HomeMy WebLinkAbout20086 - Dwelling units (09/18/12 CITY OF OSHKOSH EN I • ` ii INSPECTION SERVICES DIVISION ROOM 205
215 CHURCH AVE 1 A Ir.] t DEPARTMENT OF COMMUNITY DEVELOPMENT OSHKOSH
PO Box 1130 " CORRECTION NOTICE
OSHKOSH WI 54903-1130 ON THE WATER
Issue Date 9/18/2012 Re Issue Date 1/28/2013 Complies No
Address 131 W 8TH AVE
Sent to Q Owner 1 GLORIA MOXON 1823 S MAIN ST OSHKOSH WI 54902 -6952
Required for Occupancy Occupancy
Introduction There has been no further contact, schedule of corrective action or confirmation of compliance concerning this order received
by this office. Please contact this office with the status of the corrections.
Item# 1 Code MUN 16-33A(7) Complies No Comply By 09/25/2012 IMMEDIATELY
Description All dwelling units, vacant or occupied, shall be provided with working, approved smoke detectors one each in the basement
first and second floors. Common area smoke detectors(basements) are the sole responsibility of the property owner. The
owner shall replace batteries once per year or at the beginning of new tenancies. Written responsibilities shall be given to the
occupants concerning smoke detectors.
Item# 2 Code ss 101.647 Complies No Comply By 09/25/2012 IMMEDIATELY
Description The owner of a dwelling shall install a functional carbon monoxide detector in the basement of the dwelling and on each floor
level except the attic, garage, or storage area of each dwelling unit. Except as provided under par. (b)the occupant of the
dwelling unit shall maintain any carbon monoxide detector in that unit. (b) If any occupant gives written notice to the owner that
the carbon monoxide detector is not functional,the owner shall provide,within 5 days after receipt of that notice, any
maintenance necessary to make that carbon monoxide detector functional.
Item# 3 Code MUN 16-33A(9) Complies No Comply By 09/25/2012 IMMEDIATELY
Description All living unit entryways shall be equipped with solid core doors in good condition and deadbolt locks installed as defined in
Section 16-22 OMC. Deadbolt on entrance door is not working properly. Bolt sticks. Repair or replace the deadbolt.
Complies No Comply By 09/25/2012 IMMEDIATELY
Item# 4 Code MUN 16-35A(3) P Description Cracked/damaged/leaking fixtures or other plumbing conditions,which create un-sanitary conditions or unusable fixtures, shall
be replaced/repaired by a licensed plumber with permit. Repair the leak on the kitchen sink.
Item# 5 Code MUN 16-35A(1)(a) Complies No Comply By 10/19/2012
Description Every floor,floor covering,wall, ceiling, kitchen counters&tops,cupboards&exterior doors etc shall be kept in good repair.
Repair the damaged sections of the ceiling and wall in the bedroom. It appears that there was a leak in that area-make a
repair if it is still leaking. Replace the missing deawer front on the bathroom cabinet. Paint the repaired wall section in the
bathroom. Replace the missing glass on the entrance door.
Item# 6 Code MUN 16-34A(1) Complies No Comply By 10/19/2012
Description Every dwelling unit shall have heating facilities which are capable of safely and adequately heating all habitable rooms and
bathrooms to a temperature of at least 67 degrees F with an outside temperature of minus 15 degrees without forcing the
heating system. All habitable rooms to be supplied with adequate heat sources. All heating shall be in operation to maintain
this minimum during all occupied periods. Install baseboard heaters in the bedrooms and bathroom (heat supplies not found in
those rooms.)
20086 Page 1 of 2
Item# 7 Code MUN 16-34A(3)(a) Complies No Comply By 10/19/2012
--- - -- ----
Description Every outlet and fixture shall be properly installed and shall be maintained in a good and safe working condition and shall be
connected to the source of the electric power in a safe manner.All living units shall be provided with safe and adequate
electrical facilities, fixtures&wiring. Bathroom light is not working.
Summary notice. Failure to contact immediately before e 2 4/137wioll arrange
in additional enforcement action.dy to verify compliance with this
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 10/18/2012 —_--—-_
Office hours are Monday through Friday 7:30 a.m. -4:30 p.m. or by appointment.To schedule inspections please call the Inspection
Request line at 236-5128 noting the addre •=rmit number(when applicable),and the nature of what needs to be inspected.
rte. Date t I k/�,
Signature ^�'-"�
Inspected by: Andrew Prickett 236-5137 aprickett®ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: a Bldg
Elec ---
HVAC —
J Plbg I -- — -
Li Designer
Other 1 OCCUPANTS 131A W 8TH AVE
OSHKOSH WI 54902 -
U Inspector
20086 Page 2 of 2
CITY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205
(11111q
215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT
PO Box 1130 CORRECTION NOTICE OSHKOSH
OSHKOSH WI 54903-1130
ON THE WATER
Issue Date 9/18/2012 Re Issue Date Complies No
Address 131 W 8TH AVE
Sent to ✓ Owner 1 GLORIA MOXON OSHKOSH WI 54902 -6952
Eir— -_ 1823 S MAIN ST
Required for Occupancy Occupancy
Introduction An inspection of your rental property(living unit)following a tenant complaint revealed the following violations of the Oshkosh
Minimum Housing Code which shall be corrected by the compliance dates specified for each item. If you have any questions
regarding the requirements of this notice please contact me immediately at(920)236-5137.
