01 20 S10A,S11A,S00
MULTIPLEX 5000,Zone Model ZDM A,B ZDMOt 20 S10A,S11A,S00
MULTIPLEX 5000,Zone Model ZDM-D A,8 ZDMD01 20 S10A,St tA,S00
SYSTEM 5000,Zone Model VZM D VZMOt 20 S10A,S11A,S00
SYSTEM 5000,Zone Model ZDM D ZDM01 20 StOA,S1 tA,S00
SYSTEM 5000,Zone Model ZDM-D D ZDMD01 20 S10A,S11A,S00
SYSTEM 5000,Zone Model VZM A,B VZM01 25 S10A,S11A,S00
SYSTEM 5000,Zone Model ZDM A,B ZDM01 25 S10A,S11A,S00
SYSTEM 5000,Zone Model ZDM-D A,B ZDMD01 25 S10A,S11A,S00
Land►s& GYR(MCC PowersJ
Conbol Unit Description Loop Contro/ Detectors ESL Campatibility
SYyle Unit ID# Per Circuit /dentifier
SYSTEM 600/fMS,Zone RCU/533-150 B,D 533150 18 S10A,S11A,S00 .
Mirtone
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit lD# Per Circuit Identifier '
7100,ar7112 B A 30 S10A,S11A,S00
7200 B A 30 StOA,S11A,S00
7200,Zone Mode17230 D A 30 S10A,S11A,S00
7600,or 7800 B A 30 S10A,S11 A,S00
7600,Zone Madel 7602 B A 30 S10A,S11 A,S00
7600,Zone Mode17630 or 7640 D A 30 S10A,S11 A,S00
7800,Zone Mode17602 B A 30 S10A,S11A,S00
7800,Zone Mode17630 or 7640 D A 30 S10A,S11A,S00
7900,Zone Models 79045-2,or 79045A-2TA B A 13 StOA,S00
7900,Zone Mode179044A D A 13 S10A,S00
79002U,Zone Model 79096U-2,79045-21A, B A 30 S10A,S11A,S00
79110,79110D,79111
GE Security ESL Compatibility Index-10/04 subject to change wiihout notice CaII FaxBack for latest listings 800-483-1495
14
Mirtone (Continued)
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuif Idenfi/ier
79008U,Zone Mode179096U-2,79045-21A, B A 30 S10A,S11A,S00
79110,79110D,79111
79029,Zone Mode179096U-2,79045-21A, B A 30 S10A,S11A,S00
79110,79110D,or79111
79030,Zone Mode179096U-2,79045-21A, B A 30 S10A,S11A,S00
79110,79110D,or 79111
79096U,Zone Madel 79096U-2,79045-21A, B A 3D S10A,S11A,S00
79110,79110D,or 79111
79500,Zone Mode179096U-2,79045-21A, 8 A 30 S10A,S11A,S00
79110,79110D,or 79111
79500U-CA,Zone Mode179096U-2,79045-21A, B A 30 S10A,S11A,S00
79110,79110D,or 79111
8000,Zone Models 8070,8071,8072,8073, B A 30 S10A,S11A,S00
8070A,8071A,8072A,8073A
8000,Zone Models 7630 or 7640 D A 30 S10A,S11A,S00
9200,Zone Models 8070,8071,8072,8073, B A 30 S10A,S11A,S00
8070A,8071A,8072A,8073A
9200,Zone Models 7630 or 7640 D A 30 S10A,S11A,S00
9200 Remote,Zone Models 7630,or 7640 D B 30 S10A,S11A,S00
9200 Remate,Zone Models 8070,8071,8072 B A 30 S10A,S11A,S00
8073,8070A,8071A,8072A,or8073A
9500,Zone Models 7630,or 7640 D B 13 S10A,S11A,S00
9500,Zone Models 8070,8071,8072, B A 13 S10A,St tA,S00
8073,8070A,8071 A,8072A,or 8073A
NIOOSe(see GE Security)
Napco Security Systems
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit lD# Per Circuit Identifier
MA-1000 Series B Household Fire 10 S09A
MA-1008 Series B Household Fire 10 S09A
MA-1010 Series B Household Fire 10 S09A
MA-1016 Series B Household Fire 10 S09A
MA3000 SERIES B MA3000A and 10 S10A,S00
MA3000B
MFA-6012,Zone Madel with B,D MF12A 10 S09A
or without CA6000
MFA-6024 Series,Zone Model with B,D MF24A 30 S10A,S11A,S00
ar without CA6000
S5500 SERIES B S5000A and 10 S10A,S00
S5000B
Gem-P3200 �CleanMe B 6EM-PS 10 S09A
Gem-P9600 � `""""` B GEM-PS 10 S09A
National Guardian
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit /dentifier
CONTROLINK 5200,Zone Models ZN-1, B,D D 15 S10A,S00
ZN-2,ZN-3
3100 Series,Zone Model 7433 B C 20 S10A,S00
GE Security ESL Compatibility Index-10/04 subject to change without notice Call FaxBack for latest lisiings 800-483-2495
15
NefinrorX(see GE Security)
Notifier '
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit Identi6er
AFC-90,Zone IZA424 B,D A 20 S10A,S00
AFM-200,Zone Model IMMX-2,or M3-TW B,D A 25 S10A,S00
AFP-1010,Zone Model IMMX-2,or M3-NV B,D A 25 S10A,S00
AFP-200,Zone Madel IMMX-2,or M3-TW B,D A 25 S10A,S00
AM-2020,Zone Model IMMX-2,or M3-TW B,D A 25 S10A,S00
SFP-2,SFP-4,SFP-6&SFP-8 B,D A 24 S10A,S11A,S00
SFP-400 B,D A 25 S10A,S00 :
SGL-1000,SGL-4000 B A 24 S10A,S11A,S00
System 500,Zone Model IZ-BF,or B,D A 20 S10A,S00
IZ-4F,IZE-AF,IZ-4AF
S500,Zone Madel IZM-8 or IZE-A B,D A 30 S10A,S11A,S00
S5000 ar S500,Zone Model IZM-8 or IZE-A B,D A 30 S10A,S11A,S00
XP Transponder,Zone Model XPM-8 B,D A 40 S10A,S00
4800,Zone Madel 2Z2W-A or 4Z2W-B B A 24 S10A,S11A,S00
4885,Zone Model 2Z2W-A or 4Z2W-B B A 24 S10A,S1 tA,S00
Optex Morse, Inc.
