Loading...
HomeMy WebLinkAboutHVAC - 03/30/1978 COUNCIL- MANAGER ADMINISTRATION T • March 30, 1978 J. Thomas Sizelove, Jr. P.O. Box 4347 Brookwood Madison, Wis. 53711 Heating and ventilation plans new auto parts sales 6 service building Jack Meyer, Owner 2200 Montana St., Oshkosh J. Thomas Sizelove, Jr., designer Dear Sir: Heating and ventilating plans have been reviewed by this office for compliance with important code re- quirements. The drawings are stamped "Construction may proceed." All items that are required to be changed by this letter, must be corrected before commencing that part of the work. This approval is not a Heating Permit. Necessary city permits must be secured before commencing work. You are hereby advised that he owner, as defined in Chapter 101.01 (i) of the Wisconsin State Statues, is responsible for all code requirements not specif- ically cited herein. Code requirements are set forth in Chapter 50 thru 64 of the rules of the Department of Industry, Labor and Human Relations. The building will be inspected during construction and a final inspection will be made after completion to insure complete compliance with City and State codes. The architect, professional engineer, builder or owner shall keep at the building, as evidence of approval, one set of plans bearing the stamp of approval. Ind. 64.19 It appears that outside air intakes may be ctdser than 10 feet (measured in any direction) from outlets emitting products of Combustion, exhaust vents, or plumbing vents. CITY HALL • 215 CHURCH AVENUE • P. O. BOX 1130 • OSHKOSH, WISCONSIN 54901 P. 0. BOX 1130 • OSHKOSH, WISCONSIN 54901 J. Thomas Sizelove, Jr. March 30, 1978 Page two Ind. 50.12 Structural data is required to show that the roof purlins are adequate to support the weight of the furnaces. Ind. 64.18 A negative pressure shall be maintained in the toilet rooms and garage area. Sincerely EDWARD L. R .MER Chief Building Inspector CC: Mr. Jack Meyer 637 W. S. Park Ave Wm. J. Petri 2202 -a Indiana Ave. Sheyboygan, WI 53088 ELR:cm • J. Thomas Sizelove, Jr. March 30, 1978 Page Two Ind. 50.12 Structural data is required to show that the roof purlins are adequate to support the weight of the furnaces. Ind. 64.18 A negative pressure shall be maintained in the toilet rooms and garage area. Sincerely, r EDWARD L. :EIMER Chief Bui ding Inspector ELR:njp cc: Mr. Jack Meyer 637 W. South Park Avenue // Mr. William J. Petri ,,// 2169 Verla Drive Oshkosh, WI 54901 l PLANS APPROVAL Department of Safety & Building Division Box 7946 APPLICATION INDUSTRY, LABOR AND HUMAN RELATIONS 201 E. Washington Avenue SB -118 (Rev. 6/77) Madison, Wisconsin 53707 INSTRUCTIONS: Fill in all applicable data. Submittal of Plan Approval Application form is required with each plan submittal. Examination and inspection fees, as determined on back of form, are required to be submitted with a minimum of three sets of plans. Data required on plans is described in code section Ind 50.12. Codes can be purchased from the Department of Administration, Document Sales, 202 S. Thornton Ave., Madison, 53703 1. THIS APPLICATION IS FOR: li.g Building Plan Approval ['Heating Plan Approval ❑Other 2. PLANS FOR: 1C1 New Building ❑Addition ❑Alteration ['Structural ['Footing & Foundation ❑Revision to previously approved plans ❑Other 3. PROJECT INFORMATION Name of Owner Building Occupancy or Use Designer or Design Firm Jack Meyer Auto Service Center Wm. J Petri, Designer Company Tenant Name, if any Street & No. 2202 -A Indiana AVE?. Street & No. Building Location, Street & No. City State & Zip 637 W. So. Park Ave. 2200 Montana St Winn. Sheboygan, Wi. 53088 City State & Zip City M County Phone Villag Qshkosh Wi. 54901 Town 414-457-2511 Previous Owner if any Return Plans to ['Owner (iAesigner Z3 35 / O 4. DETERMINATION OF FEES SEE CHAP. IND. 69 FOR FULL SCHEDULE FOR OFFICE USE ONLY SEE BACK OF PAGE FOR FEE CALCULATION AND ABBREVIATED FEE SCHEDULE 4a Building Plan Fee $ T i., — Amount Rec'd Total Volume 4b Heating - Ventilation Fee $ Date Recd 4c Other $ Receipt No. 24826 4d Inspection $ 50.00 4e TOTAL $ 7.6 5. OTHER INFORMATION 5a Type of Construction ['Fire Resistive —Type A ❑Metal Frame Protected ['Exterior Masonry ❑Wood Frame Protected ❑Fire Resistive —Type B ❑ Heavy Timber gMetal Frame Unprotected :Mood Frame Unprotected 5b Mechanical Information: Type of Heating Net Rating of Heating Units 5c SOIL BEARING CAPACITY (See Ind.53.21) Yes No Method used to determine capacity: Check One- Verified Presumptive ❑ p Sprinkler System Provided? Check Value Used- PSF 2000 ❑ , 3000 �, 4000 ❑ ❑ ® Fire Alarm Provided? 6000 0,12000 ❑ , Other ❑ IJ Other Detection System Provided? ❑ El Emergency Power Provided? 