Apri130, 2004
Re: Creation of Classroom/Media Room in Basement, type E use
913 Nebraska St
File#L6-31-0404
The above-reference plans have been stamped CONDITIONALLY APPROVED based upon
review for conformance to the current edition of the Wisconsin Administrative Building and
Heating, Ventilating and Air Conditioning Code, chapters COMM 61-65. These plans have
NOT been reviewed for conformance to the Plumbing Code (ch. COMM 16) and any COMM
code not specifically mentioned. This approval is not a Building Permit. Necessary city permits
must be secured before commencing work.
You are hereby advised that the owner, as defined in Chapter 101.01 (I) of the Wisconsin State
Statutes, is responsible for all code requirements not specifically cited herein. Code requirements are
set forth in Chapters 61 through 65 of the rules of the Department of Commerce.
The building will be inspected during construction and a final inspection will be made after
completion to insure compliance with city and state codes.
The architect, professional engineer, builder or owner shall keep at the building as evidence of
approval, one set of plans bearing the stamp of approval.
COMM 64.0004 This approval does not include heating and ventilating. Such plans are required to
be submitted and approved prior to installation of such equipment.
COMM 62.2702.2.4 Provide emergency illumination per 1003.2.11.2.
COMM 11/ICC/ANSI 701.1 Visual notification devices shall be provided for the fire alarm system
in this area of remodeL
COMM 907.2.3 Provide manual pull stations at the exits from this floor level if not already present.
COMM 1004.3.2 Corridors for more than 30 occupants shall be one hour rated. Provide revisions.
COMM 1004.2.4 Provide evidence that the exit access travel distance has been provided.