HomeMy WebLinkAbout20912-Electric (05/17/2013) CITY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205 �
215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT �
PO Box 1130 OSHKOSH
OSHKOSH WI 54903-1130 CORRECTION NOTICE
ON THE WATER
Issue Date 5/17/2013 Re Issue Date Complies No
Address 1100 EASTMAN ST
Sent to � Owner PATRICK M NEMECEK 1350 MARICOPA DR OSHKOSH WI 54904 -8151
Required for Occupancy Occupancy
Introduction WPS personnel informed the inspection department of code violations pertaining to your electrical service. I have verified the
violations and now request that you address the situation.
Item# 1 Code NEC 230.51 Complies No Comply By O6/16/2013
Description Service entrance conductors shall be supported by staples or other approved means. 12"from service heads and enclosures,
30"intervals.
�
Item# 2 Code NEC 11-44(A) Complies No Comply By 06/16/2013
Description Should any electrical equipment be found unsafe or dangerous to persons or property,the person owning or using such
electrical equipment shall be notified in writing by the Electrical Inspector the need to make the equipment safe. Failure to
comply with such notice within the time specified shall be sufficient cause for the Electrical Inspector to disconnect electrical
service to said equipment or to cause the arrest of such person owning or using such electrical equipment.The electrical
service has deteriorated to an unsafe condition due to degradation of the outer cable jacket.
Item# 3 Code MC 11-22(D) Complies No Comply By O6/16/2013
Description Electricians licensed with the ciry required to do wiring on any building that is not a single family residence owned and
occupied by the owner.Wiring done for the purpose of rental or sale of such residences is also limited to a licensed electrician
20912 Page 1 of 2
Item# 4 Code NEC 358.30(A) Complies No Comply By 06/16/2013
Description Electrical Metallic Tubing shall be securely fastened in place at least 3'from every termination and at least every 10'.
Summarv I appreciate your cooperation on this matter. Please contact me about correcting these problems as soon as possible. If I
have not heard from you or compliance is not achieved by the below-mentioned date,WPS will receive orders to disconnect
your electrical service as of 12 P.M.June. 17th,2013, and/or a$232 citation may be issued, possibly daily,from the date of
correction notice issuance,or an abatement action will be pursued by the Ciry of Oshkosh.
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/contractoNagent must sign and date at the bottom of this notice
and retum it to the Inspection Services Division by the Compliance Date of 6/16/2013
Office hours are Monday through Friday 7:30 a.m.-4:30 p.m.or by appointment.To schedule inspections please call the Inspection
Request line at 2 - 1 g-tt��dress, permit number(when applicable),and the nature of what needs to be inspected.
,/ �` �,��
Signature Date�
Inspected by: Adam rause 236-5274 akrause@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: Bldg _
Elec _
HVAC _
Plbg _
Designer _
✓ Other WPS-SERIC STRANGEWAY 3300 N MAIN ST PO BOX 420 OSHKOSH WI 54901 -0420
Inspector