Approved: November 1, 2013
Issued: November 1, 2013
Century Oaks Homes LLC
2748 Holiday Ct
Neenah, WI 54956-9011
CERTIFICATE OF OCCUPANCY
An Occupancy Permit is hereby granted for the new 34 unit CBRF located at 1816 Vinland Street,
Oshkosh, Wisconsin 54901 as described in Building Permit Application number(s) 155249.
Project Description: New 34-unit CBRF
Major Occupancy: Institutional
Location: C-1 Neighborhood Business District
Construction Classification: Type VA
Total Square Footage: 28,491 sq ft
Sprinkler Design: NFPA- 13
LIMITATIONS: Maximum persons and/or living units: per approved plans
NOTES:
1) Copies of inspection results are available upon request in room 205, City Hall.
2) Future permits may be required for additional work to your property.
3) It is highly recommended to contact our office to verify allowable occupancy uses prior to any change
in tenant/ownership of the building.
A new Certificate of Occupancy shall be required prior to occupancy, should additional building(s) be
erected, or should any buildings mentioned above be altered or moved. The use of land, or buildings,
shall not be changed until a Certificate of Occupancy is issued for that occupancy. All conditions noted
above must be complied with in order for this certificate to be valid.
Bui ing Systems Inspector
CC: Ganther Construction
Suburban Electrical Engineering Inc
Christensen Heating &A/C Inc
O'Neill Enterprises Inc
JFZ/smw
s
Building Permit Work Card
Job Address 1816 VINLAND ST _ __ Permit Number 0155249 Create Date 4/23/2013
Owner __ ___ _ _ Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family Plan Z3-3736-0413
Occupany Permit Required Flood Plain _ Height Permit _ Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF"Per state approved plans Trans ID 788841
of Work
HVAC Contr _ _ Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 09l16/2013 01:OOPM Type Footings Inspector John Zarate approved
ono tube inspection between 1-2pm today
I
� I
Date/Time requested: 9/16/2013 11:38 AM Notice Type: Ready Date/Time: 09/16/2013 01:OOPM
Access: �� —
Requested By: GANTHER CONSTRUCTION Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
- ---------- ------------------------- pp------
Date/Time Inspected 10/28/2013 10:OOAM Type Final Inspector Tom Spierowski a roved
ill be ready for final inspection by Tuesday, 10/28
all received from request line �
,
Date/Time requested: 10/25/2013 10:59 AM Notice T e: Read Dat I
YP y e/Time: 10/28/201310:OOAM
Access: anther Construction _ - —�
Requested By: GANTHER CONSTRUCTION Phone Number: 376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---------------------------------------------------- ------------------ ---------------------
Page 9 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 0155249 Create Date 4/23/2013
Owner Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family __ _ Plan Z3-3736-0413
Occupany Permit Required Flood Plain _ Height Permit ___ Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF*Per state approved plans Trans ID 788841
of Work
HVAC Contr _ _ _ Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 08/22/2013 09:30AM Type Rough In Inspector Tom Spierowski approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE CENTER CORE
�
i
Date/Time requested: 8/21/2013 04:59 PM Notice Type: Ready Date/Time:
I--- -- --- — — —
— - - —
ccess: - --�
-- — �
Requested By: GANTHER CONSTRUCTION-AI _ Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
-------- ----------------------------------------------------------------------
Date/Time Inspected 08/27/2013 01:OOPM Type Insulation Inspector John Zarate no time
Insulation ready for inspection on center section of building —
I
I I
� �!
Date/Time requested: 8/27/2013 07:30 AM Notice Type: Ready Date/Time: 08/27/2013 01:OOPM
Access: i, --
Requested By: GANTHER CONSTRUCTION _ ____ phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------------------------------- --------------------
Date/Time Inspected 09/10/2013 10:OOAM Type Abv Ceiling Inspector Tom Spierowski approved
REQUEST LINE/READY FOR AN ABOVE CEILING INSPECTION FOR THE CENTER CORE
"WOULD LIKE INSPECTION TUESDAY(9/10)AFTER LUNCH**
Date/Time requested: 9/9/2013 03:14 PM_ Notice Type: Ready Date/Time 09/10/2013 10:OOAM
Access: —— —
� _
�--� - - � �
Requested By: GANTHER CONSTRUCTION-AI Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---- ---------------------- ------------------ --------------------------------------------
Page 8 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST __ _ Permit Number 0155249 _ Create Date 4/23/2013
Owner _ _ __ Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family ___ Plan Z3-3736-0413
Occupany Permit Required Flood Plain __ Height Permit _ Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF'Per state approved plans Trans ID 788841
of Work
HVAC Contr Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 08/16/2013 10:OOAM Type Insulation_ Inspector Tom Spierowski__ approved
REQUEST LINE/READY FOR AN INSULATION INSPECTION
I '*WOULD LIKE INSPECTION FRIDAY(8/16)MORNING-PLEASE CALLAL WITH THE RESULTS " I
�-SW wing except end 2-rooms-- ;
I I
I
Date/Time requested: 8/15/2013 11:29 AM Notice Type: Ready Date/Time:
Access: i
Requested By: GANTHER CONSTRUCTION-AI Phone Number: (9200 376-0218
0 Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---- --------- -------------------
- pp-------
Date/Time Inspected 08/21/2013 08:30AM Type Insulation _ Inspector Tom Spierowski _ a roved
REQUEST LINE/READY FOR AN INSULATION INSPECTION FOR 2 MEZZANINES AND 1 UNITS �
I �'WOULD LIKE INSPECTION WEDNESDAY(8/21)MORNING*' i
,I
Date/Time requested: 8/20/2013 02:08 PM Notice Type: Ready Date/Time: I
Access: I-.---__ - —-.—_—_ -- I
Requested By: GANTHER CONSTRUCTION-AI _ Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
-----------------------------------------------
Date/Time Inspected 08/21/2013 08:30AM Type Rough In Inspector Tom Spierowski approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE CANOPY
'"WOULD LIKE INSPECTION WEDNESDAY(8/21)MORNING" '
�
�_ �
Date/Time requested: 8/20/2013 02:08 PM Notice Type: Ready Date/Time:
Access: -- — — —
Requested By: GANTHER CONSTRUCTION-AI __ _ Phone Number: (920)376-0218
� Reinspect Fee 0 Fee Waived ❑ Reinspect Fee Paid
-----------------------------------------------------------------------------------------
Page 7 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 0155249 Create Date 4/23/2013
Owner Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family Plan Z3-3736-0413
Occupany Permit Required Flood Plain Height Permit Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF"Per state approved plans Trans ID 788841
of Work
HVAC Contr Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 08/08/2013 09:30AM Type Rough In inspector Tom Spierowski approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR EAST ELEVATION FOR BOLT EQUIPMENT PLATFORMS AND 1 CORNER I
F ONE WING THAT WASN'T INSPECTED YET '
'*WOULD LIKE INSPECTION THURSDAY(8/8)*' '
I
�--(2)east meu and east dining-- �
�
Date/Time requested: 8/7/2013 01:38 PM Notice Type: Ready Date/Time:
—
Access: �— ---
Requested By: GANTHER CONSTRUCTION-AI Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
----------------- -------- -- -- -
- - - --------------------------- pp
Date/Time Inspected 08/13/2013 11:OOAM Type Insulation Inspector Tom Spierowski a roved
insulation inspection
-east wall dining and mezz-- �,
� ,
� I
Date/Time requested: 8/12/2013 11:20 AM Notice Type: Ready Date/Time: 08/13/2013 08:OOAM
Access: i�— - —
Requested By: GANTHER CONSTRUCTION Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
----- ------------p---- - - p.
- -- ---------------------------------------------------
Date/Time Inspected 08/15/2013 07:30AM Type Rough In Ins ector Tom S ierowski approved
NW mezzanine,SW wing -- — --
I
�—_ —. I
Date/Time requested: 8/13/2013 04:19 PM Notice Type: Ready Date/Time: 08/14/2013 12:OOPM
Access: I-376-0218 -- —
Requested By: GANTHER CONSTRUCTION _ _ _ Phone Number:
— --—
-——.
Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---- ------------ --------------- --------------------------------------------
Page 6 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 0155249 Create Date 4/23/2013
Owner Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family Plan Z3-3736-0413
Occupany Permit Required Flood Plain Height Permit Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF'Per state approved plans Trans ID 788841
of Work
HVAC Contr Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 08/01/2013 10:30AM Type Re Insulation Inspector Tom Spierowski
� -- — — — — aPProved
�
�
I
�
�
�
Date/Time requested: 7/31/2013 04:05 PM Notice Type: Ready Date/Time: 08/01/2013 12:OOAM
Access:
Requested By: GANTHER CONSTRUCTION Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------------------------p------- - - p
- ----------------
------------ ---------------
Date/Time Inspected 08/02/2013 10:30AM Type Rough In Ins ector Tom S ierowski
— _ approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE NORTHWEST WING ONLY
'*WOULD LIKE INSPECTON PRIOR TO NOON ON FRIDAY(8/2)"* '
�
�
Date/Time requested: 8/1/2013 03:06 PM Notice Type: Ready Date/Time:
Access: � N SITE IS STEVE IS(920)376-0237
Requested By: GANTHER CONSTRUCTION-Allen Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------------------ ----p- --- --- - - p.