Conhol Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit ldentifier
G824 Series B 5000-04t18 10 S10A,S00
MDC Series No 2-wire fire loops,use 4-wire models ar ESL 505 2 ta 4 wire converter module :
Pem-All Fire Extinguisher Corporation
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit ldentifier
PEM-5000,Zone Model IMZ-8,IZE-A B,D A 30 S10A,S11A,S00
Potter Electric Signal Company
Conhol Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID A� Per Circuit ldentifier
PFC 100 B A 15 S10A,S00
PFC t00R,PFC-2000,PFC-4000 B,D A 25 S10A,S00
PFC 2000A B,D A 20 S10A,S00
System One/15,Zone Model BAIN,BAIXN, B,D PNV 30 S10A,S00
BBIN,BBIXN,BZAI,BZAIX,BZN-21AX,BZBI,BZBIX
System One/15,Zone Model VAIN,VAIXN, D PV 30 S10A,S00
VBIN,VBIXN,VZAI,VZAIX,VZBI,BZBIX,VZN-21AX �
Protectowire Company
Control Unit Description Loop Control Detectors ESL Compatibility
SYyle Unit ID# Per Circuit Identi/ier
ACR-1600,Zone Model ZM-2200 A,D ZM-2200 10 S10A,S11A,S00
GE Security ESL Compatibility Index-10/04 subjeci to change wiihoui notice Call FaxBack for latesi listings 800-483-2495
f6
Radionics, Inc.
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
D2012,Zone 1 A 10 S11A
D2012U,Zone 1 A 10 S11A
02112 with or w/o D125B A A 5 S09A,S10A,St 1A
D2112-01 10 S09A,S10A,S11A
D2212 B 5 S09A
D2212B,Zone 1 A 10 S11A
D2412,Zone 1 A 10 S11A
D2412U,Zone 1 A 10 S11A
D2412EU A 10 S11A
D2812 A A/B 5/15 S09A,S10A,S11A
D2812U,Zone 1 A 10 S11A
D4112 A B 12 S09A
D6112 A B 12 S09A
D7112,Zone Model D125,ar D1256(12V) A A 12 S09A
D7112,Zane Model D1256�24V� A A 48 S10A,S00
D7212,Zone Model D125,or D1256(12V) A A 12 S09A
D7212,Zone Model D1256�24V) A A 48 StOA,S00
D8112,Zone Model D125,or D125B(12V) A A 12 S09A
D8112,Zone Model D1256(24V) A A 48 S10A,S00 ,
D9112,Zone Model D125,ar Dt 25B�12V) A A 12 S09A
D9112,Zane ModeID1256124V) A A 48 S10A,S00
D9412 with or w/o D125B SO
DS22128 A A 10 S10A,S11A
D7412
Safetech, Inc.
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
S1000 B,D 40 S10A,S11A,S00
S1005 B 40 S10A
S1010 B 40 S10A '
S2000,Zone Madel CCA-1,CCA-3,or DZM B,D CO2 40 S10A,S11A,S00
S2000,Zane Madel DZS B,D CO2A 40 S10A,S11A,S00
S3000 1�IeanMe B,D 40 S10A,S11A,S00
Scantronic (USA), INC.
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
AV9000 Series,Zone FM2000 B Household Fire 20 S09A
ELB,Zone FM2000 B Household Fire 20 S09A
EL16,Zone FMZ000 B Household Fire 20 S09A
SC1600 Series,Zone FM2000 B Househald Fire 20 S09A
SC8000 Series,Zone FM2000 B Household Fire 20 S09A
GE Security ESL Compatibiliry lndex-10/04 subject to change without notice Call FaxBack for latesi listings 800-483-2495
17
�� � f
Securitylink/Ameritech
Conhol Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuii Identifier
AM-100 B Household Fire 20 S09A
SL 150 B Household Fire 20 S09A
Secutron
Control Unit Description Loap Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
MR-2900,with MR-2928 or 2938 B,D 40 S10A,S11 A
Silent Knight Security Systems
ConlrolUnitDescription Loop Control Detectors ESLCompatibility
Style Unit lD# Per Circuit ldentifier
2820,Zone Model 7181 A B 10 S10A,S00
4720,Zone Model 7181 A B 10 S10A,S00
5104,Zone Mode17181 A B 10 S10A,S00
5107,Zone Mode17181 A B 10 S10A,S00
5204�12V) A 12C 12 S10A,S00 :
5204�12V) A 12C 15 S11A
5204124V� A 24C 15 S10A,S00
5204124V) A 24C 15 S11A
5207,Zone Mode17181 A B 10 S10A,S00
5207�12V) A 12D 15 S10A,S00
5207(24V) A 24D 20 S10A,S00
5207,Zone Model 5210 B 24A 10 S10A,S11A,S00
5208 w/5217 Zone Expander B,D 24F 40 S10A,S11A
C6000 A 24EE 25 S09A,S10A,S11A,S00
C6000 B 24EE 25 S09A,S10A,S11A,S00 '
SK2224 B 24F 40 S09A,S10A,S11A,S00
SK4224 1CIeanMe B,D 24FF 30 S11A,S10A
SK6324 B 24F 30 S10A,S11A
Simplex-Grinnell(See TycoJ
Spectronics Corporation
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
320 or 324 Zone Model 320/LC/OS-24 B Model# 12 S10A,S00
624/MX,Zone Model ADS or MX/OSRP B Model# 12 S10A,S00
624/MX,Zone Model MX/OSH or MX/10-10H B Model# 20 S10A,S11A,S00
624/MX,Zone Model MX/10-10 B,D Model# 10 S10A,S11A,S00
640 or 641,Zone Madel MX8/WIB,OSS,S2 B Model# 12 S10A,S00
640 or 641,Zone Madel S2A D Model# 12 StOA,S11A,
640 or 641,Zone Model MX8/WIBH or S2W B Model# 20 S10A,S00
640 ar 641,Zone Madel S2WA D Model# 20 S10A,St 1A,S00
FASA,Zone Model FASA B,D Model# 20 S10A,S11A,S00
GE Security ESL Compatibility Index-10/04 subject to change wiihout notice Call FaxBack for latest lisiings 800-483-2495
18
.
