HomeMy WebLinkAbout17407-Electric (06/10/2011) INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 6/10/2011 Compliance Date 7/10/2011 Compliance No
Address 726 N MAIN ST
Name Address City State Zip Code
Sent to u Owner RICHARD L GRAMS 414 ATLAS AVE MADISON WI 53714 -3106
Li Required for Occupancy Occupancy
Introduction While conducting a routine neighborhood inspection it was noted that code violations are present on your property. The
electrical supply to the pole sign is a noncompliant condition. Please contact an electrician to make corrections.
Item # 1 Code Mun Code 11 - 22(D) Compliance No Compliance Date 07/10/2011
Description Electricians licensed with the city required to do wiring on any building that is not a single family residence owned and
06/10/2011 occupied by the owner. Wiring done for the purpose of rental or sale of such residences is also limited to a licensed electrician
Last
Updated
Item # 2 Code NEC 400.8(1 -4) Compliance No Compliance Date 07/10/2011
Description Flexible cords - -Uses Not Permitted: (1) As a substitute for the fixed wiring of a structure (2) Where run through holes in walls,
06/1 0/2011 structural ceilings, suspended ceilings, dropped ceilings, or floors (3) Where run through doorways, windows, or similar
openings (4) Where attached to building surfaces
Last
Updated
17407 Page 1 of 2
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
(/ .. DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 6/10/2011 Compliance Date 7/10/2011 Compliance No
Address 726 N MAIN ST
Name Address City State Zip Code
Sent to L✓J Owner RICHARD L GRAMS 414 ATLAS AVE MADISON WI 53714 -3106
LJ Required for Occupancy Occupancy
Introduction While conducting a routine neighborhood inspection it was noted that code violations are present on your property. The
electrical supply to the pole sign is a noncompliant condition. Please contact an electrician to make corrections.
I
Item # 3 Code NEC 406.8(B)(1) Compliance No Compliance Date 07/10/2011
Description 15- and 20- Ampere Receptacles in a Wet Location 15- and 20- ampere, 125- and 250 -volt receptacles installed in a wet
06/10/2011 location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
Last
Updated
Summary Please contact an electrician to correct the problem in the next 30 days. Feel free to contact me at 920 - 236 -5274 with any questions as well.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 7/10/2011
Office hours for obtaining permits are Monday through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please cal he Inspe tion Request line at 236 -5128 noting the address, permit number (when applicable), and the
nature of wha e /j s b i ected.
Signature �. Date � i/
Inspected by: Adam Krause 236 -5274 akrause @ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: LJ Bldg _
LL Elec _
HVAC _
__ Plbg _
LJ Designer _
LJ Other _
LJ Inspector