- - ---------- --
------------------------------- ---
Date/Time Inspected 08/O6/2013 10:OOAM Type Insulation Ins ector Tom S ierowski
_____ approved
REQUEST LINE/READY FOR AN INSULATION FOR THE NORTHWEST WING ONLY —
I **WOULD LIKE INSPECTION TUESDAY(8/6)MORNING*" I
i
-- ,
Date/Time requested: 8/5/2013 02:15 PM Notice Type: Ready Date/Time: 08/O6/2013 10:OOAM I
Access: � --
Requested By: GANTHER CONSTRUCTION-AI __ Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------------------------------------ ----------------------
Page 5 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 0155249 Create Date 4/23/2013
Owner _ _ Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family _ Plan Z3-3736-0413
Occupany Permit Required Flood Plain Height Permit Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF"Per state approved plans Trans ID 788841
of Work
HVAC Contr _ _ Plumbing Contr
Electric Contr
Inspections:
Date/Time inspected 07/26/2013 09:OOAM Type Rough In Inspector Tom Spierowski
approved
REQUEST LINE/READY FORA ROUGH INSPECTION FOR THE SOUTHEAST WING ONLY
"WOULD LIKE INSPECTION ON FRIDAY(7/26)*' I
�
I i
�
i
Date/Time requested: 7/25/2013_1121 AM Notice Type: Ready Date/Time:
Access:
Requested By: GANTHER CONSTRUCTION-AI Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived � Reinspect Fee Paid
----------------------------p---- - p.
- - - - -
- - - ----- -- - - -----------------------------------------
Date/Time Inspected 07/26/2013 09:OOAM Type Insulation Ins ector Tom S ierowski
— approved
INORTHEAST WING ONLY ___�
� �
',
� '
-- — -- ----
Date/Time requested: 7/30/2013 08:49 AM Notice Type: Ready Date/Time: �
Access: � — — --
Requested By: GANTHER CONSTRUCTION Phone Number:
Reins ect Fee � Fee Waived ❑ Reinspect Fee Paid
---0-------p---------------------------- ------------------
-----------p------- - - p.
- - ------------------------------------------
Date/Time Inspected 07/31/2013 11:OOAM Type Insulation Ins ector Tom S ierowski
not approved
REQUEST LINE/READY FOR AN INSULATION INSPECTION FOR THE SOUTHEAST WING ONLY
Not Ready �
I
Date/Time requested: 7/30/2013 02:47 PM Notice Type: Ready Date/Time: 07/31/2013 11:OOAM
Access: �--
Requested By: GANTHER CONSTRUCTION-Allen �
Phone Number: (920)376-0218
� Reinspect Fee � Fee Waived � Reinspect Fee Paid
--- ----------------------------------------------------- -
Page 4 of 9
y
f:
Building Permit Work Card
. Job Address 1816 VINLAND ST _ Permit Number 0155249 Create Date 4/23/2013 �
Owner _____ Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family __ ____ __ Plan Z3-3736-0413
Occupany Permit Required Flood Piain _ Height Permit Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF'Per state approved plans Trans ID 788841
of Work
HVAC Contr ___ Plumbing Contr
Electric Contr
Inspections:
Date/Time Inspected 06/07/2013 09:30AM Type Slab on Grade Inspector Tom Spierowski
approved
lab ready for inspection
I
�
�
— — --
--
Date/Time requested: 6/6/2013 12_47 PM Notice Type: Ready Date/Time: O6/07/2013 07:30AM
Access: �_ — I
Requested By: GANTHER CONSTRUCTION_ Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
----------------------p-------- - ----- -----------------------------------------
Date/Time Inspected 07/15/2013 11:34AM Type Note ins ector Adam Krause
EC called re:putty pads between boxes in 1 hr wall. I'll be looking at his R.I.w/o them,they'll be installed Wed. pm or Thurs am-ASK
I I
I �
Date/Time requested: 7/15/2013 11:34 AM Notice Type: Ready Date/Time: 07/15/2013 11:34AM
Access: �
Requested By: GANTHER CONSTRUCTION Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---------------------p---- - p.
- ----------------------------------------------------
Date/Time Inspected 07/23/2013 09:30AM Type Rough In Ins ector Tom S ierowski
approved w/cond.
NE wing only. rough in framing.Need to verify shoulder studs under headers ,
,'
Date/Time requested: 7/22/2013 11:36 AM Notice Type: Ready Date/Time: 07/23/2013 07:30AM
Access: - ---
Requested By: GANTHER CONSTRUCTION Phone Number:
� Reinspect Fee 0 Fee Waived ❑ Reinspect Fee Paid
--------- ---------------- ----------------------------------------
Page 3 of 9
Building Permit Work Card
Job Address 1816 VINLAND ST _ _ Permit Number 0155249 Create Date 4/23/2013
Owner _ _ Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family Plan Z3-3736-0413
Occupany Permit Required Flood Plain _ Height Permit _ Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF*Per state approved plans Trans ID 788841 €
� of Work �
HVAC Contr __ Plumbing Contr
Electric Contr — —
Inspections:
Date/Time Inspected 05/13/2013 12:OOPM Type Foundation Backfill Inspecto� John Zarate
approved
EXT 5048/READY FOR A WALL POUR INSPECTON
i
i
�
Date/Time requested: 5/10/2013 01:27 PM Notice Type: Ready Date/Time: 05/13/2013 11:OOAM
Access: . —
Requested By: GANTHER CONSTRUCTION-AI �
Phone Number: (920)376-0218
� Reinspect Fee 0 Fee Waived � Reinspect Fee Paid
----------- --- -
- ------------- --p-------- -- - - ---
- - - - - -------------------------------------
Date/Time Inspected 05/14/2013 12:45PM Type Footings Ins ector John Zarate
approved
REQUEST LINE/READY FORA WALLAND FOOTING INSPECTION
I
�
�
Date/Time requested: 5/14/2013 07:39 AM Notice Type: Ready Date/Time: 05/14/2013 01:OOPM J
Access: �'----- — ---- — -- — — —---- —
Requested By: GANTHER CONSTRUCTION-AI Phone Number: 920-376-0218 �
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------------- -
- ------------ ----p------- — - - --- -
- - - - - ----------------------------------
Date/Time Inspected 05/15/2013 02:30PM Type Footings Ins ector John Zarate
approved
REQUEST LINE/READY FORA WALLAND PAD INSPECTION
I
�
i
Date/Time requested: 5/15/2013 08:27 AM
Notice Type: Ready Date/Time: 05/15/2 1
_ ___ 0 3 02:OOPM
Access: �— --- —
Requested By: GANTHER CONSTRUCTION-AI ---�
Phone Number: 920-376-0218
0 Reinspect Fee � Fee Waived � Reinspect Fee Paid
---------------------------- -----------------------
Page 2 of 9
i
Building Permit Work Card
Job Address 1816 VINLAND ST Permit Number 0155249 Create Date 4/23/2013
; Owner Contractor GANTHER CONSTRUCTION
Category 130-New Multi-Family
_ Plan Z3-3736-0413
Occupany Permit Required Flood Plain E
— __ Height Permit Class of Const: Type VA
Use/Nature Comm/CBRF/New 34 unit CBRF*Per state approved plans Trans ID 788841
of Work
HVAC Contr _ Plumbing Contr `
Electric Contr
Inspections:
Date/Time Inspected 05/07/2013 12:OOPM Type Footings Inspector Tom Spierowski
REQUEST LINE/READY FORA FOOTING INSPECTION approved
--partial ok-- I
�
�
-- �
Date/Time requested: 5/6/2013 07:47 AM Notice Type: Ready Date/Time: 05/07/2013 01:30PM
Access: ——
Requested By: GANTHER CONSTRUCTION-AI
_ Phone Number: 920-376-0218
— ---
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid — :
---------------------
---- ----- -P--------- - - p.