Thorn Automated Systems
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID A� Per Circuit Identifier
FIREQUEST 100-12 B 10112A 7 S10A,S00
FIAEQUEST 100-24 B,D 10124A 30 S10A,S00
FIREQUEST 200,Zone Model 2ZX B,D 200A 22 S10A,S11A,S00
FIREQUEST 200,Zone Model 4ZX,4ZXD B 200A 22 S10A,S11A,S00
or COMM CONT REV.W
FIREQUEST 200,Zone Model U B,D 200X 22 S10A,S11A,S00
FIREQUEST 200,Zone Model MASTER HALON B,D 200A 22 S10A,S11 A,S00
FIREQUEST 200,Zone Model VSD B,D 200A 30 S10A,S11A,S00
FIREQUEST 300 B,D F2 20 S10A,S11A,S09A
K-101-24 B,D 10124A 30 S10A,S11A,S00
KDA-1000,Zone Model AIZ or AIZ-2 D 1000A 30 S10A,S11A,S00
KDR-1000,Zone Model BIZ,BIZ-2,BIZ-5 B 1000A 30 S10A,S11A,S00
KDR-1000,Zone Model DZM B 1000B 30 S10A,S11A,S00
KDR-1000,Zone Model MIZP B 1000C 30 S10A,S11A,S00
ryCO
Control Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
Simplex 2001-8001,Zone Model 2001-1017 or B Model# 15 S10A
2001-1019
Simplex 2001-8001,Zone Model 2001-1018 or D Model# 15 S10A
2001-1020 or 2001-1027
Simplex 2001-8005,Zone Model 2001-1017 or B Madel# 15 S10A
2001-1019
Simplex 2001-8005,Zone Model 2001-1020 or D Model# 15 S10A
2001-1027
Simplex 2120,Zone Models 2120-0523,2120-0535, B Model# 30 S10A,S11A, '
2120-7011 with 2120-0117
2120-7012 with 2120-0117,2120-7013 with 2120-0117
2120-7014 with 2120-0117,2120-7015 with 2120-0117
2120-7019 with 2120-0117,2120-7022 with 2120-0117
2120-7023 with 2120-0117,2120-7024 with 2120-0117
Simplex 2120,Zone Models 2120-7031 with D Model# 30 S10A,S11A,
2120-0117
2120-7032 with 2120-0117
Simplex 2120,Zone Models 2120-7031 with D Model# 30 S10A,S11A,
2120-7033 with 2120-0117
Zone Models,2120-7806,2190-9144,
2190-9145,2190-9153,2190-9154
Simplex 4001-9403,Zone Model 4001-9403 or B,D Model# 15 StOA
Simplex 4001-9403,Zone Model 4001-9813
Simplex 4001-9404,Zone Model 4001-9404 or B,D Model# 30 S10A,S11A,
Simplex 4001-9813,Zone Model 4001-9813
Simplex 4002,Zone Model 4002-5001, B,D Model# 15 S10A
4002-5002 or4002-7001
Simplex 4002,Zone Model 4002-5003, B,D Model# 15 S10A
4002-5004 or 4002-7002
Simplex 4100,Zone Model 4100-5001, B,D Model# 30 S10A,S11A,
4100-5002,4100-7001 or4100-7002
Simplex 4100,Zone Model 4100-5011,4100-5012, B,D Model# 30 S10A,S11A,
4100-7011
Wormald Autopulse 1000 B SZBt 50 S10A,S11A
GESecurity ESL Compafibility Index-10/04 subject to change without notice Cal/FaxBack for latesf listings 800-483-2495
19
.
TyCO (ContinuedJ
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit ldentifier
Wormald Autopulse 2000 B M661 50 S10A,S11A,S00
Wormald Autopulse 2000 D M6D1 50 S10A,S11A,S00
Wormald Autopulse 3000 B M681 50 S10A,S11A,S00
Wormald Autopulse 3000 D M6D1 50 S10A,S11A,S00
Wormald Autopulse 4000 B M2061 50 S10A,S11A,S00
Wormald Autopulse 4000 D M20D1 50 S10A,S11A,S00
Multizone 6P B M661 50 S10A,S11A,S00
Multizone 6P D M6D1 50 S10A,S11A,S00
Multizone 20M B M20B1 50 S10A,S11A,S00
Multizone 20M D M20D1 50 S10A,S11A,S00
Multizone 20P B M20B1 50 S10A,S11A,S00
Multizone 20P D M20D1 50 S10A,S11A,S00
Walter Kidde
Control Unit Description Loop Contro/ Detectors ESL Compatibility
Style Unit ID# Per Circuit Identifier
295100,Zone Model MIZP B,D 10124A 30 S10A,S1 tA,S00
295101,Zone Model MIZP B,D 10124A 30 S10A,St tA,S00
Westec
Conhol Unit Description Loop Control Detectors ESL Compatibility
Style Unit ID# Per Ciicuit ldentifier
MS-5000 Zone Model with or w/o MS5041/MS5042 A W 10 S10A,S11A,S00
Wormald US, Inc. (See TycoJ
GESecurity ESL Compatibility Index-10/04 subject to change wiihoui notice Call faxBack for latest listings 800-483-2495
20
�
� �
� —
...... �:��;,.,,;:; �,.,,.
