Loading...
HomeMy WebLinkAbout20234 - Electrical Space (101512) CITY OF OSHKOSH INSPECTION SERVICES DIVISION ROOM 205 0 215 CHURCH AVE DEPARTMENT OF COMMUNITY DEVELOPMENT PO Box 1130 CORRECTION NOTICE OSHKOSH OSHKOSH WI 54903-1130 ON THE WATER Issue Date 10/15/2012 Re Issue Date Complies No Address 714 OREGON ST Sent to Q Owner 1 ROLANDA GOHEEN 714 OREGON ST OSHKOSH WI 54902 -5968 Required for Occupancy 1 Occupancy Introduction While conducting the rough electrical inspection,the following violations were noted. Item# 1 Code NEC 110.26 Complies No Comply By 11/14/2012 Description Working clearance required for electrical equipment. Working space required by this section shall not be used for storage. Dedicated Electrical Space.A space 30"wide and 36"deep-wall built up to side of the electrical panel. Item# 2 Code NEC 250.64(D)(2) Complies No Comply By 11/14/2012 Description grounding electrode conductor shall be connected between the grounded conductor in each service equipment disconnecting means enclosure and the grounding electrode system. Each grounding electrode conductor shall be sized in accordance with 250.66 based on the service-entrance conductor(s)supplying the individual service disconnecting means. -The GEC is damaged/not all strands are clamped to the ground rod Item# 3 Code SPS 316.250(1) Complies No Comply By 11/14/2012 Description A single electrode consisting of a rod, pipe or plate shall be augmented by one additional electrode of any of the types specified 250.52 (A) (4)to (A) (8).Where multiple rod, pipe or plate electrodes are installed to meet the requirements of this section,they may not be less than 1.8 m (6 ft) apart. 20234 Page 1 of 2 Item# 4 Code NEC 230.70(A)(2) Complies No Comply By 11/14/2012 Description Service disconnecting means shall not be located in bathrooms. Summary Please make arrangements to have these violations corrected in the next 30 days. Feel free to contact me with any concerns or questions at 236-5274. Violations must be corrected and approved by the noted compliance dates of each item. Call for reinspections prior to concealment and/or occupancy. Upon completing the corrections,the owner/contractor/agent must sign and date at the bottom of this notice and return it to the Inspection Services Division by the Compliance Date of 11/14/2012 Office hours are Monday through Friday 7:30 a.m. -4:30 p.m. or by appointment.To schedule inspections please call the Inspection Request line at 236-5128 noting the address, permit number(when applicable),and the nature of what needs to be inspected. Signature Date Inspected by: Adam Krause 236-5274 akrause@ci.oshkosh.wi.us I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes. Print Name Company Signature Date Also Sent to: Q Bldg Q Elec J HULLAR ELECTRIC LLC 2535 KNAPP ST OSHKOSH WI 54902 -9004 �I HVAC Plbg — — f Designer j Other----- — ------ - -------- ---------- J Inspector 20234 Page 2 of 2