CONDITIONAL APPROVAL
Identification Numbers
PLAN APPROVAL EXPIRES: 12/21/2014
Transaction ID No.2190490
SITE: Site ID No. 753519
Dermatology Associates Oshkosh Please refer to both identification
numbers, above, in all correspondence
2351 State Rd 44 with the agency.
City of Oshkosh
Winnebago County
SW1/4, SE1/4, S33, T18NN, R16E
FOR:
Facility: 702768 DERMATOLOGY ASSOCIATES OSHKOSH
DAVE RICHARDS Page 2 12/21/2012
2351 STATE RD 44
Plan Type: Addition-Alteration; 1 Interior Fixture(s)
Object Type: Cross Connection Control Device, Health Care Regulated Object ID No.: 1406258
Device is Serving: Lab Equipment; Device Type: Reduced Pressure Preventer; Location on Property: Under
Lab Sink; Manufacturer:WATTS; Model: 009 OT; Serial No.:419633; 1/2"Valve Size
The submittal described above has been reviewed for conformance with applicable Wisconsin
Administrative Codes and Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The
owner, as defined in chapter 101.01(10),Wisconsin Statutes, is responsible for compliance with all code
requirements.
No person may engage in or work at plumbing in the state unless licensed to do so by the Department
per s.145.06,stats.
The following conditions shall be met during construction or installation and prior to occupancy or use:
Key Item(s)
1. SPS 382.41(5)(e)3.a. If an RP or RP Detector is located within a building, a drain or receptor shall be
provided to receive the vent port discharge. If a floor drain is to receive the discharge from the vent
ports of a reduced pressure principle backflow preventer or a reduced pressure detector backflow
preventer, the flow or pathway of the discharge may not create a nuisance.
2. SPS 382.41(5)(f).This cross connection control assembly shall be installed in accordance with this
paragraph.
3. SPS 384.10(2) Product Review and Approval. (a) 1. Each type of plumbing product which falls into
one of the of the categories in Table 384.10 shall be approved by the department in accordance
with this subsection before the product may be sold for use in a plumbing system or installed in a
plumbing system. Health care plumbing appliances furnished for installation in this plumbing
system shall have received prior department product review and approval and shall be installed by a
properly licensed plumber. The owner of the facility and the representative responsible to
purchase such equipment shall be made aware of this requirement.
DAVE RICHARDS Page 3 12/21/2012
Reminders
• The cross connection control assemblies indicated in the above Description box have been
registered with the Department. Each Device shall be tagged as per SPS 382.40(3)(d)3. Each device
shall be tested and reported as per SPS 382.22(8).
A copy of the approved plans, specifications and this letter shall be on-site during construction and
open to inspection by authorized representatives of the Department,which may include local
inspectors. If plan index sheets were submitted in lieu of additional full plan sets, a copy of this approval
letter and index sheet shall be attached to plans that correspond with the copy on file with the
Department. If these plans were submitted in an electronic form, the designer is responsible to
download, print, and bind the plans along with our approval letter. A department electronic stamp and
signature shall be on the plans which are used at the job site for construction. All permits required by
the state or the local municipality shall be obtained prior to commencement of
construction/installation/operation.
In granting this approval the Division of Safety & Buildings reserves the right to require changes or
additions should conditions arise making them necessary for code compliance.As per state stats
101.12(2), nothing in this review shall relieve the designer of the responsibility for designing a safe
building, structure, or component.
Inquiries concerning this correspondence may be made to me at the telephone number listed below, or
at the address on this letterhead.
Sincerely, Fee Required $ 170.00
Fee Received $ 170.00
Balance Due $ 0.00
Timothy J Lamb
Plumbing Plan Reviewer, Integrated Services WiSMART code: 7657
(608)266-9647, 07:00-03:30 M-f
tim.lamb @wisconsin.gov
cc: Gms Inc Dba Gartman Mechanical Services
Thomas L Braun, Plumbing Consultant, (715) 340-5387, Mon. 7:45-4:30
Bryce Buntin, Dermatology Associates
DAVE RICHARDS Page 4 12/21/2012
Note: Effective January 1, 2012, all codes under the jurisdiction of the Division of Safety&
Buildings will be modified. Code references with prefixes starting with "Comm" will be replaced with
"SPS"to recognize the relocation of the Division of Safety& Buildings from the former Dept. of
Commerce to the Dept. of Safety & Professional Services.Additionally, all S&B codes will be
renumbered and addressed in a "300" series. For future reference,the Wisconsin Commercial Building
Code will be addressed by SPS Chapters 360-366.