HomeMy WebLinkAbout21468-Electric (09/06/2013) CiTY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205 � 215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT � PO Box 1130 OSHKOSH OSHKOSH WI 54903-1130 CORRECTION NOTICE ON THE WATER Issue Date 9/6/2013 Re Issue Date Complies No Address 1013 N LARK ST Sent to ✓ Owner BERNARD L SORENSON SR REV LIVIN� 1013 N LARK ST OSHKOSH WI 54902 -3349 Required for Occupancy Occupancy Introduction While conducting the final electrical inspection,the following violations were noted. Item# 1 Code Mun code 11-22 Complies No Comply By 10/06/2013 Description Permit valuation provided was$2399.20. The estimate provided to the owner was for$5100.A$51 permit fee is still owed for the electrical permit. Item# 2 Code NEC 250.120(A) Complies No Comply By 10/09/2013 Description Where equipment grounding consists of a raceway or where it is a wire within a raceway or cable, it shall be installed in accordance with the applicable provisions in this Code using fittings for joints and terminations approved for use with the type raceway or cable used.All connections,joints, and fittings shall be made tight using suitable tools. Liquid tight fittings shall be made up tight. Item# 3 Code NEC 408.4 Complies No Comply By 10/09/2013 Description Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use.The identification shall include sufficient detail to allow each circuit to be distinguished from all others. Breakers in the service panel are no longer supplying power to sertain circuits and should be relabeled as"spares"to alleviate any confusion to the user. Item# 4 Code NEC 310.16 Complies No Comply By 10/09/2013 Description Branch circuit conductors are terminated under the main breaker lugs, creating an overcurrent hazard Item# 5 Code Mun code 11-44 Complies No Comply By 10/09/2013 Description Should any electrical equipment be found unsafe or dangerous to persons or property,the person owning or using such electrical equipment shall be notified in writing by the Electrical Inspector the need to make the equipment safe.There is evident corrosion of the electrical service panel Item# 6 Code NEC 110.3(B) Complies No Comply By 10/09/2013 Description Service panel cover connot mount flush due to small disconnect subpanel being mounted underneath it. 21468 Page 1 of 2 Item# 7 Code NEC 408.41 Complies No Comply By 10/09/2013 Description Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor. Summarv Please make arrangements to have these violations corrected in the next 30 days. Feel free to contact me with any concerns or questions at 236-5274. Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment and/or occupancy. Upon completing the corrections,the owner/co�tractor/agent must sign and date at the bottom of this notice and return it to the Inspection Services Division by the Compliance Date of 10/6/2013 Office hours are Monday through Friday 7:30 a.m. -4:30 p.m. or by appointment.To schedule inspections please call the Inspection Request line at -5 28 n ting ess, permit number(when applicable),and the nature of what needs to be inspected. Signature �� Date 7 ' � � Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes. Print Name Company Signature Date Also Sent to: Bldg ✓ Elec � PIEPER ELECTRIC INC 5070 N 35TH ST MILWAUKEE WI 53209 -5302 HVAC I Plbg — — Designer Other I _ Inspector 21468 Page 2 of 2