ESL 500N Series
Low-profile two-and four-wire photoelectric smoke detectors
Overview
The ESL 500N series two-and four-wire conventional photoelectric
smoke detectors bring together trusted technology and a full line of
features to meet the demands of every type of application.The 500N
offers sounder models in two-and four-wire applications,specifically /
to meet residential code requirements.The 521 NCSXT has the
additional benefit of low current draw which makes it compatible with
a wide variety of control panels.The ESL 500N series also offers ��� ¢ ; �
choices for optional auxiliary relays and isolated heat sensors,not � 4 �
available before in the ESL 500 series. �
�f
ESL offers CleanMeO,dust compensation,field replaceable optical
chambers,multiple criteria heat algorithms,and self-diagnostics
features.
Outstanding Features
The ESL 500N series detectors work on the light-scattering principle.
A pulsed infrared light-emitting diode serves as the light source,and a
high-speed photo diode as the sensing element.This design has Standard Features
superior protection agains false/nuisance alarms caused by dust,
insects,AF,and ambient light.The proprietary optical chamber is field
replaceable. ° Built-in sounder available in two-and four-wire models
• Patented CleanMe�feature
A confirmed alarm causes the LED to light continuously.The unit • Built-in dust compensation
indicates trouble by flashing the LED every second.This meets the • Field-replaceable optical chamber
NFPA 72 field sensitivity testing requirements.Units with built-in
85dBa sounders emit a temporal 3 pattern when in alarm and will emit
a steady tone when ihe input power is reversed.
All wiring terminates in clamp-type screw terminals.The detectors
mount to a standard single-gang electrical box,a 4-inch octagonal
box,a 4-inch square electrical box,or WIREMOLD No.5739 fixture
box.
i �
Speciticar�ons
E/echica/ Environmental
•Power supply,6/12 V operation:6.0 to 20 VDC polarity sensitive •Operating temperature,thermal models:32 to 100°f�0 to 37°C)
•Power supply,12/24 V operation:8.5 to 33 VDC polarity sensitive •Operating temperature,nonthermal models:32 to 120°F�0 to 50°C)
•Maximum ripple p-p 16/12/24 V�:10%(V p-p) •Storage temperature:-4 to 158°F�-20 to 70°C)
•Typical average standby current:70 uA ✓` ✓ Operating humidity range:0 to 95%noncondensing
.Typical alarm current(6/12/24 V►:up to 60 mA max.if not limited by Physical
control panel •Detector head dimensions:5.5 in.(140 mm►dia.;2 in.�50 mm)high
•Auxiliary relay contacts:1.0 A C�?30 VDC;Form C •Mounting dimensions:5.25 in.(133 mm)dia.;0.3 in.(8 mm)high
•Alarm contacts:500 mA C�?36 VDC(resistive) •Weight:9.6 oz.(272 g)
Features •Construction:ABS plastic
•RFI immunity:20 V/m min.;1 to 1000 MHz Color:White head and base
•Field wiring size:12 to 24 AWG;16 to 22 recommended Packaging:10 detectors per carton
,Heat detector,rate of rise:15°F/min(8.3°C/min)and>105°F Regulatory
(40.6°C) •UL,CUL,CSfM
•Heat detector,fixed threshold:135°F(57.2°C)
•UL 2-wire compatibility identifiers:S10A,S11 A
•Drift compensation adjustment:1.0%ft.max.
•Reset time:1 sec.min.
•Photoelectric sensitivity:3.1%+0.5 to 1.0%
Related Diagram Ordeiing Infom►ation
521 NCRXT 2-wire,CleanMe,heat sensor,aux.relay,8.5 to 33 VDC,
S11A
521 NCSXT 2-wire,CleanMe,heat sensor,sounder,8.5 to 33 VDC,
S10A
521 NCSRXT 2-wire,CleanMe,heat sensor,sounder,aux.relay,8.5 to
33 VDC,S11A
� --� � �-- , �. 541 NB 4-wire,6 to 33 VDC
� E JI I 1 1 1 I I� ,�
N o� `r 541 NBXT 4-wire,heat sensor,6 to 33 VDC
v � �� / / ; 541 NCSRXT 4-wire,heat sensor,sounder,aux.relay,8.5 to 33 VDC
� --_
541NCSXTE 4-wire,heat sensor,sounder,end of line relay,8.5 to 33
VDC
541 NCSRH 4-wire,isolated heat sensor,sounder,aux.relay,8.5 to
33 VDC
541 NCRXT 4-wire,heat sensor,aux.relay,8.5 to 33 VDC
541 NCXTE 4-wire,heat sensor,end of line relay,8.5 to 33 VDC
541 NCSXT Photoelectric 4-wire smoke detector,sounder,8.5 to 33
VDC
��� 503-665-5700 Asia Europe
�S[,(�,� GESgCp�/fi/ 888-G6SECURITY te1652-2907-8108 te1+44-113-238-1668
� (437-3287) fax 652-2142-5063 fax+44-113-253-8121
faxback 800-483-2495 Australia Latin America
emailinfoQgesecuriry.com te1+61-3-9259-4700 te1305-267-4301
www.GESecurity.com www_gesecurity.com fax+613-9259-4799 fax305-267-4300
As a comparry of innovation,GE Securiry reserves[he right m change pmduct specifications wiMout notice.Por the latest pmduct specifications,visit GE Securiry online at www.GESeariry.com or contaci your GE Security sales representative.
