HomeMy WebLinkAbout21468-Electric (09/06/2013) CiTY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205 �
215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT �
PO Box 1130 OSHKOSH
OSHKOSH WI 54903-1130 CORRECTION NOTICE
ON THE WATER
Issue Date 9/6/2013 Re Issue Date Complies No
Address 1013 N LARK ST
Sent to ✓ Owner BERNARD L SORENSON SR REV LIVIN� 1013 N LARK ST OSHKOSH WI 54902 -3349
Required for Occupancy Occupancy
Introduction While conducting the final electrical inspection,the following violations were noted.
Item# 1 Code Mun code 11-22 Complies No Comply By 10/06/2013
Description Permit valuation provided was$2399.20. The estimate provided to the owner was for$5100.A$51 permit fee is still owed for
the electrical permit.
Item# 2 Code NEC 250.120(A) Complies No Comply By 10/09/2013
Description Where equipment grounding consists of a raceway or where it is a wire within a raceway or cable, it shall be installed in
accordance with the applicable provisions in this Code using fittings for joints and terminations approved for use with the type
raceway or cable used.All connections,joints, and fittings shall be made tight using suitable tools. Liquid tight fittings shall be
made up tight.
Item# 3 Code NEC 408.4 Complies No Comply By 10/09/2013
Description Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use.The
identification shall include sufficient detail to allow each circuit to be distinguished from all others. Breakers in the service panel
are no longer supplying power to sertain circuits and should be relabeled as"spares"to alleviate any confusion to the user.
Item# 4 Code NEC 310.16 Complies No Comply By 10/09/2013
Description Branch circuit conductors are terminated under the main breaker lugs, creating an overcurrent hazard
Item# 5 Code Mun code 11-44 Complies No Comply By 10/09/2013
Description Should any electrical equipment be found unsafe or dangerous to persons or property,the person owning or using such
electrical equipment shall be notified in writing by the Electrical Inspector the need to make the equipment safe.There is
evident corrosion of the electrical service panel
Item# 6 Code NEC 110.3(B) Complies No Comply By 10/09/2013
Description Service panel cover connot mount flush due to small disconnect subpanel being mounted underneath it.
21468 Page 1 of 2
Item# 7 Code NEC 408.41 Complies No Comply By 10/09/2013
Description Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another
conductor.
Summarv Please make arrangements to have these violations corrected in the next 30 days. Feel free to contact me with any concerns
or questions at 236-5274.
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/co�tractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 10/6/2013
Office hours are Monday through Friday 7:30 a.m. -4:30 p.m. or by appointment.To schedule inspections please call the Inspection
Request line at -5 28 n ting ess, permit number(when applicable),and the nature of what needs to be inspected.
Signature �� Date 7 ' � �
Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: Bldg
✓ Elec � PIEPER ELECTRIC INC 5070 N 35TH ST MILWAUKEE WI 53209 -5302