HomeMy WebLinkAbout17127-Electric (04/29/2011) rei) INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
OSHKOSH WI 54903 -1130
ON THE WATER
Issue Date 4/29/2011 Compliance Date 5/29/2011 Compliance No
Address 1990 MENARD DR
Name Address City State Zip Code
Sent to ✓ Owner RJDGAD LLC 3109 NICOLET DR GREEN BAY WI 54311 -7211
H Required for Occupancy Occupancy Commercial
Introduction While conducting a routine inspection the following violations were noted. 4/29/11 8:14 AM, 1 called the E.C. to discuss but he
did not return my call.
Item # 1 Code NEC 210.8 Compliance No Compliance Date 05/29/2011 IMMEDIATELY
Description (B) Other Than Dwelling Units. All 125 -volt, single - phase, 15- and 20- ampere receptacles installed in the locations specified in
04/29/2011 (1) through (5) shall have ground -fault circuit - interrupter protection for personnel:
(2) Kitchens
Last
Updated
Item # 2 Code Comm. 16.090 Compliance No Compliance Date 05/29/2011 IMMEDIATELY
Description All electrical power and communication equipment shall be constructed, installed, operated and maintained so as to minimize
04/29/2011 hazards to life and property. All electrical installations shall conform to the National Electrical Code and the requirements of the
State Electrical Code Comm. 16 (exposed exterior wiring which appears to be abandoned from what may have been an
Last exterior sign)
Updated
17127 Page 1 of 2
r • INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
�) DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 4/29/2011 Compliance Date 5/29/2011 Compliance No
Address 1990 MENARD DR
Name Address City State Zip Code
Sent to Q Owner RJDGAD LLC 3109 NICOLET DR GREEN BAY WI 54311 -7211
Required for Occupancy Occupancy Commercial
Introduction While conducting a routine inspection the following violations were noted. 4/29/11 8:14 'AM, I called the E.C. to discuss but he
did not return my call.
Item # 3 Code NEC 200.6 Compliance No Compliance Date 06/03/2011 IMMEDIATELY
Description (A) Sizes 6 AWG or Smaller. An insulated grounded conductor of 6 AWG or smaller shall be identified by a continuous white or
05/04/2011 gray outer finish or by three continuous white stripes on other than green insulation along its entire length.
Last
Updated
Summary To avoid any further inconvenience, please correct the above noted violations immediately. Any questions or concerns please feel free to
contact me @ 920 -236 -5046 or email kbenner @ci.oshkosh.wi.us.
Violations must be corrected and approved within 30 days unless otherwise noted. CaII for remrtspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and tlateat the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 5/29/2011
Office hours for obtaining permits are Monday through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236 -5128 noting the address, permit number (when applicable), and the
nature of w ha inspected.
Signature Date IS/ 4t L�
Inspected by: Kevin Benner 236 -5046 kbenner @ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: ❑ Bldg
Q Elec FOLSKE ELECTRICAL SERVICES LLC 4285 RIPPLE AVE OSHKOSH WI 54904 -6868
HVAC
Plbg
LI Designer
[11 Other BRAT STOP 1190 MENARD DR OSHKOSH WI 54902 -
Q Inspector Brian Noe
17127 Page 2 of 2