IPS-ESL 500N Series-2005-04-27 03:55:47 Neleased:D.042005
� ,
ESL 500 Series Note
Please refer to the ESL Compatibility Index for a complete
S m o ke Detecto r 1�sting of p trol panels and proper identifiers.For a copy
of the Com atibili Index,call 1-800-648-7424 or visit
www.sentrol.com for a copy to down load.Remember,
Installation Instructions 4-wire smoke detectors do not require a
comparibility listing.
Description A WARNING
This document is intended for licensed electricians/
The ESL 500 Series Smoke Detectors offer 2-wire,4-wire,12VDC, alarm installers.Interlogix csnnot provide technical
and 24VDC detectors for fire system applications. support to unqualified persons.
Depending on the model,the smoke detector pmvides the following
features: If you have questions,call Interlogix st 1-800-648-7424.
Detector/base lock
Discourages unauthorized removal of the smoke detector by requiring Selecting a Location
a screwdriver to remove the detector from the base. Selecting a suitable location is critical to the operarion of smoke
C1eanMe� detectors.T'his equipment should be installed in accordance with
Enables the control panel to receive a waming signal via a 505 the National Fire Protection Association's(NFPA)Standard 72.
module,or C1eanMe compatible panel,indicating that the optical A-8-1.2.1.a Where to Locate the Required Smoke Detectors in
chamber needs to be replaced.This feature is available on the 521/ Existing Consnuction.The major threat from fire in a family
528 Series 2-wire detecto�only. living unit occurs at night when everyone is asleep.The
The detecto�ship with the C1eanMe feature tumed off.To tum on principal threat to persons in sleeping areas comes from fires in
the CleanMe signal move DIP switch 2 on the back of the detector to �e remainder of the unit.Therefore,a smoke detector(s)is best
the"on"position.See Figure 1. located between the bedroom areas and the rest of the unit.In
units with only one bedmom area on one floor,the smoke
o" l /��\ detector(s)should be located as shown in Figure 2 A.
1.On=A(6-12V)range � G /.-'��� ' In family living units with more than one bedroom area or with :
Off=C(12-24V)range � �'�� bedrooms on more than one floor,more than one smoke detector
�
z.o�=CleanMe signal on i is required,as shown in Figure 2 B.
OR=CIeanMe signal ofl I �i .
(521/528 Saries only) �\ I
�o o�
Note � NO COM NC / '
Tuming the CleanMe signal � �
on witlaut usfng fhe 505 �
module and/or compatible ��
penel will aeete a trouble Relay(CRXT)unit only Dining Kipy�en gedrop� Bedrop� .
� signal. R� � �
Correct Incorrect 2 A �
•
Figure 1.Switches u��R� �,�,,,
�
Self�tiagnostics
Includes automatic sensirivity testing.Once a day and immediately
upon first power up,each 500 Series detector performs a full N� a� �' �°`°°m
diagnostic test that includes a dynamic test of the sensing chamber � '
and internal electronics.This meets NFPA 72 field sensitivity testing Z e �
requirements without the need for external meters. `"'"B`�°°"' �°'°°'"
• �
Drift compensstion
The detectors automatically adjust sensitivity,up to a ma�cimum of eaa�m
1.0%/ft.,as the detectors become dirty. �
Using the 2-wire 521/528 Series with a panel that does not have 2-
wire capabilities :
The ESL 505 module can convert the 2-wire 521/528 Series to a 4-
wire input on the control panel.The 521/528 Series is UL Listed as
compatible with the 505 module and will be fully UL compliant with � • ��
any UL listed 24 VDC control panel and panels that do not operate 2 c ��� '��
below 12V.Each 505 module will accommodate up to 20 ESL 521/ •
528 Series smoke detectors.See the 505 module installation a�"m° i °ia"�
instructions for more information. !
Selectable voltage range for UL 2-wire compa6bility ea��c '
1'he 500 Series 2-wire smoke detectors have a DIP switch that allows
the installer to choose between 12/24V operation and 6/12V �=Required srtake deteGors
operation.See Figure 1 and Specifications. �_�d�ba,ai s�ace deieao�s�y��red r���co�sw�o�
Figure 2.Detector placement
ESL 500 Series 1
In addition to smoke detectors outside of the sleeping areas,the Installing the Detector
installation of a smoke detector on each additional story of the family All wiring must conform to the Narional Electric Code(NEC)
living unit,including the basement,is required.These installations and/or local codes having jurisdiction.Use 12 to 24 AWG wire
are shown in Figure 2 C.The living area smoke detector should be to install the detector.
installed in the living room or near the stairway to the upper level,or
in both locations.The basement smoke detector should be installed in 1. If you are using the detectodbase lock,remove the detector
close proximity to the stairway leading to the floor above.Where ��kout and break off the tab on the mounting base.See
installed on an open-joisted ceiling,the detector should be placed on
the bottom of the joists.T'he detector should be positioned relative to Figure 3.
the stairway to intercept smoke coming from a fire in the basement 2• Remove the red plastic cover from the detector.The
before the smoke enters the stairway. detector is shipped with a cover for protection against
construction site dust.