- --------------------- -- -------------------
Date/Time Inspected 05/08/2013 11:OOAM Type Footings ins ector Tom S ierowski
approved
REQUEST LINE/READY FOR A FOOTING(SOUTHEAST SECTION ABOUT 300FT)
"WOULD LIKE INSPECTION BETWEEN 10-11AM ON WEDNESDAY(5/8)*` '
�
� :
Date/Time requested: 5/7/2013 04:07 PM Notice Type: Ready Date/Time:
Access: �---- — ---- -
Requested By: GANTHER CONSTRUCTION-AI_ Phone Number: 920-376-0218
Reins ect Fee 0 Fee Waived � Reinspect Fee Paid
-- �-----p
---------------------- -- -
- -------------------------
----------
-----------------------
a e ime Inspected Type Inspector John Zarate
— cancelled
REQUEST LINE/READY FOR A WALL POUR INSPECTION �
I
Date/Time requested: 5/9/2013_ 12:31 PM Notice Type: Ready Date/Time: 05/10/2013 02:OOPM �
Access: — — — --- --- - --
. _
Requested By: GANTHER CONSTRUCTION-AI Phone Number: 920-376-0218 �
� Reinspect Fee � Fee Waived � Reinspect Fee Paid —
---------- ---------------------------------------
Page 1 of 9
t
;
Electric Permit Work Card
Job Address 1816 VINLAND ST Permit Number 156016 Create Date 6/4/2013 '
Owner _ Contractor SUBURBAN ELECTRICAL ENGINEERINC `f
Service ' New � Change 0 Temp � N/A I Type � Overhead � Underground � N/A I
�
Volts 120/240 Circuits _ Luminaires }
Amps 800 Switches Receptacles Value $187,000.00 '
Use/Nature OMM/NEW CBRF '*check#59631 — - — ---
of Work I
,
Inspections:
Date/Time Ins ected 10/09/2 ;
P 013 1 :
0 15A
M T
e Final
YP
In
__ s e
_ p ctor Adam Krause approved
REQUEST LINE/READY FOR A FINAL INSPECTION FOR THE SOUTHWEST&NORTHWEST WINGS ONLY
'*WOULD LIKE INSPECTION WEDNESDAY(10/9)MORNING*` i
IPanel labeling, handle ties
� �
I
—
Date/Time requested: 10/07/2013 08:25 AM Notice Type: Ready Date/Time: 10/09/2013 08:OOAM
Access: I — — —
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC I
Phone Number: (920)841-7093 '
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid
----------------p-------- - - -
- - - --------------------------------- – – --
- - - ------
Date/Time Inspected 10/18/2013 09:15AM Type Final Ins ector Adam Krause
notapproved
REQUEST LINE/READY FOR FINAL INSPECTION —
i �*WOULD LIKE INSPECTION FRIDAY(10/18)MORNING�'
INot ready i
� '
Date/Time requested: 10/15/2013 01:06 PM Notice Type: Ready Date/Time: 10/18/2013 OS:OOAM
Access: ! — — ---
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC Phone Number: (920)841-7093
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid
------------------p-----
- - - -
- - - ------ -------------------------------------
Date/Time Inspected 10/28/2013 10:OOAM Type Final Ins ector Adam Krause
— approved .
REQUEST LINE/READY FOR A FINAL INSPECTION
""WOULD LIKE INSPECTION MONDAY(10/28)MORNING** �
;
�
� �
—
Date/Time requested: 10/22/2013 11:38 AM Notice Type: _ Ready Date/Time: 10/28/2013 07:OOAM I
Access: �_
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC Phone Number: 920-841-7093-Rodney
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid
--------- -------------------------------------------------
Electric Permit Work Card
Job Address 1816 VINLAND ST _ _ Permit Number 156016 Create Date 6/4/2013
Owner
_____ Contrector SUBURBAN ELECTRICAL ENGINEERIN(
Service New 0 Change� Temp 0 N/q � Type � Overhead � Underground � N/A I
Volts 120/240 Circuits _ Luminaires
Amps 800 Switches _ Receptacles Value $187,000.00 '
Use/Nature OMM/NEW CBRF •*check#59631 €
of Work =
�
� �
—
Inspections: —
.
D .
ate
/Time Inspected 09/03/2013 09.30AM T e Under r
YP ound
9 Ins
pector Adam Kr
ause
no time
REQUEST LINE/READY FOR A TRENCHING INSPECTION FOR SITE LIGHTING
"WOULD LIKE INSPECTION TUESDAY(9/3)*" I
Not to be ready until the pm.All the pipe is already in the ground.This only pertains to sono-tubes for lot lights I
�
� — ------ �
Date/Time requested: 08/30/2013_10:00 AM _ Notice Type: _ Ready Date/Time: 09/03/2013 08:OOAM '
Access: � — -- -- --- - — — _—__— -
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC — �
- — — Phone Number: (920)841-0793 Rodney
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid '
---------------- ----------p------- - - -
- - --- ------------
----------------------------
ate/Time Inspected 09/10/2013 10:30AM Type Abv Ceiling Ins ector Adam Krause
REQUEST LINE/READY FORAN ABOVE CEILING INSPECTION FOR SOME GRID WORK — approved
I
I "WOULD LIKE THE INSPECTION TUESDAY(9/10)AFTERNOON'* :
I I
� '
I , — -- --- —. i
Date/Time requested. 09/0 /
9 2013 11:55 AM Notice Type: _ Ready Date/Time: 09/1
0/
2013 10:
OOAM
Access:
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC �
— Phone Number: (920)841-7093 Rodney
� Reinspect Fee � Fee Wavied Reins ect Fee Paid
----------------�------p
---------------------p------ - -
- - -
- - --- -- - ----------------pp--------------
Date/Time Inspected 09/25/2013 09:OOAM Type Final Ins ector Tom Spierowski a roved
I inal ready for inspection on NE and SE wings
I I
I �
-- --------
Date/Time requested: 09/23/2013 01:35 PM Notice Type: Ready Date/Time: 09/25/2013 09:OOAM
Access: j — _ _ �
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC --�
-- Phone Number:
� Reinspect Fee � Fee Wavied Reins ect Fee Paid
----- -----------�------P
--------------- -- ---------------------------
i
Electric Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 156016 Create Date 6/4/2013
Owner _ ____ Contractor SUBURBAN ELECTRICAL ENGINEERIN(
Service �� New 0 Change� Temp � N/A Type 0 Overhead � Underground � N/A I
Volts 120/240 Circuits Luminaires
Amps 800 Switches Receptacles Value $187,000.00
Use/Nature ICOMM/NEW CBRF "check#59631 --
of Work
� I :
� i
� ------ �
- -- - ----- --�
Inspections:
Date/Time Inspected 08/20/2013 09:30AM Type Rough In Inspector Adam Krause
_ approved
REQUEST LINE/READY FORA ROUGH INSPECTION FOR THE FRONT CANOPY ONLY
�
,
'
Date/Time requested: 08/19/2013 11:35 AM Notice Type: Ready Date/Time: 08/19/2013 12:OOPM
Access: '� — - -
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC �
Phone Number: (920)841-7093 Rodney
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid
----------- -----
------p----
- - -
- - - ----- --------- -- ---------- - - - -
- - - - ----------
Date/Time Inspected 08/22/2013 02:OOPM Type Rough In Ins ector Adam Krause
approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE CENTER PART OF CENTURY OAKS
�
I "WOULD LIKE INSPECTION THURSDAY(8/22)'* ;
�
�
Date/Time requested: 08/20/2013 03:17 PM Notice Type: _ Ready Date/Time: 08/22/2013 08:OOAM I
Access: �_ - ------
----
--
-- --
---_ _ -
- -- . -
e ues e - -_ -
q y: UBURBAN ELECTRICAL ENGINEERING INC __ Phone Number: (920)841-7093 Rodney
- --
� Reinspect Fee Fee Wavied - -
� ❑ Reinspect Fee Paid --
---------------
-----P------- - - -
- - -----------
-------------- ---------------
Date/Time Inspected 08/28/2013 12:30PM Type Service Ins ector Adam Krause
- approved
REQUEST LINE/READY FOR THE MAIN SERVICE INSPECTION
"WOULD LIKE INSPECTION WEDNESDAY(8/28)AFTERNOON*• ;I
Faxed to WPS 8-29-13 8 AM
i
I
Date/Time requested: 08/27/2013 11:41 AM Notice Type: _ Ready Date/Time: 08/28/2013 12:OOPM
Access: '
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC Phone Number: (920)841-7093
- - --
� Reinspect Fee 0 Fee Wavied ❑ Reins ect Fee Paid
- - - ----------------------------p--- ---
----------------------- -- -------------------------
Electric Permit Work Card
Job Address 1816 VINLAND ST _ permit Number 156016 Create Date 6/4/2013 �
Owner - -- ——— —
_ _ Contractor SUBURBAN ELECTRICAL ENGINEERIN(
Service � New � Change� Temp � N/A JI Type � Overhead � Underground � N/A �
Volts 120/240 Circuits Luminaires
Amps 800 Switches Receptacles Value $187,000.00
Use/Nature OMM/NEW CBRF **check#59631
of Work
I
I i
I
�--- — �
Inspections: —
Date/Time Inspected 08/08/2013 01:30PM Type Rough In In
sector A
