HomeMy WebLinkAbout20544 - Raceways/ conductors (12/14/12) CITY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205
215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT
PO Box 1130 OSHKOSH
OSHKOSH WI 54903-1130 CORRECTION NOTICE
ON THE WATER
le-•'e Date 12/14/2012 Re Issue Date Complies No
.ress 1918 W LINWOOD AVE
Sent to ✓j Owner AARON F/TINA M FABIANO 1918 W LINWOOD AVE OSHKOSH WI 54901 -2119
Li Required for Occupancy Occupancy
Introduction WPS personnel informed the inspection department of code violations pertaining to your electrical service. I have verified the
violations and now request that you address the situation.
Item# 1_ Code DSPS 316.230(3) Complies No Comply By 01/13/2013
Description Raceways containing service conductors or cables, or service entrance cable not contained within a raceway, shall not extend
longer than 8 feet into a building to the service disconnect or the first service disconnect of a group of disconnects as permitted
by NEC 230.71. The raceways or conductors shall be considered to have entered the building at the point where they pass
through the outer surface of the building exterior, except as permitted by NEC 230.6.The electrical service cable is enclosed
within the soffit and fascia.
Item# 2 Code Mun Code 11-44 Complies No Comply By 01/13/2013
Description Should any electrical equipment be found unsafe or dangerous to persons or property, the person owning or using such
electrical equipment shall be notified in writing by the Electrical Inspector the need to make the equipment safe. Failure to
comply with such notice within the time specified shall be sufficient cause for the Electrical Inspector to disconnect electrical
service to said equipment or to cause the arrest of such person owning or using such electrical equipment.The electrical
service cable wrapped in tape suggests that it has deteriorated to an unsafe condition due to degradation of the outer cable
jacket.
20544 Page 1 of 2
Item# 3 Code NEC 230.51 Complies No Comply By 01/13/2013
Description Service entrance conductors shall be supported by staples or other approved means. 12"from service heads and enclosures,
30"intervals.
Summary Please contact an electrician to correct the problem in the next 30 days. Feel free to contact me at 920-236-5274 with any
questions as well.
Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment
and/or occupancy. Upon completing the corrections,the owner/contractor/agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 1/13/2013
Office hours are Monday through Friday 7:30 a.m. -4:30 p.m. or by appointment.To schedule inspections please call the Inspection
Request line at 236-128 notin the"address, permit number(when applicable), and the nature of what needs to be inspected.
Signature �' Date./.a'.4
Inspected by: Adam Krause 236-5274 akrause @ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date