6. DESIGN AND SUPERVISION (IND 50.13) The design, plans, computations and specifications for this project have been prepared under my supervision. I am registered as an ❑ Architect ❑Engineer Designer in Wisconsin as provided in Section 443.01 of the Wisconsin Statutes.jl am not registered. If this building, existing and additions, contains over 50,000 cu. ft. total volume, it must be designed by a registered person. I hereby permit the Dept. to sell plan copies without further written authorization ❑Yes lit]No SEE BACK OF PAGE FOR ADDITIONAL INFORMATION ON PUBLIC RECORDS. Sigrynture of die 'g r 9 Registration Number Date L/ /. �.� / 0197 If this building, existing anp( dditions, contains over 50,000 cu. ft. total volume, the construction of this project shall be under fhe sf ervision P of a Wisconsin registered ar itect, engineer or in the case of heating and ventilating, designer. Plans for buildings over 50,000 cu. ft. will not be approved until the name of the supervising professional is known. Name of Supervising Professional Registration Number NOTE: The supervising professional shall file a written report with the Department upon completion of construction. ( Ind 50.13 (3) (c)] I r 4. DETERMINATION OF FEES INSTRUCTIONS: 1. Refer to fee schedule shown below. 2. Enter area of each floor in appropriate space. 3. Enter height of each floor (Height includes attic and space between floors). 4. Compute volume of each floor /attic space and total volume for building.* 5. Compute building and /or heating fee per building. 6. Enter other fee (if any) in space per building. 7. Compute inspection fees per building. 8. Total fees and transfer information to front page. The "total volume" is determined by the overall outside dimensions of length, width and height. EXAMINATION FEES PER BUILDING NOTE Building Plan Fee: Fee. 60 per 1000 cu. Ft. (1) Heating & Ventilating Plans submitted separately Minimum Fee $25.00 require an inspection fee of $44.00. Heating & Ventilating Plan Fee: Fee. 40 per *12) Plans other than building or heating require an 1000 cu. ft. Minimum Fee $25.00 inspection fee of $25.00. Alterations to bldgs: Fee $1.50 per $1,000 (3) Warehouses - Reduce plan examination fees (Not est. cost. Minimum fee $25.00 inspection fees) by 30 %. *Structural Plans $25.00 per Bldg. (4) Building plan fee for Bldgs. exceeding 1,000,000 Revision to approved Plan $25.00 cu. ft. is $600 plus $0.40 per 1,000 cu. ft. in excess *Exhaust Systems $25.00 per plan (Govt. Owned only) of 1,000,000 cu. ft.. *Spray Booths $25.00 per Plan (Govt. Owned only) (5) Heating & Ventilation plan Fee for Buildings Permit to Start Construction (SB -198) $35.00 per Bldg. exceeding 1,000,000 cu. ft. is $400 plus $0.25 per *Footing & Foundation Plans $25.00 per Bldg. 1000 cu. ft. in excess of 1,000,000 cu. ft. *Stadium, Grandstand, Bleacher $10.00/1000 Seats Minimum Fee $25.00 *Fire Escapes $25.00 per fire escape INSPECTION FEES PER BUILDING: Building Volume /Alt. Cost Fee Up to 25,000 cu. ft. /dollars $50.00 25,001 - 100,000 cu. ft. /dollars $75.00 100,001 - 500,000 cu. ft. /dollars $100.00 500,001 - 1,000,000 cu. ft. /dollars $125.00 In excess of 1,000,000 cu. ft. /dollars $150.00 No. of Floors Area Height Total each Floor Total Vol. /1000 x Exam Fee Building Plan Fee Basement /Ground to • 6X11..16 30! -24 326 cu. ft. x .60 = $ 1st Floor 40x50 x 12. 24500 cu. ft. Total Vol. /1000 x Exam Fee Heating Ventilating Fee 2nd x = cu. ft. x .40 = $ 3rd x = cu. ft. CiStructural $25.00 ■ • tion $1.50/1000 Other 4th & 5th ■ DExhaust $25.00 attic & etc. x = cu. ft. ■ DRevision $25.00 $ Total Volume or 2+826 Inspection Fee Total Cost of Alteration = $ 50.00 Total TRANSFER ALL DOLLAR AMOUNTS AND VOLUME TO FRONT PAGE PUBLIC RECORDS A copy of the plans submitted with this application will be held in the files of this division and are considered Public Records. Interested persons may, upon request, review the plans and files in this office. Copies of the plans will be sold, upon request and fee payment, unless the designer specifically indicates that he /she wishes the sale restricted. ENGINEERING DATA 3 FORCED AIR GAS FURNACES HEATING UNITS GS11 SERIES — HORIZONTAL STOWAWAY GAS 60,000 to 160,000 Btuh INPUT Page35 Add -On Cooling 1 -1/2 thru 5 Nominal Tons July 15, 1977 • Factory Assembled and Tested • Several Sizes Available _ t • Low Cost Installation • Sized For Air Conditioning . , s • Durable Heat Exchanger s , � • Efficient Steel Burners • Compact Cabinet Design • Complete Service Access '.. -"Ili: , ----', • Powerful Direct Drive Blower • Right or Left -Hand Air Discharge W`� '� • Controls Furnished and Installed �� Horizontal STOWAWAY Gas Furnaces Provide Dependable, Space- Saving Comfort Systems The Lennox GS11 Series horizontal STOWAWAY gas fur- blower service access is provided at the front or rear of the naces are designed for installations that will save valuable unit. Units are shipped for left -hand air discharge. Rugged floor space for other