p dam Kr
ause approved
iREQUEST LINE/READY FOR A ROUGH INSPECTION
I "WOULD LIKE INSPECTION TODAY OR 1 ST THING ON FRIDAY(8/9)"*
�
Date/Time requested: 08/08l2013 09:26 AM Notice Type: _ Ready Date/Time: 08/ I
Access: --
08/2013 09:OOAM
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC �
Phone Number: (920)841-7024 Jeremy
Reins ect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
---0-------p-----------------
- - - -
---- - - ----------------p------- - - -
- - ----------------------- -- --------------
Date/Time Inspected 08/14/2013 01:30PM Type Rough In Ins ector Adam Krause
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE SOUTHWEST WING ONLY
"WOULD LIKE INSPECTION WEDNESDAY(8/14)EARLYAFTERNOON"* '
�
�
Date/Time requested: 08/12/2013_12:04 PM Notice Type: Ready Date/Time: 08/14/2013 12:OOPM
Access: � — ——
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
Phone Number: (920)841-7093
� Reinspect Fee � Fee Wavied ❑ Reinspect Fee Paid
------------------- ------p- ---- -- - - -
- - - ----------------------- - -- -- --
Date/Time Inspected 08/19/2013 09:15AM T e Rou h In
yp 9 Ins ector Adam Krause approved
REQUEST LINE/READY FOR A ROUGH WSPECTION FOR THE 2 ROOMS LEFT ON THE SW WING AND MEZZ ABOVE SW WING �
WOULD LIKE INSPECTION MONDAY(8/19)MORNING*'
�
�
---- -- I
Date/Time requested: 08/15/2013 01:00 PM Notice Type: Ready Date/Time: 08/19/2013 08:OOAM
Access: I — ------ _ — --- ---
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC I
Phone Number: (920)841-7093 Rodney
� Reinspect Fee � Fee Wavied ❑ Reinspect Fee Paid
--------------- -- ------------------ -- -----
Electric Permit Work Card
Job Address 1816 VINLAND ST Permit Number 156016 Create Date 6/4/2013
Owner _ Contractor SUBURBAN ELECTRICAL ENGINEERIN( t
i
Service �Ne�,y Chan e Tem
0 9 0 P � N/A � Type 0 Overhead � Underground � N/A `
Volts _ 120/240 Circuits Luminaires �,
Amps 800 Switches _ Receptacles Value $187,000.00
Use/Nature OMM/NEW CBRF **check#59631 — -------
of Work —
I
�
Inspections:
Date/Time Inspected 07/17/2013 11:OOAM Type Rough In_ Inspector Adam Krause
REQUEST LINE/READY FORA ROUGH INSPECTION FOR THE NORTHEAST WING ONLY approved
I "'WOULD LIKE INSPECTION WEDNESDAY(7/17)MORNING'* �
i
—
Date/Time requested: 07/15/2013 11:42 AM Notice Type: Ready Date/Time: 07/17/2013 08:OOAM
Access: l —
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
Phone Number: (920)841-7093 Rodney
0 Reinspect Fee � Fee Wavied ❑ Reinspect Fee Paid
- -
- ---------------
-------------------- - - -
- - - ------------ -
ate/Time Inspected 07/22/2013 01:45PM T e Rou h In
Yp 9 Inspector Adam Krause approved
�EQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE SE WING ONLY —
I "'WOULD LIKE INSPECTION LATER ON MONDAY(7/22)" ,
I
I
Date/Time requested: 07/19/2013 08:46 AM Notice Type: Ready Date/Time: 07/22/2013 12:30PM I
Access: i —
Requested by SUBURBAN ELECTRICAL ENGINEERING INC
Phone Number: (920)841-7093 Rodney
� Reinspect Fee � Fee Wavied Reins ect Fee Paid
----------------� -----p
_ _
--- - ---- -- -- --------- ----------------------------------------------
Date/Time Inspected 07/31/2013 01:30PM Type Rough In_ Inspector Adam Krause
approved
REQUEST LINE/READY FOR A ROUGH INSPECTION FOR THE NORTHWEST WING ONLY -- -- —�
""WOULD LIKE INSPECTION EARLYAFTERNOON ON WEDNESDAY(7/31)•* I
�
Date/Time requested: 07/30/2013 06:29 AM Notice T e: I
YP _ Ready Date/Time: 07/31/2013 12:OOPM
Access: I
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
Phone Number: (920)841-7093
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid
----- -- ------------------------------
Electric Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 156016 Create Date 6/4/2013
Owner Contractor SUBURBAN ELECTRICAL ENGINEERIN(
Service � New � Change� Temp N/A T e �
� � Yp 0 Overhead_ � Underground � N/A �
Volts 120/240 Circuits Luminaires �
Amps 800 Switches _ Receptacles Value $187,000.00
, Use/Nature OMM/NEW CBRF "check#59631 ---- —
of Work
�
�
� IInspections:
Date/Time Inspected 06/05/2013 10:OOAM Type Underground Inspector Adam Krause
Ir— --- — _ approved
� � �
� I
Date/Time requested: 06/04/2013 02:07 PM Notice Type: Ready Date/Time: 06/05/2013 09:OOAM I
Access: � --- —
L
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
Phone Number:
----
Reinspect Fee � Fee Wavied ❑ Reinspect Fee Paid
------------------ -- ---- -- - - -- -
- - - -------- --------- -- ---
-----------------------
ate/Time Inspected 06/12/2013 09:OOAM Type Temporary Inspector Adam Krause
Faxed to WPS 6-12-13 11 am — ----- __ -----—_ approved
Refaxed to Luana @ 800-305-9754 6-13-13 11 AM
Refaxed to Luana @ 800-305-9754 6-13-13 2:30 PM � '
,I
� I
�
Date/Time requested: O6/11/2013 02:21 PM Notice Type: Ready Date/Time: 06/11/2013 02:30PM
Access: � -- —
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
— — Phone Number: 841-7093
� Reinspect Fee � Fee Wavied � Reinspect Fee Paid '
-------- -------------
-------p---- -- - - -
- - --------- --------------CN--------------
Date/Time Inspected 07/10/2013 10:30AM Type Consultation Ins ector Adam Krause
r-- — _ --- —
�
i
I
Date/Time requested: 07/09/2013 1132 AM Notice Type: Ready Date/Time: 07/10/2013 09:OOAM
Access: � -- --
Requested by: SUBURBAN ELECTRICAL ENGINEERING INC
---- Phone Number:
— ------
Reinspect Fee � Fee Wavied Reins ect Fee Paid
------------------- ❑ P
----------- -- - -----------------------
�
HVAC Permit Work Card
Job Address 1816 VINLAND ST _ Permit Number 157613 Create Date 09/09/2013
Owner CENTURY OAKS HOMES LLC Contractor CHRISTENSEN HEATING&A/C INC
Fuel ✓ Gas Oil Electric � Solar I�I�Solid
System [�✓ New �Re lace �� Value $175,000.00
� �? ] Other �
✓ Forced Air Radiant Steam � Vent —�
�� �—_� aC �
Electric Hot Water Su I. 1
� � PP _ Con. Burner �
Chimney Type ChimneylA � Chimney B � Direct Vent � NotApplicable
Use/Nature ,Comm/CBRF/New 34 unit CBRF*Per state approved plans Trans ID 2267082 **check#64050approved
of Work
I
�
�
Inspections:
Date/Time Inspected 10/28/2013 10:OOAM Type Final _ Inspector Tom Spierowski
— approved
I
� 'i
Date/Time requested: 10/31/2013 09:32AM Notice Type: Ready Date/Time: 10/28/2013 10:OOAM �
Access: j
Requested By: CHRISTENSEN HEATING&A/C INC Phone Number:
Reins ect Fee � Fee Waived � Reinspect Fee Paid
---0------p------ --- --------------------------------------------
--- ----------------------- ----- ------------------------
Plumbing Permit Work Card
Job Address 1816 VINLAND ST Permit Number 155857
Owner — Create Date 05/29/2013
--- --__ Contractor O'NEILL ENTERPRISES INC `
Category 442-Commercial-Interior(New/Relocated Fi '
Plan D9-504-0513-P Value $193,000.00 '
Bathtub 0 Clothes Wshr _ 8 Classrm Sink 0 Surgeons Sink 0 Roof Drain
Shower 35 Lnd Tra 0 Deduct Meters p
rY Y 3 Exam Sink __0 Sterilizer 0 Soda Dis
Whirlpool 1 Sum Pum p 0 Wtr Sewer Mtrs p
P P _ 0 F Prep Sink _ 0 RPZ Valve 0 Coffee Maker
Lavatory 39 San Sump/Pump 0 FINWst Sink 0 Bidet � Wtr Usage Mtrs p
--- 0 Site Drain 0 Misc. p
Toilet 36 Water Softner 0 Hand Sink 0 Urinal � Fixtures
0 Wait.St.
Kit Sink 2 Standp Rec _8 Lab Sink 0 Beer Ta
Dis osal — --- p 0 Ice Chest p
P 0 Gar Drain _ 0 Plaster Sink 0 Dip Well 0 Comm Ice Maker 0
Dishwasher 1 Local Waste 0 Sculry Sink 0 Drink Ftn
Floor Drain 4 Bar Sink -- _ 0 Int Grease Trap p
39 Serv Sink 4 Wash Ftn 0 Ext Grease Trap 0
Hose Bibb 4 Breakrm Sink 0 Shamp Sink 0 Catch Basin
Water Heater � 0 Eye Wash Statn p
Use/Nature COMM/mtenor plumbing associated with the construction of a retirement community/all work will meet state and local code
of Work ,
i
�
�
I
Size Material Type # Conn.Type
Sanitary Sewer
Storm Sewer
Water Service
Inspections for Work Card 125972
Date/Time Inspected 10/25/2013 08:OOAM Type Re Final
— _____ _ Inspector Jerry Fabisch approved w/cond.
