Building and illumination plans have been reviewed by the Department of
Industry, Labor and Human Relations for compliance with the important code
requirements. The plans are stamped *Conditionally Approved,* and construction
may proceed subject to local regulations, but all items that are required to be
Changed by this letter must be corrected before commencing that of the
work.
You are hereby advised that the owner as defined in Chapter 101.01 (2) (i)
of the Wisconsin State Statutes is responsible for all oode requirements not
specifically cited herein. Code requirements are set forth in Chapters 50
through 64 of the Rules of the Department.
The building will be inspected during and after construction by a deputy of
this depsrtnent to insure ocmplete compliance with Wisoonsin Codes. The owner
may notify the state building inspector listed below if a final inspection is
desired before taking possession of the building.
ILHR 50.15 Eridenoe of approval. The arohiteot, professional engineer,
designer, builder or owner shall keep at the building, one set of plans bearing
the stamp of approval.
O ILAR 50.12 Submit for approval joist girder plans, calculations, application l
(SB -118) and fees. /
MAR 50.12 Submit for approval HVAC plans, caloulations, applioation form 1
(SB -118) and fees. / a
SLUR 50.12 (4) Submit design onloulations for steel joist with top chord )
cantilever at one end.
DI LHR -SBD -5850
Ellis Stone Construction Company
August 2, 1984
Page 2
•
ILHR 51.047 (6) All fire doors shall be equipped with automatic or self-
closing devices.
ILRR 54.145 Portable fire extinguishers shall be provided, as specified in
ILHR 51.22.
ILIR 54.14 (1) The mechanical room ceiling shall be at least a 2 -42our fire -
resistive rated system, or the walls of the room extend to the ceiling. The
tire- division wall shall comply with ILHR 52.01 (13) (a) 1, 2 or 3.