HomeMy WebLinkAbout21385-Electric (08/13/2013) CITY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205 �
215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT �
PO Box 1130 OSHKOSH
OSHKOSH WI 54903-1130 CORRECTION NOTICE
ON THE WATER :
Issue Date 8/13/2013 Re Issue Date Complies No
Address 641 SCHOOL AVE
Sent to ✓ Owner SECRETARY OF HOUSING&URBAN DI 4400 WILL ROGERS PKWY 300 OKLAHOMA Cll OK 73108 -1870
Required for Occupancy Occupancy
introduction While conducting the electrical service inspection,the following violations were noted.
Item# 1 Code NEC 314.17(A) Complies No Comply By 09/12/2013
Description Openings through which conductors enter shall be effectively closed.-KOs knocked out of the service panel and 2 basement
ceiling boxes
Item# 2 Code NEC 314.17(B) Complies No Comply By 09/12/2013
Description Where raceway or cable is installed with metal boxes or conduit bodies,the raceway or cable shall be secured to such boxes
and conduit bodies.-A cable enters the service panel without a connector
Item# 3 Code NEC 300.15 Complies No Comply By 09/12/2013
Description Where the wiring method is conduit,tubing,Type AC cable,Type MC cable,Type MI cable, nonmetallic-sheathed cable, or
other cables, a box or conduit body shall be installed at each conductor splice point,outlet point, switch point,junction point,
termination point,or pull point-no boxes visible where light fixtures are not installed
Item# 4 Code NEC 250.8 Complies No Comply By 09/12/2013
Description Grounding conductors and bonding jumpers shall be connected by thread-forming machine screws that engage not less than
two threads in the enclosure.-ground clamp on water meter is loose, not able to be tightened (Corrosion)
Item# 5 Code NEC 110.26 Complies No Comply By 09/12/2013
Description Working clearance required for electrical equipment.Working space required by this section shall not be used for storage.
Dedicated Electrical Space.A space 30"wide and 36"deep
21385 Page 1 of 2
Item# 6 Code MC 16.35(A)(1)(a) Complies No Comply By 09/12/2013
Description Every floor,floor covering,wall, ceiling, kitchen counters&tops, cupboards&e�erior doors etc shall be kept in good repair.-
Upper room ceiling in disrepair
Summarv Please correct the above violations and request a re-inspection within the next 30 days. Office hours are Monday-Friday
7:30-4:30pm. If you have questions feel free to contact me at 236-5274. Electrical corrections must be complete prior to
restoring electrical service.
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 9/12/2013
Office hours are Monday through Friday 7:30 a.m. -4:30 p.m.or by appointment.To schedule inspections please call the Inspection
Request line at 236-5128 notin the a ress,permit number(when applicable),and the nature of what needs to be inspected.
Signature '"_J '�,✓�--� Date_b � -7 ' /�
Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: Bldg
Elec — —
HVAC — — :
Plbg — _—
Designer — _—
✓ Other WPS-ERIC STRANGEWAY 3300 N MAIN ST PO BOX 420 OSHKOSH WI 54901 -0420
Inspector —
21385 Page 2 of 2