purposes. These versatile units can be heat exchanger is designed for maximum heat transfer and installed on combustible flooring in a attic space, on a slab in minimum air resistance. Equipped with steel burners for crawl space, hanging from joists in a basement or crawl long service life and maximum efficiency. Quiet operating space, suspended from the ceiling in a utility or furnace blower has sufficientcapacitytohandleadd-onaircondition- room.. Lennox direct expansion evaporator coolingunit,elec ing airvolume requirements. Units are A.G.A. Certified for tronic air cleaner and automatic humidifier can easily be use with natural or propane gas. Air filter(s), filter adapter added to the horizontal gas furnace for a complete all and hanger rod kit are available as optional equipment. Units season Total Comfort system. Heavy gauge steel cabinet has are test operated at the factory and shipped completely deluxe baked -on enamel finish. Heating section is insu- assembled ready to install. Installer has only to locate unit, fated to cut heat loss. Cabinet has provisions for suspending. mount thermostat, make duct, flue, gas line and electrical A choice of flue connection, burner, controls location and supply connections to complete a low cost installation. Typical Applications _� �0 +o I _ �5: '�'( T —' L L1= - - Crawl Space Installation Basement Installation Attic Installation With cooling coil, electronic air With cooling oil . cleaner and automatic humidifier g With cooling coil, electronic air cleaner and automatic humidifier NOTE — Specifications, ratings and dimensions subject to change without notice. FEATURES Rugged Cabinet — Constructed of heavy gauge cold rolled steel Fan and Limit Controls — Factory installed, wired and accurately with a durable baked -on enamel finish. Heating section of cabinet is located. Fan control assures proper blower operation and has ad- completely lined with foil faced fiberglass insulation resulting in low justable blower off temperature setting. Continuous blower opera - cabinet surface temperatures and quiet operation. Flanges on sup- tion may be accomplished by adjusting the fan control to the ply and return air openings permit ease of duct connection. Knock- minimum temperature setting. Dual limit controls, one located at outs are furnished in the top and bottom panels for hanger rods. Flue each end of the heating section, provide protection from abnormal connection can be made at front or rear of unit. Large removable operating conditions. doors, front and rear, provide complete service access to blower Wiring Junction Box Power supply and thermostat wiring con - compartment. Doors are equipped with knobs for easy removal. nections are made at junction box. Conveniently located on front of Units are shipped for left -hand supply air discharge. For applications the unit for easy access. Junction box lid has a screw terminal board requiring a change in supply air direction simply relocate the draft for ease of thermostat wiring connections. hood, controls, wiring channel enclosure, gas valve and the main burner with pilot to the opposite side of the unit. Transformer — 24 volt control transformer is furnished as standard equipment and is factory installed on the wiring junction box. Efficient Direct Drive Blower — Units are equipped with quiet, vari- able speed direct drive blowers. Each blower is statically and dynam- Blower Cooling Relay — Furnished as standard equipment and fac ically balanced. Multiple -speed motor is resiliently mounted. A tory installed on the wiring junction box. Relay activates blower choice of blower speeds is available on each blower. See blower operation during cooling cycle. Relay is not furnished with the performance charts. Change in blower speed is easily accomplished GS11 D -60 and GS11D-80 models. by a simple change in wiring. Thermostat (Not Furnished) — Heating thermostat is optional equipment and must be ordered extra. For all season applications a Durable Heat Exchanger Clamshell type heat exchanger is con- heating - cooling thermostat is furnished with the condensing unit. structed of heavy gauge cold rolled steel and is designed for normal Fresh Air Inlet (Optional) — Fresh air inlet provides entry of outdoor expansion and contraction without metal fatigue. Design provides air into return air system of installation. Equipped with internal mesh long service life, maximum efficiency and minimum resistance to air screen. Connects to 6" round pipe. Order number BM -3632. flow. Air Filters (Optional) — One inch thick frame filters are available and Steel Burners — Each burner has two rows of practically continuous must be ordered extra. Filter media is washable or vacuum cleanable steel ports which result in quiet and clean combustion. Burner and polyurethane coated with oil for increased