Item# 1 Code MUN 16-33A(7) Complies No Comply By 09/25/2012 IMMEDIATELY
------------- --
Description All dwelling units, vacant or occupied, shall be provided with working, approved smoke detectors one each in the basement
first and second floors. Common area smoke detectors(basements)are the sole responsibility of the property owner. The
owner shall replace batteries once per year or at the beginning of new tenancies. Written responsibilities shall be given to the
occupants concerning smoke detectors.
Item# 2 Code ss 101.647 Complies No Comply By 09/2.5/2012 IMMEDIATELY
Description The owner of a dwelling shall install a functional carbon monoxide detector in the basement of the dwelling and on each floor
level except the attic, garage, or storage area of each dwelling unit. Except as provided under par. (b)the occupant of the
dwelling unit shall maintain any carbon monoxide detector in that unit. (b) If any occupant gives written notice to the owner that
the carbon monoxide detector is not functional,the owner shall provide,within 5 days after receipt of that notice, any
maintenance necessary to make that carbon monoxide detector functional.
Item# 3 Code MUN 16-33A(9) Complies No Comply By 09/25/2012 IMMEDIATELY
Description All living unit entryways shall be equipped with solid core doors in good condition and deadbolt locks installed as defined in
Section 16-22 OMC. Deadbolt on entrance door is not working properly. Bolt sticks. Repair or replace the deadbolt.
Item# 4 Code MUN 16-35A(3) Complies No Comply By 09/25/2012 IMMEDIATELY
Description Cracked/damaged/leaking fixtures or other plumbing conditions,which create un-sanitary conditions or unusable fixtures, shall
be replaced/repaired by a licensed plumber with permit. Repair the leak on the kitchen sink.
Item# 5 Code MUN 16-35A(1)(a) Complies No Comply By 10/19/2012
Description Every floor,floor covering,wall, ceiling, kitchen counters&tops, cupboards &exterior doors etc shall be kept in good repair.
Repair the damaged sections of the ceiling and wall in the bedroom. It appears that there was a leak in that area-make a
repair if it is still leaking. Replace the missing deawer front on the bathroom cabinet. Paint the repaired wall section in the
bathroom. Replace the missing glass on the entrance door.
Item# 6 Code MUN 16-34A(1) Complies No Comply By 10/19/2012
- _- -- -----------------
Description Every dwelling unit shall have heating facilities which are capable of safely and adequately heating all habitable rooms and
bathrooms to a temperature of at least 67 degrees F with an outside temperature of minus 15 degrees without forcing the
heating system. All habitable rooms to be supplied with adequate heat sources. All heating shall be in operation to maintain
this minimum during all occupied periods. Install baseboard heaters in the bedrooms and bathroom (heat supplies not found in
those rooms.)
20086 Page 1 of 2
Item# 7 Code MUN 16-34A(3)(a) Complies No Comply By 10/19/2012
Description Every outlet and fixture shall be properly installed and shall be maintained in a good and safe working condition and shall be
connected to the source of the electric power in a safe manner.All living units shall be provided with safe and adequate
electrical facilities, fixtures&wiring. Bathroom light is not working.
Summary It is the responsibility of every property owner to confirm compliance with these orders before the compliance date as
specified. Please contact this office on or before the scheduled due date(s)to schedule a re-inspection of the property. If you
are unable to make the necessary repairs by the listed compliance date(s), please submit a schedule of corrections to be
made, along with competion dates. Submitting a schedule can result in extended periods of time to make repairs on those
items not Life/Safety issues.
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 10/18/2012
Office hours are Monday through Friday 7:30 a.m. -4:30 p.m.or by appointment.To schedule inspections please call the Inspection
Request line at 236-5128 no ' he address, permit number(when applicable),and the nature of what needs to be inspected.
Signature Date 9 //"2–
Inspected Inspected by: Andrew Prickett 236-5137 aprickett@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: Bldg
Elec
HVAC "
JPlbg-- _ —
U Designer j —
-
0 Other 1 OCCUPANTS 131A W 8TH AVE OSHKOSH WI 54902 -
Inspector 1
20086 Page 2 of 2
al ti
•.74 I _ 5 _• .� Ile• J �• ..
L n •i a 5
a F °..rg4;L4 °� + SI��- '- 4a 9 k • � �' •-�. y'.. f 1.
n fin.�� 5 6 •... � �. °�r ni '�' fan
� '•� �-n��rRa f_ ,s'q�' it F �. � °� � a
s
r
_
in
r
F
Violation(s) of MUN 16-34A(3)(a) at 131 W 8t"Ave—9/5/12
lip
:v
_jai
fF.._
r
31
40 o-� T
IF
T r
e.+i•
Violation(s) of MUN 16-35A(1)(a) at 131 W 8t"Ave—9/5/12
IF o
4
s
,
i
,
n
Violation(s) of MUN 16-35A(3), 16-33A(7) &ss 101.647 at 131 W 8th Ave—9/5/12
u
, < .
\ \ I
.._ . �
Violation(s) o v U N I6-33A(9) 16-35ap#% at 131 W/`Ave—9/5/12
: \
J04 ,
_ w
. \\ �
< �
GIL
Violation(s) of MUN 17-36A & 16-34A(1) at 131 W 8th Ave—9/5/12
. A
7&&8%\ o MUN1wa4(l} & I31W 8 t av-9512
. .� . . .�-
. -
� �
-sl
. . .�
. � �� � • � �