HomeMy WebLinkAboutBuilding & HVAC #84-07-0269-B r r;*/ ik J State of Wisconsin Department of Industry, Labor and Human Relations r • October 11, 1984 SAFETY & BUILDINGS DIVISION 201 E. Washington Avenue rue No. E -17581 P.O. Box 7969 Madison, Wisconsin 53707 Walter J. Okray Ellis Stone Construction Company P. O. Box 356 Stevens Point, WI 54481 Dear Mr. Okrays Grocery Store The Copps Corporation, Owner • 1801 West 4th Avenue Oshkosh, Winnebago County Plan Number 84 -07- 0269 -B Volutes 1,191,960 Cubic Peet Peter C. Joseph, Supervising Professional A.0 TUB 64.34 The duct construction requirements of this section apply to anything inside the duct es well as the outside, therefore if combustible materials are looated in the duet, they shall be isolated or Dowered with an approved noncombustible material. Tf the material within the duct tunnel does not comply with the oode, then the tunnel marmot be used as a ventilation air duct and an alternate return ',etas must be utilised. Note: this is not considered a plenum as cowered in TZAR 64.41. Sincerely, Rick Olson Staff Engineer (Tel. 608 -266 -9291) RO,T00307 cos R -3 Covi11, phone 715- 346 -3493, Friday Ashkaeh Building Inspector The Copps Corporation 2828 Wayne Street Stevens Point, WI 54481 DI LHR -SB D -5850