efficiency. Use RP prod - port surfaces are smooth with no ledges or ridges to accumulate lint ucts filter coating no. 418 (P -8 -5069) when reoiling. See specification and dirt. A crossover igniter, perpendicular to the main burner, table for filter size. carries a positive flame from burner to burner to achieve fast, sure and safe ignition. Individually removable burners and pilot burner Filter Adapter (Optional) — Field installs to the return air inlet of the are mounted in a slide -out tray for ease of service. A primary air unit and extends into the return air plenum or duct exterior to the shutter assembly is furnished on all units. The air shutters are linked blower section. Filter(s) are accessible for removal and replacement to each adjacent burner so adjustment of the outboard burner ad- through front and rear blower section access doors. Filters are not justs all the other burners at the same time. included with adapter and must be ordered extra. Automatic Gas Controls — Silent operating gas controls provide Hanger Rod Kit (Optional) — Four hanger rods are available for 100% safety shutoff. Manual lighted pilot burner provides sure and suspending the unit. Eyebolt type steel rods have 3/8 -16 threads on safe operation. For propane models a field conversion kit is required one end and are 28 inches long. Rods extend through the cabinet and and must be ordered extra. are secured under the unit when installed. Order number 78A75 . SPECIFICATIONS GS11 -60 AND GS11 -80 MODELS Model Number GS11D -60 GS11Q3 -60 GS11D -80 GS11D2 -80 GS11Q3 -80 Btuh input 60,000 60,000 80,000 80,000 80,000 Btuh output at bonnet 48,000 48,000 64,000 64,000 64,000 Flue size (in.) 4 4 5 5 5 A.G.A. certified high statics (in. wg.) .50 .50 .50 .50 .50 Gas piping size (in.) (Nat. & Prop.) _ 1 /2 1/2 1/2 1/2 1/2 Blower wheel nom. diam. x width (in.) 10 x 6 10 x 6 9 x 6 10 x 6 10 x 6 Blower motor horsepower 1/5 1/3 1/5 1/4 1/3 Tons of additive cooling - - -- 1 -1/2, 2 or 2 -1/2 - - -- 1 -1/2 or 2 2 -1/2 or 3 Net weight (Ibs.) (1 package) 155 161 170 177 180 Electrical characteristics 120 volts — 60 hertz — 1 phase (all units) Optional Model No. FC3 - 60 FC3 - 60 FC3 - 80 FC3 - 80 FC3 - 80 Filter Adapter Net weight (Ibs.) 8 8 10 10 10 Optional *Filter, no. & size (in.) (1) 15 x 20 x 1 (1) 15 x 20 x 1 (1) 16 x 20 x 1 (1) 16 x 20 x 1 (1) 16 x 20 x 1 *Frame filters with cleanable polyurethane media. Filters must be ordered extra. NOTE — For Propane units a field changeover kit is required and must be ordered extra. Order number 76A77 all models. –36— SPECIFICATIONS GS11 -100 AND GS11 -120 MODELS Model Number GS11D2 -100 GS11Q4 -100 GS11Q4 -120 Btuh input 100,000 100,000 120,000 Btuh output at bonnet 80,000 80,000 96,000 Flue size (in.) _ 5 5 5 A.G.A. certified high statics (in. wg.) .50 .50 .50 Gas piping size (in.) (Nat. & Prop.) 1/2 1/2 1/2 Blower wheel nom. diam. x width (in.) 9 x 8 10 x 8 10 x 10 C Blower motor horsepower 1/4 2 o 1/3 1/2 Tons of additive cooling or 2-1/2 3, 3 -1/2 or 4 2 -1/2, 3, 3 -1/2 or 4 Net weight (Ibs.) (1 package) _ 195 202 230 Electrical characteristics _ 120 volts -60 hertz — 1 phase (all units) Optional Model No. _ FC3 -100 FC3 -100 FC3 -120 Filter Adapter Net weight (Ibs.) 12 12 13 Optional *Filter(s), no. & size (in.) (1) 20 x 20 x 1 (1) 20 x 20 x 1 (2) 15 x 20 x 1 Coe *Frame filters with cleanable polyurethane media. Filters must be ordered extra. NOTE — For Propane units a field conversion kit is required and must be ordered extra. Order number 76A77 all models. GS11 -140 AND GS11 -160 MODELS Model Number GS11Q3 -140 GS11Q5 -140 GS11Q5 -160 Btuh input 140,000 140,000 160,000 Btuh output at bonnet 112,000 112,000 128,000 Flue size (in.) 6 6 6 A.G.A. certified high statics (in. wg.) .50 .50 .50 Gas piping size (in.) (Nat. & Prop.) 1/2 1/2 1/2 Blower wheel nom. diam. x width (in.) 10 x 10 12 x 9 12 x 12 Blower motor horsepower 1/3 3/4 3/4 Tons of additive cooling 2 -1/2 or 3 3 -1/2, 4 or 5 4 or 5 Net weight (Ibs.) (1 package) 253 266 291 Electrical characteristics 120 volts — 60 hertz —1 phase (all units) Optional Model No. FC3 -140 FC3 -140 FC3 -160 Filter Adapter Net weight (lbs.) 15 15 17 Optional *Filter(s), no. & size (in.) (1) 15 x 20 x 1 (1) 16 x 20 x 1 (2) 16 x 20 x 1 *Frame filter with cleanable polyurethane media. Filters must be ordered extra. NOTE — For Propane units a field conversion kit is required and must be ordered extra. Order number 76A77 all models. HORIZONTAL EVAPORATOR UNIT ADAPTERS Opt.) HIGH ALTITUDE DERATE Factory fabricated adapters are available for matching supply air If the heating value of the gas does not exceed values listed in table, derating outlet of furnaces to inlet air opening of evaporator units listed in of unit is not required. Should the heating value of the gas exceed the table table below. Field fabricated adapters