A-B-I.Z.I.b Where to Locate the Required Smoke Detectors in New
Construction.All of the smoke detectors specified in A-8-1.2.1.a for 3. Run system wiring to the detector location and mount
existing construction are requued and,in addition,a smoke detector electrical boxes if necessary.
is required in each bedroom. 4. Line up and attach the gasket(if the detector comes with a
gasket)and mounting base to the electrical box,wall or
A-S-1.2.1.c Are More Smoke Detectors Desirable? ceiling using the screws provided.Use the wall anchors if
The required number of smoke detectors might not provide reliable necessary.See Figure 5.
eady warning protection for those areas separated by a door from the 5. Strip the system wires and connect them to the appropriate
areas protected by the required smoke detectors.For this reason,it is
recommended that the householder consider the use of additional ���nals on the detector.See Figure 6.
smoke detectors for those areas for increased protection.The 6. Attach the detector to the mounting base as follows:
additional areas include the basement,bedrooms,dining room, -Line up the raised tab on the side of the detector with the
furnace room,utility room,and hallways not protected by the arrow on the mounting base.See Figure 4.
required smoke detectors.The installation of smoke detectors in -Insert the smoke detector into the base and turn
kitchens,attics(finished or unfinished),or garages is not normally clockwise approximately 15 degrees.It should snap
recommended,as these locations occasionally experience conditions firmly into place.
that can result in improper operation '7. Apply power.
Important:Regulations pertaining to smoke detector installations g• Test the detector.See Smoke Testing the Alarm.
vary from state to state.For more information,contact your local fire
departrnent or local authority having jurisdiction.
In addition to NFPA 72,use the following location guidelines to
optimize performance and reduce the chance of false alarms from the ,
detector: � � ���
�����
���^�
• Locate ceiling-mounted smoke detectors in the center of a room ' � ?�
or hallway at least 4 inches(lOcm)from any walls or partitions. �
• Locate wall-mounted smoke detectors so the top of the detector
is 4 to 12 inches(10 to 30cm)below the ceiling. ,���1�
�' �,`�
• Do not locate detectors in or near bathrooms or kitchens. � �
�
• Locate in a suitable environment as follows:
-Temperature between 32°F(0°C)and 100°F(37°C)
-Humidity between 0 and 95%non�ondensing
Figure 4.Mounting
• Locate away from air conditioners,heating registers,and any
other ventilation source that may interfere with smoke entering
the detector.
• Mount smoke detectors on a firm permanent surface.
Smoke Testing the Detector
Smoke detectors should be tested in place annually using smoke
♦ or canned aerosol simulated smoke. Follow the instructions on
�_�� the canned smoke or use the following steps to test the detector
'������-, with smoke:
�������`
I r ��'����
� * 1. Hold a smoldering punk oc cotton wick close to the smoke
entry openings. '
2. Gently direct the smoke into the detector for 20 seconds or
�_�_� untii an alarm is indicated.
�—�
`
Be sure to extinguish the smoke source after testing! The
--" detector LED should stay on and an alazm should be indicated at
Figure 3.DetectoNbase lock the control panel. Use the system reset switch to reset the
detector.
2 ESL 500 Series
Models without gaskets: Models with gaskets:
511 C,511 AFT,518C,518AFT,521 B, 521 CRXT,528CRXT,541 C,541 CXT,
521 BXT,528B.5286XT 541 AXT,548C,548CXT,548 AXT
� � �.�
� >� � - �
� � x
� '9' � ������i �' ,����'�'��,'-. � `1
� �' �`'.�. � ;
� �� �� � �� ��, �� ��
�
� ry f �
: \ �� I'/ syny �/
. /// � - /�� � � / � �F..`� �
� :/ ���
/, � �//, �
Figure 5.Detector installation
511/518/521/528 Series 2-wir+e wiring diagram
2-wire O EOL .
initiating + Device
CIlCUIf — O .
� Listed Alartn Control O O �O O
— + _ �.
Note:The 521/528 Series are polarity sensitive. Model 511G518C Model 521CRXT/528CRXT
511AFT/518AFT �
Note:The 511/518 Senes are not CleanMe First Last �
compatible. Detector 5218/5288 pet�a �
521 BXT/5288XT � p O -
AWaming:The system may not operate if the �
detector is not connected to the control unit -
initia6ng device dreuit as spedfied in the .
detector a control unit IiteraW2.
541/548 Series 4wire wiring diagram
ESL
2D4-12l24V �.
Power
Power + Supervision .
_ O O O O Relay
— f- — +
Listed PJarm Conirol Model 541 C/548C
541AXT.548AXT Mode1541CXT/548CXT
Note:The 541/548 Series are not First Last �
CleanMe compatible Detector O Detec[w O O❑ ..
Initiating O �
Circuit O
EOL Resistor �
Figure 6.Wiring diagrams
Understanding the LED Removing the Detector
The LED on the detector indicates the status of the detector as To remove the detector from the mounting base,grasp the :
follows: detector and turn it counterclockwise appro�cimately 15 degrees.
F7ashing every 9 seconds=Normal operation. The detector should snap off of the mounting base.
On=Detects smoke,sending an alarm.
Off or flashing once every 1.5 seconds=Trouble or maintenance To remove the detector from t6e mounNng base when the
is required.Test the detectoc See Testing the Detector Sensitivity. detectodbase lock is used,insert a small screwdriver into the
locking tab slot on the side of the base and press in while simulta-
neously turning the detector counterclockwise I S degrees. See
Figure 8.
ESL 500 Series g
Testing the Detector Sensitivity
The detector provides a sensitivity test that allows you to check the '
detector sensitivity using a test magnet and the LED indicator on the j�� \
detector as follows: � �� �
1. Hold the test ma et u to the raised TEST letters on the to of
% V`�
� p p p
the detector for 2 seconds. See Figure 7. Once the test starts, I �
\ /
the alarm LED flashes one to nine times. �> �
2. Count the number of times the LED flashes and use the
following table to determine the status of the detector sensitivity Figure 7.Testing the detector
and what action to take,if any.
