HomeMy WebLinkAboutHVAC #84-07-0269-B (09/25/1984) • eII ELLIS STONE CONSTRUCTION CO. P.O. Box 366 • Stevens Point, Wisconsin 54481 • (715) 344 -4552 September 25, 1984 Department of Industry, Labor & Human Relations Safety & Building Division 201 East Washington Avenue P. 0. Box 7969 Madison, Wisconsin 53707 Attention: Rick Olson Re: Grocery Store Copps Corporation, Owner 1801 West 9th Avenue Oshkosh, Winnebago County Plan No. 84 -07- 0269 -B File No. E -17581 Dear Mr. Olson: In your letter of September 19, 1984 for heating and ventilation plan approval you cite ILHR 63.22 requiring additional insulation at the return air tunnels. please b8 advised that the normal temperature of the return air will be 58 F to 62 F since this air is tempered by the "spill air" from the refrigerated cases located directly over the air inlets. This calculates out to a temperature differential with the surrounding medium (ground) of less than 25 F and, therefore, duct insulation is not required per ILHR 63.22(1)(b)1. The thermal resistance (R) of the insulation being provided at the tunnel walls adjacent to the exterior is R -10.8 which exceeds requirements of ILHR 63.22(1)(a) by 200 %. Yours very truly, OK-0" /0+/ ELLIS STONE CONSTRUCTION COMPANY fc,O, VAQ, f201kriAt: PB:bjb Pete Bentzen •'tit A cc: Walter J. Okray 6 IV C. Joseph S EP 2 Ed Pliska (The Copps Corporation) �--t Donald P . Cov i l l 3 �. T Y& 11; - D03 DIV. ✓ ..Oshkosh Building Inspector -1 AUTHORIZED DEALER ARM Tti Armco Building Systems W I , . _ 4