are required to match evap values, or if the elevation is greater than 6,000 feet above sea level it will be orator units other than those shown in the table. See section Cooling necessary to derate unit. Lennox requires that derate conditions be 4% per Units — Blower Coil Units for complete Evaporator Unit data. thousand feet above sea level. Thus at an altitude of 4000 feet, if the heating value of the gas exceeds 1000 Btu /ft the unit will require a 16% derate. Furnace Model No. Horizontal Evaporator ' Adapter Elevation Above Maximum Heating Coil Model No. Model No. Sea Level (Feet) Value (Btulft CH2 -21 FF & CH2 -26FF BQ360 -26 5001 — 6000 900 GS11Q3 -60 CH3 -41FF BQ360-41 4001 —5000 950 3001 —4000 1000 GS11D2-80 CH2-21FF & CH2 -26FF BD280 -26 2001 — 3000 1050 GS11 Q3 -80 CH3-41FF BQ380 -41 Sea Level — 2000 _ 1100 GS11D2 -100 CH2 -26FF BD2100 -26 GS11D2-100 GS11Q4 -100 CH3 -41FF BQ4100 -41 A.G.A. INSTALLATION CLEARANCES (inches) GS11Q4 -100 CH3 -51FF B04100 -51 GS11Q4 -120 CH3 -41FF BQ4120 -41 Rear & Sides 6 CH3-51FF BQ4120 -51 Top 8 GS11Q3 -140 CH3 -41FF BQ3140 -41 Floor Combustible GS11Q5 -140 CH3 -51FF BQ5140 -51 *Flue 6 CH3 -65FF BQ5140 -65 This clearance to all flue pipes except type "B." Type "8" flue clearance is GS11Q5 - 160 CH3 - 51FF BQ5160 - 51 listed by U.L. CH3 - 65FF _ BQ5160 - NOTE — A clearance of at least 30 inches should be provided at the front of the unit for combustion air and servicing. —37— DIMENSIONS (inches) NOTE — Provide adequate service clearance of at least 30 inches at front of unit. FC3 -120, FC3 -140 or FC3 -160 OPTIONAL FC3 -60, FC3 -80 or FC3 -100 Optional Filter Adapter GAS VALVE Optional Filter Adapter L I. / LOCATION y \i L el \ K SUSPENDING HOLES_ i 1 (Top and Bottom Panels) ° 314 r H t ■ I ' RETURN AIR\ 1 / -. PLENUM t (Not Furnished RETURN AIR by Lennox) PLENUM ■ TOP VIEW (Not Furnished by Lennox) �{ A C 8� 518 c 13-1/2 em. BLOWER ACCESS 518 i + 314 _ (Front and Rear) 1 G ELECTRICAL WIRING — - - a*E—.0. (15116 - 9 JUNCTION —, FLUE OUTLET BOX *D n (Front or Rear) U r FAN & LIMIT CONTROL r / ' o , *D SUPPLY VALVE 1 , AIR — 1 \\ \ // / OPENING 1 \ - -' \ n , 1 1 • — _1 / s 4F *Return air and supply air BURNER ACCESS NOTE — Drafthood and controls may be A - F opening are same size. (Front or Rear) used on either side of the unit. DISCHARGE END FRONT VIEW Model No. A B C D E F G H J K L GS11D -60, GS11Q3 -60 50 22-3/4 11-5/8 21 9-3/4 7/8 2-5/16 48-1/2 4-1/8 3-3/4 11 GS11D -80, GS11D2 -80, GS11Q3 -80 50 22-3/4 14-1/8 21 12-1/4 7/8 2-13/16 48-1/2 6-5/8 3-3/4 10 -9/16 GS11D2 -100, GS11Q4 -100 50 22-3/4 16-5/8 21 14 -314 7/8 2-13/16 48-1/2 9-1/8 3-3/4 13-3/8 GS1104 -120 50 22-3/4 19-1/8 21 17-1/4 7/8 2-13/16 48-1/2 11 -518 3-3/4 11-11/16 GS11Q3 -140, GS11Q5 -140 53 24 21-5/8 21-3/4 19-3/4 1-1/8 3-5/16 51-1/2 10-1/2 5-9/16 10-13/16 GS11Q5 -160 53 24 24-1/8 21-3/4 22-1/4 1-1/8 3-5/16 51-1/2 13 5-9/16 11-1/16 BLOWER DATA GS11D -60 BLOWER PERFORMANCE GS11Q3 -60 BLOWER PERFORMANCE External Static Air Volume (cfm) @ Various Speeds External Static Air Volume (cfm) Cad Various Speeds Pressure (in. wg.) High Medium Low Pressure (in. wg.) High Medium Low .15 925 650 500 .15 1410 890 650 .20 910 650 495 .20 1380 870 630 .25 890 640 495 .25 1350 850 620 .30 870 630 490 .30 1310 830 600 .35 850 620 490 .35 1280 820 580 .40 825 600 485 .40 1240 800 560 .45 800 585 480 .45 1200 770 540 .50 775 575 470 .50 1160 750 520 OTE I cfm is measured external to furnace. Filter resistance not included. NOTE — All cfm is measured external to furnace. Filter resistance not included. —38-- BLOWER DATA GS11D -80 BLOWER PERFORMANCE GS11D2 -80 BLOWER PERFORMANCE External Static Air Volume (cfm) (a? Various Speeds External Static Air Volume (cfm) @ Various Speeds Pressure (in. wg.) High Medium Low Pressure (in. wg.) High Medium Low .15 1000 765 600 .15 1155 930 800 .20 970 755 595 .20 1140 925 795 .25 940 735 590 .25 1115 920 790 .30 900 715 580 .30 1090 910 785 .35 865 690 570 .35 1070 890 775 .40 820 665 545 .40 1050 855 760 .45 770 635 510 .45 1025 835 735 .50 720 600 465 .50 1000 800 700 NOTE -All cfm is measured external to furnace. Filter resistance not included. NOTE -All cfm is measured external to furnace. Filter resistance not included. GS11Q3 -80 BLOWER PERFORMANCE External Static Air Volume (cfm) @ Various Speeds Pressure (in. wg.) High Medium Low .15 1510 1190 805 .20 1470 1175 805 .25 1440 1160 805 .30 1400 1140 800 .35 1370 1130 795 .40 1330 1115 790 .45 1295 1095 770 .50 1250 1060 750 NOTE -All cfm is measured external to furnace. Filter resistance not included. GS11D2 -100 BLOWER PERFORMANCE GS11Q4 -100 BLOWER PERFORMANCE External Static Air Volume (cfm) @ Various Speeds External Static Air Volume (cfm) @ Various Speeds Pressure (in. wg.) High Medium Low Pressure (in. wg.) High Medium Low .15 1240 1025 900 .15 1790 1340 1040 .20 1210 1025 