FINAL READY FOR INSPECTION
"*STILL NEED TO SET SHAMPOO SINK/CABINETS WEREN'T IN YET'*'
Date/Time requested: 10/24/2013 12:03 PM Notice Type: Ready Date/Time: 10/25/2013 08:OOAM
Access: --
� --
Requested By: O'NEILL ENTERPRISES INC
__ _ Phone Number:
� Reinspect Fee 0 Fee Waived Reins ect Fee Paid
--------------�-----p
-------------------P-------------- -
DatelTime Inspected 11/01/2013 10:30AM T e Re Final
---- -----aPproved----------
Yp Ins ector Jon Mueller
final on shampoo sink installation for occupancy
OK
Date/Time requested: 10/31/2013 02:04 PM Notice Type: Ready Date/Time: 11/01/2013 07:30AM
Access: �
Requested By: O'NEILL ENTERPRISES INC
__ Phone Number:
----
Reins ect Fee 0 Fee Waived (] Reinspect Fee Paid
P
----- ------------------ ----------
, ;
Inspections for Work Card 125972
Date/Time Inspected 08/08/2013 11:30AM T e Rou h In
yp 9 __._ Inspector Jerry Fabisch
ONLINE REQUEST/READY FOR A ROUGH INSPECTION ---- approved
'*PAT WOULD LIKE TO BE PRESENT-PLEASE CALL*•
"'LAUNDRY ON ALL FOUR WINGS HAVE NOT BEEN PIPED TO DATE NEED TO HAVE ADDITIONAL WALL BUILT/THEY WILL CALL
WHEN READY FOR THAT INSPECTION OR TAKE PICTURES TO VERIFY CODE IS MET"**
Date/Time requested: 8/6/2013 05:58 PM Notice Type: Ready Date/Time: 08/08/2013 11:OOAM
Access: IppEN DURING DAY —
Requested By: O'NEILL ENTERPRISES INC-Patrick ONeill —
Phone Number: (920)428-4700
� Reinspect Fee � Fee Waived Reins ect Fee Paid
------------------------
-- -p
-
- -------------p----------- -
Date/Time Inspected 08/22/2013 11:30AM T e Rou h In
----------- ---------------
yp 9 Ins ector Jon Mueller
RI on 4 laundry areas approved
OK
Date/Time requested: 8/22/2013 09:21 AM Notice Type: Ready Date/Time: 08/22/2013 11:OOAM
Access: � — -- —
Requested By: O'NEILL ENTERPRISES INC �
Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
---------- -------- -
- - -------------
- - - - ----------- -- - --
ate/Time Inspected 10/14/2013 11:OOAM Type Final -------�-�----�-------
— _ _ inspector Jerry Fabisch notapproved
final ready for inspection
'**NOT COMPLETELY DONE WITH FINAL P�UMBING SEVERAL ITEMS STILL NEED TO BE INSTALLED/ALSO HAVE A LIST OF
ISSUES THAT NEED TO BE ADDRESSED AS WELL"'
Date/Time requested: 10/14/2013 08:45 AM Notice Type: Ready Date/Time: 10/14/2013 09:OOAM
Access: � ---_—
—_—
---
_--
— ------ —
—_.___
Requested By: O'NEILL ENTERPRISES INC -
__- -
----------
--- ---- Phone Number.
-----------
Reins ect Fee � Fee Waived Reins ect Fee Paid ----
P ❑ P --
---------------------------------
j
Inspections for Work Card 125972 '
Date/Time Inspected 07/11/2013 09:30AM Type Rough In Inspector Jerry Fabisch
ri READY FOR INSPECTION ON FIRST WING OF BUILDING approved
Date/Time requested: 7/10/2013 _02:38 PM Notice Type: Ready Date/Time: 07/11/2013 09:OOAM
Access: — ---- ____
Requested By: O'NEILL ENTERPRISES INC — �
----____.__ _ Phone Number: '
� Reinspect Fee � Fee Waived � Reinspect Fee Paid — — '
-------- --------- -
- ----------- - - - - -
- - - ---------------- --
Date/Time Inspected 07/17/2013 02:30PM T e Rou h In
- -
---- - -- -----------
yp _ 9__ _ Inspector Jerry Fabisch approved
RI ready on southeast side of building
Date/Time requested: 7/17/2013 09:33 AM Notice Type: Ready Date/Time: 07/17/2013 01:30PM
Access: 'i --
Requested By: O'NEILL ENTERPRISES INC
Phone Number:
� Reinspect Fee 0 Fee Waived ❑ Reinspect Fee Paid
- - - - - -
- - - -- - -----------------------
---------------------- -
Date/Time Inspected 07/25/2013 10:OOAM T e Rou h In
- - - - ---------
— Yp 9 ___ Inspector Jon Mueller approved
RI on 3rd wing
OK
Date/Time requested: 7/25/2013 07:36 AM Notice Type: Ready Date/Time: 07/25/2013 10:OOAM
Access: Ir— — ----------- ---
Requested By: O'NEILL ENTERPRISES INC — 1
— Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
-- - ---- --------------------------------
�
�
Inspections for Work Card 125972
Date/Time Inspected O6/03/2013 02:30PM Type Underground Inspector Jerry Fabisch
UG inspection ready -- approved
Date/Time requested: 6/3/2013 08:06 AM Notice Type: Ready Date/Time: O6/03/2013 02:OOPM
Access: �` -
Requested By: O'NEILL ENTERPRISES INC l
Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
- -
- -- ---------------------------- -
- ----------- Jer
----------- - -- --
- -- --------------------- -------
a e ime Inspected 06/04/2013 02:30PM Type Underground Inspector ry Fabisch
— — approved
UG kitchen waste ready for inspection
Date/Time requested: 6/4/2013 07_35 AM Notice Type: Ready Date/Time: O6/04/2013 02:OOPM
Access: '---__— —------------- -----
Requested By: O'NEILL ENTERPRISES INC �
Phone Number:
0 Reinspect Fee � Fee Waived � Reinspect Fee Paid
- -
-- -- ------------------------- --
-- ---p----- ry
------- ---------------------------------------
ate/Time Inspected O6/05/2013 11:15AM Type Underground Ins ector Jer Fabisch
Final on UG inspection
— approved
Date/Time requested: 6/5/2013 _08:12 AM Notice Type: Ready Date/Time: O6/05/2013 10:30AM
Access: �
Requested By: O'NEILL ENTERPRISES INC --
------_ Phone Number:
� Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid —
------------------------------------------
t
Inspections for Work Card 125972 i
Date/Time Inspected 05/29/2013 02:OOPM Type Underground_ Inspector Jerry Fabisch `
UG ready for inspection on northeast comer of building — aPproved `,
Date/Time requested: 5/29/2013 08:45 AM Notice Type: Ready Date/Time: 05/29/2013 08:OOAM
Access: i
Requested By O NEILL ENTERPRISES INC
Phone Number:
� Reinspect Fee � Fee Waived � Reinspect Fee Paid
----------------
---------------------- - -
- - ----------------------------- -
Date/Time Inspected 05/30/2013 01:15PM Type Underground Inspector Jon Mueller
UG inspection ready for southeast corner of building --- approved
OK
Date/Time requested: 5/30/2013 10:45 AM Notice Type: Ready Date/Time: 05/30/2013 01:OOPM
Access: i — ---------- —
Requested By: O'NEILL ENTERPRISES INC —
Phone Number:
0 Reinspect Fee � Fee Waived ❑ Reinspect Fee Paid
------- ----- --- -
- - ---------------
-- - - -
Date/Time Inspected 05/31/2013 02:OOPM Type Underground Inspector Jon Mueller
UG ready for inspection approved
OK
Date/Time requested: 5/31/2013 08:02AM Notice Type: Ready Date/Time: 05/31/2013 01:OOPM
Access: ��— --__— -- --- —
Requested By: O'NEILL ENTERPRISES INC
--_ Phone Number:
� Reinspect Fee 0 Fee Waived Reins ect Fee Paid —
--------------- �- -----p
---------------------------------------
�
t
Plumbing Permit Work Card �
JobAddress 1g16 VINLAND ST
Owner CENTURY OAKS HOMES LLC Permit Number 158261
Create Date 10/14/2013
Contractor O'NEILL ENTERPRISES INC
Category 442-Commercial-Interior(New/Relocated Fi
Plan D9-504-0513-P Value
Bathtub _ 0 Clothes Wshr 0 Classrm Sink p $1,000.00 j
Shower — Surgeons Sink 0 Roof Drain
0 Lndry Tray 0 Exam Sink 0 Deduct Meters p
— 0 Sterilizer 0 Soda Disp 0 Wtr Sewer Mtrs
Whirlpool 0 Sump Pump 0 F Prep Sink 1 RpZ Valve �
Lavatory 0 San Sum /Pum _ 0 Coffee Maker 0 Wtr Usage Mtrs p
P p 0 FINWst Sink 0 Bidet
Toilet 0 Water Softner --- 0 Site Drain 4 Misc. �
— 0 Hand Sink 2 Urinal � Fixtures
Kit Sink 0 Stand Rec — 0 Wait.St.
p _ 0 Lab Sink 0 Beer Ta
Disposal 0 Gar Drain p 0 Ice Chest p
0 Plaster Sink 0 Dip Well 0 Comm Ice Maker p
Dishwasher 3 Local Waste 0 Scul Sink
Floor Drain � ry � Drink Ftn 0 Int Grease Trap p
Bar Sink 0 Serv Sink 0 Wash Ftn
Hose Bibb 2 Breakrm Sink � Ext Grease Trap �
0 Shamp Sink 1 Catch Basin
Water Heater 0 pedicure chair -- 0 Eye Wash Statn p
Use/Nature �COMM/ Additional fixtures added to permit#155857 ---
of Work --------------
Size Material
Sanitary Sewer Type # Conn.Type
Storm Sewer
Water Service
�
Inspections for Work Card 128674
Date/Time Inspected 10/25/2013 07:45AM Type Final
-- ____ Inspector Jerry Fabisch approved
FINAL READY FOR INSPECTION
Date/Time requested: 10/25/2013 08:54 AM Notice Type: Ready Date/Time: 10/25/2013 07:OOAM
Access: � --- -- _
Requested By: O'NEILL ENTERPRISES INC
Phone Number:
� Reinspect Fee 0 Fee Waived � Reinspect Fee Paid
-----------------------------------
BALCO BALANCING INC.
