HomeMy WebLinkAbout17063-Plumbing (03/25/2011) 0 INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 3/25/2011 Compliance Date 4/24/2011 Compliance No
Address 1727 ELMWOOD AVE
Name Address City State Zip Code
Sent to Lij Owner AARON E DROESSLER/RONALD C WIE 3139 BROOKS RD OSHKOSH WI 54904 -8532
Required for Occupancy Occupancy
Introduction A final inspection of the plumbing on 3/24/2011 revealed the following violations:
Item # 1 Code Comm. 82.30(9) Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description Proper drainage pattern fittings are required from vertical to horizontal at the kitchen sink drain in basement near the sill plate
03/25/2011 and at the 3" stack in the basement receiving the 2nd floor waste discharge.
Last
Updated
Item # 2 Code Comm. 82.40(4) Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description A control valve shall be installed in the supply piping to each exterior hose bibb.
03/25/2011
Last
Updated
Item # 3 Code Comm. 82.40(7) Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description The sizing of the water supply system shall be based on the empirical method and limitations outlined in this subsection or on
03/25/2011 a detailed engineering analysis acceptable to the department. A water calculation worksheet is required to be submitted to
insure proper pipe sizing.
Last
Updated
Item # 4 Code Comm. 82.40(8) Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description All plumbing fixtures, appliances and appurtenances with 3/8" or larger inlet openings and with solenoid actuated quick closing
03/25/2011 valves shall be provided with water hammer arrestors. The dishwasher and automatic clothes washer fixture supplies required
hammer arrestors.
Last
Updated
Item # 5 Code Comm. 82.41(3) Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description Water supply systems and the connection of each plumbing fixture, piece of equipment, appliance
03/25/2011 or nonpotable water piping system shall be designed, installed and maintained in such a manner to prevent the contamination
of water supplies by means of cross connections. The hose bibb installed in the basement at the water meter requires proper
Last cross connection protection.
Updated
17063 Page 1 of 3
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 3/25/2011 Compliance Date 4/24/2011 Compliance No
Address 1727 ELMWOOD AVE
Name Address City State Zip Code
Sent to U Owner AARON E DROESSLER/RONALD C WIE 3139 BROOKS RD OSHKOSH WI 54904 -8532
Hi Required for Occupancy Occupancy
Introduction A final inspection of the plumbing on 3/24/2011 revealed the following violations:
Item # 6 Code Comm. 82.41 Table 2 Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description Self- draining outside silcock complying with ASSE 1019A is required to be installed to drain dry. Silcock is currently
03/25/2011 backpitched preventing the outlet to drain down.
Last
Updated
17063 Page 2 of 3
(1D INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER OSHKOSH WI 54903 -1130
Issue Date 3/25/2011 Compliance Date 4/24/2011 Compliance No
Address 1727 ELMWOOD AVE
Name Address City State Zip Code
Sent to Owner AARON E DROESSLER/RONALD C WIE 3139 BROOKS RD OSHKOSH WI 54904 -8532
Li Required for Occupancy Occupancy
Introduction A final inspection of the plumbing on 3/24/2011 revealed the following violations:
Item # 7 Code Comm. 21 Compliance No Compliance Date 04/24/2011 IMMEDIATELY
Description Draft stopping is required to be provided in the basement at the ceiling /floor connections below the bathtub and at the 3" pvc
03/25/2011 pipe penetrations below the 1st floor bathroom and laundry area.
Last
Updated
Summary You shall be required to comply and call for re- inspection prior to occupancy.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 4/24/2011
Office hours for obtaining permits are Monday through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please call th Inspection Request line at 236 -5128 noting the address, permit number (when applicable), and the
nature of what needs a inspected.
Signature Date ' 2 . ) / / I
Inspected by: Paul Wolf 236 -5052 pwolf @ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: u Bldg -
u Elec -
u HVAC -
u Plbg BARTELT PLUMBING 2659 YORKTON PL Oshkosh WI 54904 -0
Li Designer
_ J Other -
y Inspector John Zarate
17063 Page 3 of 3