900 .20 1760 1340 1040 .25 1185 1020 900 .25 1730 1340 1040 .30 1150 1010 890 .30 1700 1340 1040 .35 1120 990 880 .35 1670 1330 1035 .40 1080 960 860 .40 1630 1320 1030 .45 1040 930 830 .45 1590 1300 1025 .50 1000 900 800 .50 1550 1270 1020 NOTE -AII cfm is measured external to furnace. Filter resistance not included. NOTE -All cfm is measured external to furnace. Filter resistance not included. GS11Q4 -120 BLOWER PERFORMANCE External Static Air Volume (cfm) (E Various Speeds Pressure (in. wg.) High Medium Low .15 1210 .20 1840 1210 .25 2300 1820 1210 .30 2260 1800 1210 .35 2210 1770 1200 .40 2160 1740 1200 .45 2110 1710 1190 .50 2050 1670 1170 NOTE -All cfm is measured external to furnace. Filter resistance not included. -39- BLOWER DATA GS11Q3 -140 BLOWER PERFORMANCE GS11Q5 -140 BLOWER PERFORMANCE External Static Air Volume (cfm) (a) Various Speeds External Static Air Volume (cfm) @ Various Speeds Pressure (in. wg.) High Medium Low Pressure (in. wg.) High Medium Low .15 .15 2560 1810 1510 .20 1340 1020 .20 2550 1800 1500 .25 1325 1005 .25 2530 1780 1480 .30 1300 980 .30 2510 1770 1470 .35 1780 1265 960 .35 2470 1750 1450 .40 1745 1255 925 .40 2430 1720 1440 .45 1710 1195 895 .45 2390 1690 1420 .50 1680 1180 885 .50 2360 1660 1390 NOTE —All cfm is measured external to furnace. Filter resistance not included. NOTE —All cfm is measured external to furnace. Filter resistance not included. GS11Q5 -160 BLOWER PERFORMANCE External Static Air Volume (cfm) (c@ Various Speeds Pressure (in. wg.) High Medium Low .15 2150 1650 .20 2140 1640 .25 2710 2120 1620 .30 2700 2100 1610 .35 2680 2080 1590 .40 2650 2060 1580 .45 2620 2030 1540 .50 2500 1960 1480 NOTE —All cfm is measured external to furnace. Filter resistance not included. rt 1 /fit 4 MAR DEPARTMENT OF COMMUNITY DEVELOPMENT —40— - --- I —4c4,. . — m • • • Pi' :1 P.' 7 P ;42 Ps :-■ P° ?' .' P / P'' 7 2 I ' Ci e - i >to *Is.a.,x >. ; + : ---, ri a t 1 i" 8 I c I 8 '' • :T 0 e_ P.9- 't 0 .1 cT ,...'"' , 9: -7 ,i zr ,.- 9.. ;-..: o. :-...-. ii: Q- 5* Jo 0 '2 -0 c -.... a . ' O — 1 Fe. in of ' Vf Z 1 0.. " * 41 2'. .0 — .. • C 2 • 0 2 0- IF 0- il 42 . r- c 0 0 PE. n 1 ") - :5- ' 3 e 1 i 0 . . , . . 0 -,... 0 , 4_ • , I : t %. 1 i z ... 01 ° - I 1 teb 4. ■ --- s .. c 1 4 t- I 1 ✓ 1 i y 1 "TI 4 0 O. 0 '''''■ 3: tt* I /4 t 1 % 1 il 7. : - al.:: ,... r>. --■ eL la- • -' 0 - - ' 1 1 2.1 I 1 ...11112 i 1 r 111111EIMMIligill __ . 4 ' r> i -0,„1 1 1 • . ' '' • - • i "Far; il izt ° I 1 1 i I 1 0 . „iim IN 1P i { l' 1.11 i I I I , 4 ....` .,... \ 1 ' . i 11111111 i C- c I . 11 C> r•10 , i fr r iV . i I 17? i t I I I 11111 i iiiiiilig .431111111011111111115917 a I CZ ° 11.00 ix, - , N./ 1 r • 34 ■T ' N I I 4 0 14 0 n C:) II C.) I I , il 11111 le it Ilen5. .. , ,.... ,, .... 1111 ,,,, vs, ,. .. , , + 1 *- > > — i ‘7 i 1 I I ° a r - t• tr 4i ) g g I I 1 i ! ... • 1 1 i 11 i I ga 41 f i i 3 > 11111E1 'i 111111111NIMININI 2.(24. ,. .. , . ,t , , , 5.- -.. i i 1. I I I 113 - lir 0 r _ illk i uz2r , ZI 3 i• 2 . I! .. , • i 2 4 I 13 . , 1 I 41 kr, ' N ■ - ! s y8 tr , of, fN il: z NA % \ cA ... c. lir , ,,,,,, a' rel. 1,, r , 1 ... .. II 4 1 .1111 t -,4. °i)• N "' .:,,.... Sbe. lb 2 Z 0., z r • , i iQ 1 IN El * 0 > milim.E. 1 ill likl 0 ..,,,.;, _... „,---.. . E ' r ''s I . 11 ■S's 1 I ," f i I I.- NO "•*. - .• if 4 , IR) ; •C 0 1 1 it g g 1 I -. •" 1 , r- c74- i I I I t c, -9> .1 .4 i r. 7 ,...,, r 2 r- - 0 ' - i --- _, 1 — — FII: f ... OP 0 .g. '',.', .• 't ' • -KR 1 1 1 t ' 0 C3 cr. rTI z 1 4 I V41 I • I I '4 til 1 ; um - ill ■ I . M LI 0 ; I i DO , . . i • 0 r - 6 4 . 1 t•' ' 1 : . I . t 1 .. . i t I 1 2i*" : I . 4 4. STEEL BUILDING CO. sea r DIVI I f EARL S ON o S ,Inc. Fond du Lac, WI. Oshkosh, Wi. Sheboygan, WI. 262 N. Seymour St. 2169 Verla Drive 2202 -A I ndiana Ave. 922 -0850 235 -3510 457 -2511 Sheboygan, Wis. November 21, 1977 Mr. Edward L. Reimer, Chief Building Inspector City of Oshkosh P.O. Box 1130 Oshkosh, Wis. 54901 New Service Building Jack Meyer, Owner 2200 Montana Str., Oshkosh, Wis. Plan File #77- 10 -2 -B Wm. J. Petri, Designer Dear Mr. Reimer: In reply to yours of November 17th, we have the following: Ind.64.05 We are submitting another copy of our thermal calcu- lations. Page 1 shows the Sales Office & Toilet Rooms with the exterior temperature at -15 and the interior at +67 Page 2 shows the Service Department with exterior at -15 and interior at +60 We trust this will answer this paragraph. Ind.51.16 We are assuming that this in reference to the two steps at the aligning pit. We did fail to show that a chain will extend from one side to the other when equipment is not in use. This is shown on the shop drawings by the manufacturer of the align- ing equipment. The Owner will provide this protection. Ind.52.28 Sheet #3 of our plans show the toilet room ceiling finish to be 5/8" sheet rock finished with three coat