6 Green Haven Court
Appleton, WI 54911
CERTIFIED TEST, ADJUST, AND ; `;`
BALANCE REP�RT ;
�
i
DATE 10/24/13 i
�
�
PROJECT CENTURY OAK HOMES '
ADDRESS 1804 VINLAND STREET
OSHKOSH1 WISCONSIN �
ARCHITECT - '
ENGINEER AUERSTEEL
NEENAH, WISCONSIN '
HVAC CONTRACTOR CHRISTENSEN HEATING AND AIR CONDlTIONING
APPLETON�WISCONSIN
NEBB TAB FIRM BALCO BALANCING INC.
ADDRESS 6 GREEN HAVEN COURT
APPLETON, WI 54911
i
G�gatan�;� '
� �� ,
Nadonal Envrtonmental Balar�cing BuBau
S VAN LITH
CFRTIFlCATION
2971 i
9 E�.3l31/14 i
/ � i
�j�Q, � �
dron+C i
i
i
�
I
BALCO BALANCING INC CERTIFICATION
6 Green Haven Court
Appleton,WI 54911
PROJECT CENTURY OAK HOMES
ADDRESS 1804 VINtAIJD STREET
OSHKOSH,WISCONSIN
�
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED I
IN ACCORDANCE WITH NEBB STAiVDARD PRQCEDURES.ANY VARfANCES FROM DES(GN QUANTiTIES WHICH �
EXCEED NE$B TOLERANCESARE NOTED THROUGHOUT THIS REPORT. i
THE AIR DISTRIBUTION SYSTEMS HAVE BEEN TESTED AND BALANCED AND FINALADJUSTMENTS f�1AVE BEEN
MADE fN ACCORDANCE WITH NEBB'PROCEDURAL STAWDARD5 FOR TESTING,AQJUSTING,BAIANCING OF
ENVIRONMENTAL SYSTEMS'AND THE PROJECT SPECIFICATIONS.
�
NEBB TAB FIRM BALCO BALANCING INC,
REG.NO. 2971 CERTIFIED BY HANS D.VAN LITH DATE 10124l13
(Air TAB Supervisor)
THE HYDRONIC dISTRIBUTION SYSTEMS HAVE 6EEN TESTEDAND BALANCEdAND FINALADJUSTMENTS HAVE
BEEN MADE IN ACCORDANCE WITH NEBB'PROCEDUREAL STANDARDS FOR TESTING,ADJUSTING,BALANCING
OF ENVIRONMENTAL SYSTEMS"AND THE PROJECT SPECIFICATIONS,
NEBB TAB FIRM BALCO BALANCING INC,
REG.N0. 2971 CERTIFIED 8Y HANS D.VAN LITH DATE 10/24113
{Hydronic TAB Supervisor)
SUBMITTEDAND CERTIFIED BY:
NEBB TAB FIRM BALCO BALANCING INC.
TAB SUPERVISOR HANS D.VAN UTH
REG.N0. 2971 SIGNATURE �""'0
DATE 10l24113 CERTIFICATION EXPIRATION DATE 3131114
r�ao���o�e��e�,re� ��p 6alan�yn ,'
Repori Not Vdl(d UNess Stamp6d wltl�
NE88 Certificatiai Seal � � �
HANS VAN LITH
CER7IFICATION
2971 �
,9� E�.3131ii4 � i
a� eF i
'a dronlc � i
�
�
BALCO BA�ANCING INC. INSTRUMENT CALIBRATIQN REPORT I
6 Green Haven Court NEBB CERTIFIED
Appleton,WI 54911
PROJECT CENTURY DAK HOMES
CALIBRATION
INSTRUMENTISERIAL NO. APPLICATION TEST DATE
�
SHORTRIDGE ADM-860/M91970 TRAVERSE 4/15/2013 �
;
SHORTRIDGE ADM-860/M91970 FLOW HOOD 4/15/2013
SHORTRiDGE ADM-860/M91970 STATIC PRESSURES 4/15/2013
EXTECH 461891 /Q378173 TACHOMETER 4/12/2013
FLUKE-322 / 95340509 VOLTS&S 4h 2/2013
CHECK-IT 626/BBI-PY 1 CONTACT PYROMETER 4/1?J2013
EXTECH HD500 1 09085368 TEMPERATURE/HUMIDITY 4/1?J2013
HYDRO DATA HDM-300 / W03078 WATER PRESSURE 1'!/23/2012
TEST DATE 10/24J13 READINGS BY ERIC VAN LANKVELT
i
�
i
BALCO BALANCING INC. AiRAPPARATUS
6 Green Haven Court TEST REPORT
Appfeton,WI 54911
PROJECT CENTURY OAK HOMES SYSTEM/UNIT F-9
�
LOCATION OSHiCOSH.WISCONSIN �
I
UNiT DATA MOTOR DATA I
Make/Model No. BRYANT Make/Frame 1 '
�ze 912S660080S21 H.PJRPM 3/4 4 SPEED �
Serial Number 1213A48997 VoItslPhase/Hertz 120 -1- fi0 '
ArrlCless VERTICAL BL�IV THRU F.L.Am s/S.F. 1 ,
Discha s l.lPBLAST Make Sheave �
Make Sheave - Sheave DiaMBore -
Sheava Diam/Bore Sheave 8�Distence
No.9eItslMaketSize Sheave er.�iam. DIRECT DRIVE
No.Filterslf e�Stze 1 PLEATED 25 X 20 X 4
TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL
Total CFM us 2000 1940 Discha e S.P. .19
Total S.P. - Suctlon S.P. .ZO
Fan RPM HIGH SPEED Reheat Coil Di1f S.P. - -
Extemal S.P. .50 .39 Coo�ln Coil Difl S.P.
Motar VoRs Tt T2 T3 120 121 Preheat Coll DIR S.P.
Motor Am s T1 T2 T3 8.4 Pilters ONF S,P.
Outside Ak CFM lls 455 429
Retum Air CFM Us 1545 151'! Vortex Dam Posidon -
Outslde Alr Dam Poefdon '
Retum Air Dem Poaition -
REMARKS (1)NOACCESS TO MOTOR TAG.
'SET MIN. O.A.WITH ECONOMIZER CONTROL IN UNIT.
�
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
National Environmerrtal Balancing Bureau
Report Not Valid Unless Stamped with NEBB Certification Seal '
i
i
�
�
i
�
BALCO BALANCING INC. RECTANGUI.AR DUCT
6 Green Haven Court TRAVERSE REPORT
Appleton, WI 54911
PROJECT CENTURY OAK HOMES SYSTEfuWNIT F-9
LOCATIONRQNE MAIN SERVICE RETURN FOR M1N. O.A. ;
ALTITUDE DENSITY - CORR.FACTOR - �
DUCT REQUIRED ACTUAL
S.P. .19" AirTempF(C) 70 Fpm 809 Sdm(sus) 1545 Fpm 791 Sdm(sUs} 1511
Size 25 X 11 Area 1.91 mis C - mis Ctm us �
i
Dista�ue Fran
eoaom Posidon 1 2 3 4 5 6 7 8 9 10 11 12 13
1 1424 1299 1550 1369 1434 �
2 374 1337 1442 1472 1405 !
3 - 830 1048 325 �
4 - 509 -
5
6
7
8
9
10
11
12
13
Distance from
Duct Ed e �
Velocity
Subtotals
Note:Take roadings with air blowing toward the observer.
REMARKS:
I
�
i
TEST DATE 10/24/13 READINGS SY ERIC VAN LANKVELT
�
National Environmental Balancing Bureau !