Flashes Obscuration Indication Action
(Approx)
1 NIA Unserviceable Reset unit and rerun
hardware fault sensitivity test.If the error
detected. persists,replace the unit.
2-3 N/A Detector is not Clean the unit.Reset unit
sensitive enough. and rerun sensitivity test. —
If the error persists,
replace the unit. �
4 3.6%/ft Detector is within N/A
5 3.1%/ft normal sensitivity
range. j/,l_�
6 2.6%/ft �'
7 2.1°/a/fl � ��
8-9 N/A Detector is too Verify that the smoke �
sensitive. chamber is snapped --
down securely.Clean unit.
After the test: Figure 8. Unlocking the detector
If the sensitivity is within timits and all other tests pass,the
detector goes into alarm and must be reset from the control panel.
If the sensitivity is not within limits or an unserviceable hardware
fault has been detected,the detector LED flashes every 1.5 seconds
until the detector is serviced. t,
�
Cleaning the Detector � ;�__L
Clean the detector cover with a dry or damp(water)cloth as needed F
to keep it free from dust and dirt. f / �
When necessary,clean the detector interior and replace the optical �__
chamber as follows:
1. Disconnect the alarm notification appliances,service release
devices and extinguishing systems. Figure 9.Removing the detector cap
2. Slide a flat-blade screwdriver into the slot on the detector cap
and gently push the handle down to pry the cap up and off. See
Figure 9.
3. Press in on the sides of the optical chamber and pull it up and
away from the detector and discard. See Figure 10.
4. Use a vacuum to remove dust and diR from the optical chambe�
base.
5. Line the new optical chamber up with the optical chamber base
and snap it down into place. oPUCai cr,amne�
6. Replace the detector cap as follows:
-Line the tabs on the cap with the slots on the detector.
-Insert the cap into the smoke detector and turn clockwise Optical chamber base
approximately 15 degrees. It should snap firmly into place.
7. Test the detector sensitivity(See Testing the Detector
Sensitiviry). �it�T 1
8. Reconnect all alarm notification appliances,service j` �— Detector cap
release devices and extinguishing systems.
Important:The control panel alarm and all aiixiliary functions
should be verified for a complete test of the system. Figure 10.Removing the optical chamber
4 ESL 500 Series
Maintaining the Detector Limited Warranty
These smoke deteCtors are designed for easy field Service and ESL is a brand name of Interlogix,Inc.The manufacturer wacrants this
maintenance. When installed and used properly,they require smoke alarm to be&ee from defects in material and workmanship under
minimal maintenance. conditions of normal use for a term of 3 years from the date of mauufacture.
During the wartanty period,if an Interlogi�c product or any of its compo-
The smoke detector should be tested monthly. See Testing the nents becomes defective,it will be repaired or replaced without chazge.
Detector Sensitivity and Smoke Testing the Detector. Out-0f-warranty units will be repaired at the discretion of the manufacturer,
if not,a card will be forwarded to the customer suggesting a replacement
Fire Prevention and Esca @ unit and che cosc of that unit.
P This warranty does not apply to units which have been subject to abuse,
The pwpose of an early warning smoke detector is to detect the presence of misuse,negligence or accident,or to which any modifications,alterations
fire in its early stages and sound an alarm giving the cecupants time to exit oc repairs have been made or attempted.
the premises safely. This warranty is extended only to the original purchaser of the smoke alaRn
and may be enforced only by such person.During the warranty period,if
Avoid Fire Hazards the alarm or any warranted components thereof becomes defecrive,at the
No detection device can procect life in all situations.Therefore,safeguards manufacturer's discretion,it will be replaced or repaired without chazge if
should be taken to avoid potentially dangerous situations as follows: retumed in accordance with the following inshuctions:
• Do not smoke in bed. Obtain a Retum Authorization Nutnber by calling 1-800-648-7422 or 503-
• Do oot leave c6ildren home alone. 692-4052,then carefully pack it in a well padded and insulated carton and
• Never clean with flammable liquids such as gasoline. retum,postal charges prepaid to:
• Properly sWre materials.Use general good housekeeping techniques to Customer Service ;
keep your home neat and tidy. A cluttered basement,attic,or ofher Interlogix,Inc.
storage area is an open invitation to fire. 12345 SW Leveton Drive
'15�alatin,OR 97062-9938
• Use combustible materials and electrical appliances carefully and only A note should be included advising the nature of fhe malfunction.Caze
for their intended uses.Do not overload electricaloutlets. must be exercised in the ro r kin of alamis retumed under fhis
P Pe P� B
• Do not store explosive and/or fast burning materials in your home. W,�ty as Interlogix will not be responsible for warranty repairs to
• Even after proper precautions ttave been taken,fires can start. equipment damaged because of improper packing.