enamel system. A copy of this specification is attached. Butler Calculations of 4012 WBF -II building are herewith submitted. We felt that since DILHR at Madison had approved this building, further submittal of calculations was not required. We should like to have them returned after thay have served their purpose. We hope this will provide all that is required to receive the permit for complete construction. cc: Mr. Jack Meyer Yours very truly, 637 W. So. Park Ave., Oshkosh, Wis. 54901 -a 1 St ;� Building Co. BUILDINGS BY <BUTLE, J•etri, Designer :9. Roc,'/ 5 PE-c/F /CA 7"/ c>#45 L0002 si As. : TN! / TI "Loola .l, JO 4 /-/ / ON axis& To 61 ,l4 01 OP CILINAMIC 7JLI TailZALAzto. PAI#47-40 COA.ICAE4F MAJ2641 SLArf, , MolVOL/rHic As P A 1-r cost orri.r& A 0 '0•1 1 10V41 14: M A rilca I / L / MPS /2 V I o OS To 141A Tara. WALLS CIF/LIAIG ; MJ.L.s 7 - 0 eadr or ASLOCK Asoxiit y. Ca/CIA/G.3 To ASA 00' TH/G Paz /44 es .0.4 o 14//ALL JO/b47 7.4Per 0 Asia c.smakIrtrO. a yig•Sciow .80.400 re. 1 3 a S P o At 7aro SE L. c>1,41 woo o Jo/ars ,r9 /2 ALL km& L S Docqz S c 1)1./A/G5 / 70/L1 .eoc ro ro-4 "La& Co Ars E AiA Ai L4/4 r& CL0 Se rS t To 21.S o ,.j VITIMate, u s - IV IV ( IEL0/4/G A TS 0 owz_ A A./0 5/N.IT-imit0A17, Sat."- ,42 5 iA/C2 rH Ci T Co Vs12 0 /i./ W A 7F/Z i1 QS r /5 a PAZ co / 0 dc 0 S y 0A2/1.1K1 .JC 74 7 0" ! COOL S/2 012 //JO/ VI o U AL CCl/C A r .4 /%37 W.4 rffeSOLIFIGIr. 1 2/ 41,4 IAJG XAoi L /TVS'S SHALL .1/41 or Oa / S 7 LL I&J 7 LET ) 200 , 4S. 4 0 0 0 ■.9 PROJECT Sales & Service Building LOCATION Montana Str.@ N. 22nd Ave. OWNER Meyer ADDRESS Oshkosh, Wis. Searl Steel Building Co., 262 N. Seymour Str . , SHEET 1 _ Fond du Lac, Wis. OF 2 DRAWN BY Wm. J. Petri DATE_ Sept. 19, X977 51.02 (16 ) Thermal Calculations - Zone #3. Total Building Size: 40' x 50' x 12' at eaves (2,000 sq.ft.) Sales, Office & Toilet Rooms (12' at eaves) = 530 sq. ft. Service Department (12' at eaves) =1.470 sq. ft. Total Area 2.000 sq. ft. Sales, Office & Toilet Rooms: Temperature Design: Ext.(-15 °. Int. +67 Difference 82 o Wall Construction: Metal Wall panels with 3" thick fiberglass insulation having reinforced foil facing; density of .6#; flame spread of 25 or less; "UL" labeled non combustible. Inside of walls to be fur - red and lined with sheet rock, except in toilet rooms to be 6" block in addition to the exterior wall treatment. Total "U" factor .11. Roof Construction: Metal Roof panels with 4" thick fiberglass (same as above) plus suspended ceiling with insulated insert panels. Total "U" factor .10. Walls(net) 744 sq.ft. x 9.02 ( .11 x 82) 6711 BTU Windows (insulated glass) 85 sq.ft. x58.04 ( .62 x 82) 4 933 " Door (un- insulated) 23 sq.ft. x82.00 ( 1.00 x 82) 1886 " Roof (with suspended oeil)608 sq.ft. x 8.20 ( .10 x 82) 4956 " Total 18486 BTU Total BTU 18,486 = 12.66 Total Area 1,460 s PROJECT Sales & Se LOCATION Montana Str . ,® 22nd Str. OWNER Meyer ADDRESS Oshkosh, Wis. Searl Steel Building Co. 262 N. Seymour Str., SHEET Fond du Lac, Wis. OF ____Z_ oRA.b'N By Wm. J. Petri Dm Sept. 19, 1977 51.02 (15) ' Thermal Calculations - Zone #3. Total Building Size: 40' x 50' x 12' at eaves (2,000 sq. ft.) Sales, Office & Toilet Rooms (12' at eaves) = 530 sq. ft. Service Department (12' at eaves) = 1,470 sq. ft. Total Area 2,000 sq. ft. - Service Department: Temperature Design: Ext. -15 ° ; Int. + 60 Difference 75°. Wall Construction: Metal wall panels with 3" thick fiberglass insulation having reinforced foil facing; density .6 #; flame spread of 25 or less; "UL" labeled non combustible. "U" factor .14. Walls in aligning pit to be 10" thick concrete with "U" factor .61. Roof Construction: Metal roof panels with 4" thick fiberglass (same as above) "U" factor .11. Walls (net) Metal 1204 sq.ft. x 10.50 ( .14 x 75) 12,642 BTU Walls (net) Concrete 60 sq.ft. x 45.75 ( .61 x 75) 2,745 0/H doors(insulated) 81 sq.ft. x 46.50 ( .62 x 75) 3,767 " Walk Door(uninsulated) 23 sq.ft. x 75.00 ( 1.00 x 75) 1,725 Roof 1392 sq.ft. x 8.25 ( .11 x 75) 11,484 " Total 32,363 BTU Total BTU 32,363 Total Area 2,760 s 11.73 • g ' 40 I t } January 12, 1978 Wrn J. Petri 2202 -A Indiana Ave. Sheboygan, Wisconsin 53088 New Service Building Jack Meyer, Owner 2200 Montana St., Oshkosh Plan File: #?7- 10 -2 -B Wm. J. Petri, Designer Dear Sir: This letter is to acknowledge receipt of information requested in our letter dated November 17, 19 77. It is noted from the structural data that 7/16" brace rods are used in the end wall, And that the r arts used are 9.5" X 2.750" X .102 ". Our reference to Ind. 52.58 in our letter dated November 17, 1977 was to emphasize that the concrete block should be made smooth and washable. This office still has not received any heating and ventilating drawings for aproval. It is our understanding that Heating and Ventilating is the responsibility of :°r. Meyer. Sincerely, EDWAL1 