Report Not Valid Unless Stamped With NEBB Ce�tification Seal �
�
�
BALCO BALANCING INC. AIR OUTLET
6 Green Haven Court TEST REPORT
Appleton, WI 54911
PROJECT CENTURY OAK MOMES SYSTEM F-9
OUTLET MANUFACTURER TESTAPPARATUS SHORTRIDGE ADM-860
� OUTLET DESIGN PRELIMINARY FINAL PERCENTpF �
SERVED N0. TYPE SIZE AK VEL AIRPLW VEL AIRFLW VEL AIRFLW OE51GN i
i
1 10 X 10 1 - 185 170 i
2 90 X 70 1 - 185 1g4 i
3 10 X 10 1 185 - 180 '
132 a 10 X 10 1 185 - �gg
5 10 X 10 1 - 185 1 g5
6 10 X 10 1 - 185 - �gp
7 10 X�10 1 185 - 175
8 10 X 10 1 - 180 �77
118C 1 10X101 - 8 - g
2 10X101 - 9 $
123 10 X 10 1 - 100 �Q�
123B 12 X 6 1 75 - 7p
9 44 10 X 10 1 100 g
1446 12 X 6 1 - 7 - 72
REMARKS: �
i
TEST DATE '10/24/13 READINGS BY ERIC VAN LANKVELT
Natipnal Environmental Balancing Bureau '
Report Not Valid Unless Stamped with NEBB Certification Seal ;
I
i
I
BALCO BALANCING INC. AIR APPARATUS
6 Green Haven Court TEST REPORT
Appleton,WI 54911
PROJECT CENTURY OAK HOMES SYSTENWNIT F-10 ;
LOCATION __ OSHKQSH.WISCONSIN �
I
UNIT DATA MOTOR DATA �
i
I
MakelAAadel No. BRYANT Make/Frame 1 '
T sue 912S660d80S21 H.PJRPM 3/4 4 SPEED
Serial Number 3413A50fi15 VoIts/PhaseMertz 120 -1- 60
ArrlGass VERTICAL BL4W THRU F.L.Am S.F. 1 �
oischa e UPBLAST Make Sheave
Make Sheava - Sheave DiamBore
Sheave DlamBoro Sheave�Disfance -
No.Berts►n�take�5ize - Sheave .D�am. DfRECT DRIVE
No.FiiterslT e�s�ze 1 PLEATED 25 X 2fl X 4
TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL
Tofal CFM Us 1875 1898 �scha e S.P. - .23
Total S.P. Suction S,P, .19
Fan RPM HIGH SPEED Reheat Coi!DifF S.P.
Fxtemal S.P. .50 .42 Coolin Coil Dilf S.P. -
Motar Vofts T1 T2 T3 120 121 Preheat Coil DiH S.P. -
Motor Am s T1 T2 T3 8.3 Fiflers Diff S.P.
Outside Air CFM Us 455 477
Retum Air CFM Us �420 1421 VoAex Dam Pasition -
Outside Air Dam Positlon '
Retum Alr Dam Position
REMARKS (1}NO ACCESS TO MOTOR i'AG.
'SET MIN. O.A.WITH ECONOMIZER CONTROL IN UNIT.
TEST DATE 10/2a/13 READINGS BY ERIC VAN LANKVELT
National Environmentai Balancing Bureau
Report iVot Valid Unless Stamped with NEBB Certfication Seal
i
i
BALCO BALANCING INC. RECTANGUI.AR DUCT
6 Green Haven Court TRAVERSE REPORT ;
Appleton, WI 54911 �
�
PR4JECT CENTURY OAK HOMES SYSTEMNNIT F-1 Q j
LOCATION/ZONE O.A.DUCT SERVICE MIN. O.A. i
ALTITUDE - DENSITY - CORR.FACTOR - �
DUCT REQUIRED ACTUAL I
s.P. -0.02 AirTemp F(C� 35 Fpm 202 Sctm(sus) 455 Fpm 212 Scfm(sUs) 477 � `
sae 18 X 18 nrea 2.25 rnls c s - mis � _ ;
Distance From '
Bottom Pos�tbn 1 2 3 4 5 6 7 8 9 10 11 12 13 �
1 256 211 262 218
�
2 249 230 216 237
3 226 150 171 280
4 184 180 1G4 255
5
6
7
8
9
10
11
12
13
Distance From
Duct Ed e
Velocity
Subtotals
Note:Take readings with air blowing toward the observec
REMARKS:
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT '
�
National Environmental Balancing Bureau
Report Not Valid Unless Stamped With NEBB Ce�ification Seal
I
i
BALCO BALANCING INC. AIR OUTLET
6 Green Haven Court TEST REPORT
Appiston,WI 54911 �
i
PROJECT CENTURY DAK HOMES SYSTEM F-10 �
OUTLET MANUFACTURER - TESTAPPARATUS SHORTRIDGE ADM-Sfi0 I
�
AREA OUTLET DESIGN PRELIMINARY FINAL PERCENT OF �
SERVEO N0. TYPE SIZE AK VEL AIRFLW VEL AIRFLW VEL AIRFLW DESIGN �
�
116 'S 0 X 10 1 100 _ 1'I p '
116B 12 X 6 1 - 7 g
1 12 X 6 1 - 150 150
118 2 12X61 150 - 147
3 12 X 6 1 150 152
4 12X61 150 - 140
1 12 X 6 1 170 175
102 2 12 X 6 1 - 170 169
3 12 X 6 1 - 170 - 165
4 12 X fi 1 170 - 174
5 12 X 6 1 170 - 177
105 10 X 10 1 - 250 259
REMARKS:
�
�
TEST DATE 10/24h3 READINGS BY ERIC VAN LANKVELT
Natianal Environmental Balancing Sureau
Report Not Valid Unless Stamped with NEBS Certification Seal
I
�
I
BALCO BALANCING INC. AIRAPPARATUS
6 Green Haven Court TEST REPORT
Appleton,WI 54911 i
�
PROJECT CENTURY OAK HOMES SYSTEMNNIT F-11 '
i
LOCATION OSHKOSH.WISCONSIN
UNIT QATA MOTOR OATA �
nnakernnoeet No. BRYANT Make/Freme 1 �
T ISae 912SB60080S21 H.P.lRPM 3/4 4 SPEED �
Serial Number 3413A50614 vons/Phase�He�tz 120 -1- fi0 '
Arr.lClaas 1/ERTICAL BLQW THRU F.L.Am s�S.F. 1
Discha UPBLAS7 Make Sheave
iMake Sheave Sheave Diam/8ore -
Sheave DiamlBore - Sheave 8 Distance
No.Bens/Makelsize - sheave o .olam. DIRECT DRIVE
No.Filtersfr �ze 1 PLEATED 25 X 20 X 4
TEST DATA DESIGN ACTUAL TEST DATA DESlGN ACTUAL
ro�ai cFM us 1915 1903 oisd,a e s.P .22
Total S.P. Suctfon S.F? .24
Fan RPM HIGH SPEED Reheat Cdl DM'S.P.
Extemal S.P. .50 .46 Coolin Coll Dlff S.P. -
Motor Volts T1 T2 T3 120 121 Preheat Coil Di}f S.P. - -
Motor Am s T1 T2 T3 - 8.3 Filters Difl S.P. - -
Outside Air CFM I/s 455 493
Retum Air CFM Us 1460 1410 Vortex Dam Positlon
OutsfdeAir Dem Positian - *
RetumAirDam PosiNon -
REMARKS (1)NO ACCESS TO MOTOR TAG.
'SET MIN. O.A.WITH ECONOMIZER CONTROL IN UNIT. �
�
TEST DATE 10/24113 READINGS BY ERIC VAN LANKVELT
National Environmental Balancing Bureau
Report Not Valid Unless Stamped witfi NEBB Certification Seal
i
i
I
BALCO BALANCING INC. RECTANGU�AR DUCT
6 Green Haven Court TRAVERSE REPORT
Appleton, WI 54911 j
i
PROJECT CENTURY OAK HOMES SYSTEMNNIT F-11
LOCATION2pNE O.A.DUCT SERVICE MfN, O.A. �
ALTITUDE - DENSIIY - CORR,FACTOR - ;
I
DUCT REQUIRED ACTUAI �
s.P -0.03 AirTempF(C) 35 Fpn 202 sar„�sus► 455 Fpm 219 sdr�,��us} 493 !
Sae 18 X 18 Area 2.25 mis Cim s - rds Gm Ils - �
�
Distance Fran ;
eouan ��, 1 2 3 4 5 8 7 S 9 10 11 12 13
1 233 263 281 256
2 229 232 192 283
3 185 200 220 201
4 '!78 188 164 234
5
6
7
8
9
10
11
12
13
Distance From
Duct Ed e
Velocity
Subtotals
Note:Take readings with air blowing tovrard the observet.
