HomeMy WebLinkAboutReinspection (building) - 04/26/2002 INSPECTION SERVICES DIVISION CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH OSHKOSH WI 54901
ON THE WATER CORRECTION NOTICE
Issue Date 4/26/02 Compliance Date 5/26/02 Compliance No
Address 2351 WESTOWNE AVE Inspected By Allyn Dannhoff 236 -5045
Name Address City State Zip Code
Sent to U Owner MENARDS INC 4777 MENARD DR EAU CLAIRE WI 54703 -0000
U Contractor _ 0 -0000
Li Other _ 0 -0000
U Inspector
Li Required for Occupancy Occupancy Commercial Notice 0 First • Final 0 Other
Introduction A reinspection on 4 - 26 - 02 revealed the following items to address:
Item # 1 Code COMM 51.15 Compliance No Compliance Date 05/26/2002
Description The turnstiles at the front entrace shall allow occupants to pass thru in emergency exit situations.
Item # 2 Code COMM 51.16 Compliance No Compliance Date 05/26/2002
Description Stair risers for the rear, interior mezzanine shall be uniform in rise and run. Maximum rise is 7" and minimum run is 11".
Remember, open risers are not allowed and the tread overhang must be designed so it does not present a catching point for
one'sfoot.
Summary Please call me to let me know the projected time to correct and when they have been corrected so I can respond with a
confirmation inspection.
DEFICIENCIES MUST BE RECTED AND APPROVED BEFORE CONCEALMENT. CALL (920) 236 -5050 FOR INSPECTION.
Signature Date ¶/
l�
Page 1 of 1