L. REIMER Chief Building Inspector ELR:db cc: Mr. Jack TSeyer 637 W. South Park Ave. November 17, 1977 Wm. J. Petri 2202 -A Indiana Ave. Sheboygan, Wisconsin 53088 New Service Building Jack Meyer, Owner 2200 Montana St., Oshkosh Plan File: #77- 10 -2 -B Wm. J. Petri, Designer Dear Sir: Building plans have been reviewed by this office for compliance with important code requirements. The drawings are stamped "Construction may proceed ". All items that are required to be changed by this letter must be corrected before commencing that part of the work. This approval is not a Building Permit. Necessary city permits must be secured before commencing work. You are hereby advised that the owner, as defined in Charter 101.01 (1) of the Wisconsin State Statutes, is responsible for all code requirements not specifically cited herein. Code requirements are set forth in Chapters 50 thru 64 of the rules of the Department of Industry, Labor and Human Relations. The building will be inspected during construction and a final inspection will be made after completion to insure complete compliance with City and State codes. The architect, professional engineer, builder or owner shall keep at the building, as evidence of approval, one set of plans bearing the stamp of approval. Ind. 64.02 This approval does not include heating and ventilating. Such plans are required to be submitted and approved prior to installation of such equipment. Ind. 64.05 Inside design temperature for retail area must be at least 65 F. Resubmit calculations taking that temperature into consideration and show that the total building envelope shall not have a loss greater than 13 3TU per hour per square foot. Wm. J. Petri Page -2- November 17, 1977 Ind. 51.16 Stairs and platforms shall be provided with railings designed in accordance to Section Ind. 51.16. Ind. 52.58 Walls and ceilings in toilet room shall be made smooth, washable and nonabsorbent. This office does not have calculations to go with DILHR approval #760902. Please submit this data. This approval is conditioned upon receiving the above information on or before December 15, 1977. Sincerely, EDWARD L. REIMER Chief Building Inspector ELR : db cc: Mr. Jack Meyer 637 W. So. Park Ave. December 22, 1977 Wm. J. Petri 2202 -a Indiana Ave. Sheboygan, Wisconsin 53088 New Service Building Jack Meyer, Owner 2200 Montana St., Oshkosh Plan File: #?7- 10 -2 -r3 Dear Sir: On reviewing the data included with your letter of November 21, 1977, I had, a few questions. I have tried calling you at 457- 2511, but no one answered the phone at those times. My questions were on the following items: 1. It appears that two overhead doors have been left out of your calculations on heat loss. Since adding the two doors to the calculations would exceed the 13 btu per square foot limit, I would like you to recheck the figures once more. 2. The plans do not show any end wall braces. Are 7/16" brace rods required in the design manual= 3. I cannot find the size of girts on the plan. Is a 9.5 X 2.750 X .102 girt specified? Sincerely, EDWARD L. REIMER Chief Building Inspector ELR :db ss =� q� DEPARTMENT OF INDUSTRY, LABOR AND HUMAN RELATIONS INDUSTRIAL SAFETY & BUILDINGS DIVISION 4802 SHEBOYGAN AVENUE MADISON, WISCONSIN 53702 PERMIT TO START CONSTRUCTION Location of Project: Owner: Jack Meyer E Street: Montana Str . , @ N. 22nd Ave., Plan File Number 7 10- 7- F City: Oshkosh Date Plans Rec'd /0°. a/ -7 7 County: Winnebago Occupancy: Sales & Service Building We, the undersigned, request to begin footing and foundation work prior to approval of the plans. Complete plans have been submitted to the ! ' • - i• - • ° u • :Lt -- . - • - .. •, • • • e y an Buildiugg and all information requested by Code Ind 50.10 has been included with the submittal. We have reviewed the specific code requirements for the building or structure, including Ind 54.01 (construction, height, and allowable area), Ind 50.12, Ind 50.001, Ind 51.01, Ind 53, and Ind 57.50 when applicable and have shown compliance on the drawings. We agree to make any changes required after the plans have been reviewed and to remove or replace noncode complying parts of the foundation and /or footings. We agree to proceed with the footings and foundation only and will not continue with the remainder of the building or structure until approval has been received. 0, ? ) Signature / /0- z / - 7 7 Owne ' Si g Date Accepted B Date ai Name: Jack Meyer Drill of ftt . to is r & uman relations Address: 637 W. South Park Ave., Not Accepted Because Oshkosh, Wis. 54901 �./er►.J— /0//y7 Plans will be examined within the next '�1, Designer s Signature Name: Wm. J. Petri 2202 — Indiana Ave., NO1E: Footing and foundation plans submitted prior to Address: final building plans will not be accepted for this permit. Sheboygan, Wis. 53081 ,, S 4/ , FILE COPY