�p�Pa�, T6e above warranty is in lieu of all other eapress warranties,aod
impGed warrantles of inerchantability and fitness for a particular
purpose are timited in duration for a period of 3 years from the date of
In Case of Fire manufacture.Under oo circumstances shall manufacturer be liable to
In the event of a fire,you should do the following: the purchaser or any other person for iucidental or wnsequential
• Leave immediately.Dodt stop to pack or search for valuables. damages of any nature,including without limitation damages for
• In heavy smoke,hold your breath and stay low,crawl if necessary.The personal injury or damages to property,and however occasiooed,
clearest air is usually near the floor. whether alleged as resulting from breac6 of warranty by maaufac-
• If you have to go through a closed door,carefully feel the door and door ��y the negligence of manufacturer or otherwise.Manufacturer's
knob to see if undue heat is present. If they seem cool,brace your foot �ability will in oo event eaceed the purc6ase price of the produc�Some
against the bottom of the door with your hip against the door and one states do not allow IimitaHons on how long an implied warranty Iasts,
hand against the top edge.Open it slightly.If a rush of hot air is felt, or the eaclusion or limitatiou of incidental or consequenHal damages,
slam the door quickly and latch it. Unvented fire tends to build up �the above limitations and exclusions may not apply to you.Unless a
considerable pressure.Be sure all membeis of the household realize and �ooger period is required by applicable law,any acHon against
understands this dangec manufacturer in connection with this smoke slarm must be commenced
• Use your neighbor's phone or a street fire alarm box to call the fire �thin one year after the cause of acHon has occurred.
deparfinent.The job of extinguishing the fire should be left to the No agent,employee or representative of the Manufacturer nor any other
professionals. person is authorized to modify this warranty in any respect.Repair or
replacement as stated above is the exclusive remedy of the purchase
hereunder.This warranty gives you specific legal rights and you also have
Be Prepared other rights which vary from state to state.
Practice the following steps to prepaze you and your family in the event
of a fire: WARNING
• Perform fire drills regularly.Use them to asswe recognition of an alazm Limitations of smoke detectors
signal. Smoke detectors aze very reliable,but may not work under all condirions.
• D�aw a floor plan and show two exits&om each room.It is important No smoke detector provides total protection of life or property.Smoke
that children be instructed carefully,because they tend to hide in times detectors are not a substitute for life insurance.
of crisis. Smoke detectors require a source of power to work.
• Establish one meering place outside the home.Insist that everyone meet This smoke detector will not operate and the alarm will not sound if the
there during an alum.This will eliminate the tragedy of someone detector is not installed properly.
reentering ihe house for a missing member who is actually safe. Smoke detectors may not be 6eard. A sound sleeper or someone who has
• If you have children and/or physically challenged people residing in �ken drugs or alcohol may not awaken if the detector is installed outside a
yow household,use window decals to help emergency personnel ��m.Closed or partially closed doors and distance can block sound.
identify the sleeping quarters of these individuals. This detector is not designed for the hearing impaired.
Smoke detectors may not always activate and provide waming early
enough.Smoke detectors only activate when enough smoke reaches the
AWARNING detector.If a fire starts in a chimney,wall,roof,on the other side of closed :
Smoke detectors CANNOT provide warnings for fires resulting doors,or on a different level of the property enough smoke may not reach
from eaplosions,smoking in bed or other fumiture,ignitioo of �e detector for it to alarm.
flammable tiquids,vapors and gases,children playing with Smoke detectors are a significant help in reducing loss,iajury and even :
matches or lig6ters. death.However,no matter how good a detection device is,nothing
works perFectly under every circumstance and we must wam you that .
Failure to properly install,test,and maintain a smoke detector you cannot eapect a smoke detector to ensure that you will never suffer
system may cause it to fail resulHng in loss of life and/or aoY damsge or injury.
PraPerty•
ESL 500 Series 5
, .. , ,
Specifications
Voltage DIP switch 1 ON for standard 12V operation(6.5-20 VDC),polarity sensitive '
DIP switch 1 OF'F for standard 24V operation(8.5-33 VDC),polarity sensitive
Ma�cimum ripple(pk to pk) 10%(V p-p)
Typical average standby current 70 uA(12/24V) :
Typical alarm current(12/24V) up to 60mA max.if not limited by control panel
Awc.relay contacts 2A @ 30VDC
Alarm contacts SOOmA @ 36VDC(resistive)
Photoelectic sensirivity 3.1%+0.5- 1.0%
Operating termperature 32°to 100°F(0°to 37°C)
Operating humidity range 0 to 95%non-condensing
RFI immunity 20V/m minimum;0-1000MHz
Color white head and base
Field wiring size 12-24 AWG
Detector packaging 10 detectors per carton
Heat detector specifications rate of rise- 15 F/min and>105 F(83 C/min and>40.6 C)
UL 2-wire compatibility identifier:
521/528-DIP switch 1 ON S09A
521/528-DIP switch] OFF S10A,S11A(RX models)
511/518 S10A
Drift compensation adjustment 1.0%/ft.max
Detector head dimensions 5 in.(12.7cm)diameter;2 in.(Scm)height
Mounting dimensions 4.75 in.(121 cm)diameter,0.3 in.(O.8cm)height
Reset time I second minimum
Listings:
511/521/541 UL 268
518/528/548 ULC
Product Ordering
Model Description
511 C/518C 2-wire,photcelectric,6.5-33 VDC
S11AFT/518AFT 2-wire,photoelectric,6.5-33VDC,rate of rise heat sensor
521B/528B 2-wire,photoelectric,6.5-33VDC
521BXT/528BXT 2-wire,photoelectric,8.5-33VDC,multi-criteria algorithms,fixed/rate of rise heat
521CRXT/528CRXT 2-wire,photcelectric,8.5-33VDC,awc.relay,multi-criteria al orithms,fixed/rate of rise heat
541G548C 4-wire,photcelectric,8.5-33VDC
541CXT/548CXT 4-wire,photoelectric,8.5-33VDC,multi-criteria algorithms,fixed/rate of rise heat
541AXT/548AXT 4-wire,photcelectric,6-20VDC,multi-criteria algorithms,fixed/rate of rise heat
Accessories:
505 Module that interprets the 521/528 models C1eanMe signal for panel and can conveR 2-wire
521models to 4-wire inputs on the paneL
401 Test magnet in plastic shell for pole mounting
SM-200 Smoke!in a can�(canned smoke)for functional testing of smoke detectors
211 Replacement optical chambers(set of 10)