HomeMy WebLinkAbout9784-Electric (12/20/2004) INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
OSHKOSH WI 54903 -1130
ON THE WATER
Issue Date 12/20/04 Compliance Date 1/19/05 IMMEDIATELY Compliance No
Address 3465 MOSER ST
Name Address City State Zip Code
Sent to u Owner GNC OSHKOSH LLC 3465 MOSER ST OSHKOSH WI 54901 -0000
j Required for Occupancy Occupancy Industrial
Introduction
While conducting a routine electrical inspection the following violations were noted and reviewed with Mike OIk from Buss
Electric. I told Mike that if the violations were corrected within 30 days, I would not issue a correction notice.
Item # 1 Code NEC 110.16 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Electrical equipment that is likely to require examination, adjustment, servicing, or maintenance shall be marked with field
installed "Arc Flash Warning Labels"
12/20/04
Last
Updated
Item # 2 Code NEC 210.4 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description When more than one nominal voltage system exists in a building each ungrounded conductor shall be identified and that
identification shall be permanently posted at each branch circuit panelboard.
12/20/04
Last
Updated
Item # 3 Code NEC 110.14 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Parallel terminations shall be made with terminals listed for the pupose (grounding)
12/20/04
Last
Updated
Item # 4 Code NEC 250.8 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Sheet metal style screws shall not be used to connect grounding conductors to enclosures
12/20/04
Last
Updated
Item # 5 Code NEC 250.97 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description For circuits over 250V to ground, the electical continuity of metal raceways shall be ensured when concentric k.o.'s are used.
12/20/04
Last
Updated
Item # 6 Code NEC 250.4 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Electrically conductive materials that are likely to become energized shall be connected together and to the electric supply
source in such a manner that establishes an effective ground path. (equipment grounds in the MCC's shall be connected to the
12/21/04 enclosure)
Last
Updated
9784 Page 1 of 3
�� INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
[/ . DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 12/20/04 Compliance Date 1/19/05 IMMEDIATELY Compliance No
Address 3465 MOSER ST
Name Address City State Zip Code
Sent to u Owner GNC OSHKOSH LLC 3465 MOSER ST OSHKOSH WI 54901 -0000
Introduction
u Required for Occupancy Occupancy Industrial
While conducting a routine electrical inspection the following violations were noted and reviewed with Mike OIk from Buss
Electric. I told Mike that if the violations were corrected within 30 days, I would not issue a correction notice.
Item # 7 Code NEC 314.17 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Where the Tray Cable enters a metallic enclosure the cable shall be be installed per NEC 314.7 (A), (B) &(D). (fittings are
required)
12/21/04
Last
Updated
9784 Page 2 of 3
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 12/20/04 Compliance Date 1/19/05 IMMEDIATELY Compliance No
Address 3465 MOSER ST
Name Address City State Zip Code
Sent to u Owner GNC OSHKOSH LLC 3465 MOSER ST OSHKOSH WI 54901 - 0000
Introduction
u Required for Occupancy Occupancy Industrial
While conducting a routine electrical inspection the following violations were noted and reviewed with Mike Olk from Buss
Electric. I told Mike that if the violations were corrected within 30 days, I would not issue a correction notice.
Item # 8 Code COMM 16.11 Compliance No Compliance Date 01/19/2005 IMMEDIATELY
Description Materials, equipment and products which do not comply with the requirements of this chapter shall not be used unless
approved in writing by the Department of Commerce Safety & Buildings or by a qualified independent third party. (Electrical
12/20/04 machinery, controls, motor control centers, etc.) This was discussed with the electrician on 8/3/04.
Last
Updated
Summary To avoid any further inconvenience please correct the above noted violations immediately. Any questions or concems please
feel free to contact me at 920 - 236 -5046.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 1/19/05
Office hours for obtaining permits are Monday through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please call the Inspection Request line at 236 -5128 noting the address, permit number (when applicable), and the
nature of what needs to be inspected.
Signature Date / ap-1/6 9 Aka
Ins •''ggr : Kevin Benner 236 -5046 kbenner@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: a Bldg
• Elec BUSS ELECTRIC INC W6166 GREENVILLE DR GREENVILLE WI 54942 -9676
u HVAC -
• Plbg _
▪ Designer
✓j Other OCCUPANT 3465 MOSER ST OSHKOSH WI 54901 -0000
_J Inspector
9784 Page 3 of 3