REMARKS:
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
Nationai Environmental Balancing Bureau
Report Not Valid Unless Stamped With NEBB Certification Seal
�
i
BALCO BALANCING INC. AIR OUTLET
6 Green Haven Court TEST REPQRT
Appleton, lM 54911
PROJECT CENTURY OAK HOMES SYSTEM F-11 �
OUTLET MANUFACTURER - TESTAPPARATUS SHORTRIDGE ADM-86Q I
�
�
I
AREA OUTLET DESIGk PREUMINARY FINAL PERCENT OF �
SERVED N0. TYPE SIZE AK VEL AIRFLW VEL AIRFLW VEL AlRFLW DESIGN I
i
149 10 X 10 1 - 100 - 110 '
149B 12 X 6 1 7 7
148A 12 X 6 1 3 38
1 12X61 - 100 - 9
148 2 12X61 - 100
147 12 X 6 1 - 50 - 47
103 12 X 6 1 70 65
104 12 X 6 1 150 144
1 12 X 6 1 250 261
2 12 X fi 1 250 24Z
1 Q2 3 12 X 6 1 250 251
4 12 X 6 1 245 246
5 12 X 6 1 240 - 240
REMARKS:
TES7 DATE 10/24113 READINGS BY ERIC VAN I.ANKVELT
Nationai Environmental Balancing Bureau
Report Not Valid Unless Stamped with NEBB Certification Seal
i
BALCO BALANCING INC. AIR APPARATUS
6 Green Haven Court TEST REPORT
Appleton,WI 54911 I
PROJECT CENTURY OAK HOMES SYSTEMNNIT MUA-1 I
LOCATION OSHKOSH.WISCONSIN i
i
�
UNIT DATA MOTOR DATA I
i
�
Make�Madel No. REZNOR MekelFrame CENTIlRY U56H j
T tze SHH260 H,P./RPM 1.5 1725 ,
Serial Number AMBG997DN01862 VaIts/Pha�Hertz 208 -3- 60
ArrJClass 1�ORIZONTAL DRAW THRU F.�.Am s/S.F. 5.0 1.15
otacha e FRONT Make Sheave MASKA
Make Sheave MASKA Sheave o�am�eore VP40 X 5/8
Sheave D�arrveore AK64 X 1" Sheave d�Distsnce - 19"
No.BellslMake/Sae 1 LINKED BELT sheave o r.Diam. 100%CLOSED
No.Filters/T elsize 6 T.A. 16 X 16 X 2
TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL
ToWI CFM Us 3135 3'I� Dieche e S.P. - ,2$
Total S.P. Suction S.P. -,$2
Fan RPM 1057 Reheat Cail DfflS.P. -
Extemal S.P. .50 .58 Cooli Coil Diff S.P. -
Motor Volts T1 T2 T3 120 21 D 212 210 Preheet Coii Dift S.P. -
Motor Am s T1 T2 T3 5.0 4.9 4.8 Filters Oiff S.P,
Outside Air CFM Us 3135 3166
Retum Air CFM Us 0 0 Va�tex Dam PosiUon
Outsfda A!r Dam PoaiNon 100°/6
Retum Air Dam PoslHon -
REMARKS
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
National Environmentai Balancing Bureau
Report Not Valid Unless Stamped with NEBB Certification Seal
i
i
i
i
BALCQ BALANCING INC. RECTANGULAR DUCT
6 Green Haven Court TRAVERSE REPORT
Appleton, W! 54911 '
i
i
PROJECT CENTURY OAK HOMES SYSTEMIUNIT MUA-1 ,
LOCATION20NE O.A.DUCT SERVICE SUPPLY
ALTITUDE - DENSITIf CORR.FACTOR -
I
DUCT REQUIRED ACTiJAL �
s.R -0.32 ,air7emP�{c) 35 Fpm 1128 sc�rn(sus) 3135 Fpm 1139 5crm(sus) 3166 '
s�e 20 X 20 r� 2.78 mrs c►m - Ma crm us - i
Distance From
Bottom Positlon 1 2 3 4 5 6 7 S 9 10 11 12 13
1 1130 987 1353 11$2 1258
2 941 1379 1114 1258 1142
3 1238 1183 1113 1083 1088
4 1104 903 1119 1174 1027
5
6
7
8
9
10
11
12
13
Distance From
Duct Ed e
Velocity �
SubtQtals
Note:Take readings wfth air blowing toward the observer.
REMARKS:
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
National Environmenta!Balancing Bureau
Report Not Valid Unless Stamped With NEBB Certification Seal
�
BALCO BALANCING INC. AIR OUTLET
6 Green Haven Court TEST REPORT
Appleton,WI 54911 j
i
i
PROJECT CENTURY OAK HOMES SYSTEM MUA-1
OUTLET MANUFACTURER TESTAPPARATUS SHORTRIDGE ADM-860 '
I
I
AREA OUTLET DESIGN PRELIMINARY FINAL PERCENTOF
SERVED N0. TYPE SIZE AK VEL AIRFLW VEL AIRFLW VEL AIRFLW DESIGN
,
145 1 12"R 1 - 627 - 615
2 12" R 1 - 627 - 589
3 12" R 'E - 627 - 642
4 12" R 1 - 627 63Q
146 12" R 1 - 627 614
REMARKS:
�
TES7 DATE 10/24/13 READlNGS BY ERIC VAN LANKVELT
Nationai Environmental Balancing Bureau
Report Not Valid Unless Stamped with NEBB Certification Seal
�
i
�
BALCO BALANCING INC FAN TEST REPORT �
6 Green Haven Court �
Appleton,WI 54911 !
�
I
i
PROJECT CENTURY�AK HOMES �
FAN DATA FAN NO.EF-5 FAN NO. EF-fi FAN NO. �
Location ROOF ROOF
Service KITCHEN HOOD DISHWASHER HOOD �
Manufacturer THERMQ7EK THERMOTEK
Model Number BDUI8TH DU30HTH
Serial Mumber -
T Class PRV J PRV I
Motor MakelS e WEG OPEN MARATHON OPEN
Motor H.P.lRPMlFrame 1.Q 1730 E56 1/4 1625 48Y
VoIts/PhaseMertz 208 -3- 60 120 -1- 60
F.L.Am s/S.F. 3.3 1.15 3.7 1.0
Motor Sheave Make/Model BROWNING -
Motor Sheave Diam./6ore VL40 X 518
Fan Sheave Make BROWNING -
Fan Sheave DiamlBore AK54 X 1" -
No. BeIts/Make/Size 1 BANDO AX26 -
Sheave b Distance 7" DIRECT DRIVE
75%CLOSED SPEED SWITCH
TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL
CFM Us 30fi0 28fi4 600 646
Fan RPM 1088 1197 1145 LOW SPEED
S.P. In/Out 1 25/.09
Total S.P. 1.0 1 .375 .34
Volta e T1 T2 T3 208 210 212 210 120 121
Am ra e T1 T2 T3 - 3.4 3.2 3.3 - 1.9
REMARKS: {1)UNABLE TO GET STATICS DUE TO HEAT WRAP AROUND DUCT.
TEST DATE 10/24/13 READ BY ERIC VAN LANKVELT
National Environmental Balanang Bureau
Report Not Valid Unless Stamped with WEBB Certification Seal
I
BALCO BALANCING INC. RECTANGULAR DUCT
8 Green Haven Court TRAVERSE REPORT �
Appleton, Vill 54911 ;
I
PROJECT CENTURY OAK HOMES SYSTEMNNIT EF-5 '
LOCATION20NE HOOD FILTERS SERVICE EXHAUST
ALTITUDE - DENSITY - CORR.FACTOR - �
�
DUCT REQUIRED ACTUAL
S.P. AirTempF(C) 70 Fpm 155 Schn{sus� 306Q Fpm 145 Sctm(sus) 2$64
Size 158 X 18 Area 19.75 m!s C s - m!s cim us -
�
Distance From
eottan Pos�on 1 2 3 4 5 6 7 8 9 10 11 12 13
1 163 145 155 155 151 138 147 172 153 129 123 128 125
2
3
4
5
6
7
8
9
10 `
11
12
13
Distance From
Duct Ed e
velociry
Subtotals
Note:Take readings with air blowing toward the observer.
REMARKS: *READ HOOD FiLTERS WITH ADM-860.
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
National Environmental Balancing Bureau
Report Not Valid Uniess Stamped With NEBB Certification Seal
�
i
BALC� BALANCING fNC. RECTANGULAR DUCT
6 Green Haven Court TRAVERSE REPORT ,
Appleton, WI 54911 ;
�
PROJECT CENTURY OAK HOMES SYSTENWNIT EF-6
LOCATION/ZONE MAIN SERVECE EXHAUST
ALTITUDE - DENSlTY - COFtR.FACTQR - ;
DUCT RE�UIRED ACTUAL ; '
S.P - AirTemp F(C) 70 Fpm 513 5crm(sus) 600 Fpm 552 5crm(susy 646 ,
sRe 14 X 12 nroa 1.17 rtJs c s - m/s c - ,
D'�sfance Fran
9onom Position 1 2 3 4 5 6 7 8 9 10 11 12 13
1 552 `
2
3
4
5
6
7
8
9
10
11
12
13
Distance From
Duct Ed e
Velocity
Subtotals
Note:Take readings wiih air blowing toward the observer.
REMARKS: 'READ EXHAUST HOOD INLET WITH VELGRIDADM-860.
TEST DATE 10/24/13 READINGS BY ERIC VAN LANKVELT
National Environmental Balancing Bureau
Repart Not Valid Unless Stamped With NEBB Certification Seal