HomeMy WebLinkAboutFax (violations) - 02/03/2009 02/03/2009 16:11 920 - 494 -4473 STIEGLER CO PAGE 01
sCAN/1 0
PIT) ti I ,
tie
+u
A
�/rELECTRICAL CONT
9
RACTORS AND COMMUNICATIONS SERVICES
FAX TRANSMITTAL
TO: 1 ` TELEFAX #:
_. . .:.. 4 d ,A . _grz. .
ATTN: . ^ ` -
DATE: 9, A TIME:
• ► AJ► _A�. __1
Iy
FROr( # OF PAGES: 4
SUBJECT: ) .9 J � 1 I
MESSAGE:
4
t i' l lwun,
c )x,_ ..-60 imv__ (-\-0, bc, t(--Ls,
r,;,,,L,e,,____ i,,,, ff ) k)._,
6 1,k,, e.d6L- , L ,44.,3„.-u,
� v rid2 Acs aza_z_ ccif)J
1 t
The Stlegler Company, Inc. • PC. Box 3644 • Green Bay, WI 54303 • 920/494 -0 • 9 2 0 � 0
0/4 447
02/03/2009 16:11 920 - 494 -4473 STIEGLER CO PAGE 02
e INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT SCA/ V/V c < 215 CHURCH
AVE
OSHKOSH CORRECTION NOTICE F4� , ,
ON THE WATER f • 0 � .ASHKOSH WI 54903 -1130
Issue Date 1/14/2009 _ Compliance Data 2/13/2009 99
Address 110 N SAWYER ST SA Compliance No
Name Address City State Zip Code
Sent to Q Owner I OSHKOSH CATHOLIC HIGH SCHOOL 110 N SAWYER ST
-'— •. _ OSHKOSH WI _
[�e WI 54902 -5696
Introduction quired for Occupancy 1 Occupancy -
While conducting a routine inspection for the Solar PV system the following violations were noted.
•
-
Iten1 # 1 Code NEC 408.35 Compliance No
Compliance Date 02/13/2009 IMMEDIATELY
Description of more than 42 overciirrent devices (other than those provided for In the mains) of a lighting and appliance branch - circuit panelboard shall
e Installed In eny one cabinet or cutout box. (Tandem Circuit Breaker)
01/14/2009
Last i);..15 AI 0 T' 5/19 fT — 0)-weie ,B/1e- +t
Updated
Item 2 Code NEC 408.36() Compliance F P No Compliance Date 02/13/2009 IMMEDIATELY
Description lug-in -type overcurrent protection devices that are backfed and used to terminate field - installed ungrounded supply conductors shall be
ecured in place by an additional fastener.
01/14/2009
Last
Updated
Item it 3 • Code NEC 690.17 _ Compliance No
Compliance Date 02/13/2009 IMMEDIATELY
Description ere all terminals of the disconnecting means may be energized in the open position, a warning sign shall be mounted on or adjacent to the
isoonnecting means.(see NEC for terminology)
01/14/2009
Last
Updated
Item* 4 Code NEC A 690.47
() Compliance No Compliance Date 02/13/2009 IMMEDIATELY
Description f installing an ac system, a groundsundl 9
nelectrode system shall be provided in accordance with 250.50 through 250.60. The grounding electrode
nductor shall be Installed In accordance with 250.64.
01/14/2009
Last
•
Updated
Item # 5 Code Comm 16.26(2) Compliance No
Compliance Date 02/13/2009 IMMEDIATELY
Description here the supplemental electrode required by NEC 250.53(D)(2) consists of made electr specified in 250.52(A)(5), not less than 2
01/14/2009 upplemental electrodes shall be installed.
Last
Updated
•
Item 6 Code NEC 690.54
Compliance No _ Compliance Date 02/13/2009 IMMEDIATELY
Description II interactive system(s) of interconnection with other sources llhasbe marked at an accessible location at the disconnecting means as
01/14/2009 Power source with the maximum ac output operating current and the operating ac voltage.
Last
Updated
14649 Page 1 of 3
02/03/2009 16:11 920 - 494 -4473 STIEGLER CO PAGE 03
C.) INSPECTION SERVICES DIVISION ROOM 205
CAN
C ITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 1,215 CHURCH AVE
OSHKOSH CORRECTION NOTICE FF a PO Box 1130
ON THE WATER C l' 4KOSH WI 54903 - 1130
Issue Date 1/14/2009 _ Compliance Date V13/2009 6 q TE
Address 110 N SAWYER ST Compliance No
_ Name Address
Sent to J J Owner OSHKOSH CATHOLIC HIGH SCHOOL 110 N SAW ST YER O S Zip Code
• • - --• - -•• • OSSHKOSH W Wl I 54902 -5696
Introduction LI Requited for Occupancy Occupancy _ —
While conducting a routine inspection for the Solar PV system the following violations were noted.
Item # 7 Code NEC 690.56 Com Banc¢ No ' - --• • - •_.. —_,
Description ulldings or Structures with both utility service and a photovoltaic pemla
ic sys em shall have a Compliance Date 02/13/2009 IMMEDIATELY
he service disconnecting means and the photovoltaic system disconnecting means, nent plaque or directory p�evlding the location of
01/14/2009
Last
Updated
14649 Page 2 of 3
02/03/2009 16:11 920- 494 -4473 STIEGL.ER OD PAGE 04
6 INSPECTION SERVICES DMSION'ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT SC4/1/
215 CHURCH AVE
OSHKOSH • CORRECTION NOTICE FAA a PO Box 1130
ON THE WATER I? 109 S
O HKOSH Wt 54903 -1130
Is9ue Date 1/14/2009 Compliance Date 2/13/2009
- . —_.. 04 T Compliance No
Address 110 N SAWYER ST -
_ Name Address City State Zip Code
Sent to Owner ; OSHKOSH CATHOLIC HIGH SCHOOL 110 N SAWYER ST
OSHKOSH WI _54902 - 5
Introduction 11 Required for Occupancy Occupancy
While conducting a routine inspection for the Solar PV system the following violations were noted.
•
Items $ Code NEC 690.61 - • - "— -
Compliance NO Compliance Date 02/13/2009 IMMEDIATELY
Description n inverter or an ac module In an interactive solar photovoltaic system shall automatically de- energize its output to the connected electrical
roduction and distribution network upon loss of voltage In that system.
01/14/2009
Last
Updated
Summary To avoid any further inconvenience, please correct the above noted violations Any questions or concerns please
feel free to contact me @ 920 - 236 -5046.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspectio p or to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 2/13/2009
Office hours for obtaining permits are Monday through Friday 7:30 -6:30 a.m. and 12:30 -1:30 p.m. or by appointment To schedule
inspections please call the Inspection Request line at 236.5128 noting the address, permit number (when applicable), and the
nature of what needs to be Inspected.
Signature _,... iii a .14
Date .
I ns: Kevin Benner 236 -5046 kbenner@cl.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name �),��' � '
Company
S! atu ro 0 3—
Data
Also Sent tot 121 Bldg _J GANTHER CONSTRUCTION
U Elec J __ 4625 COUNTY ROAD A OSHKOSH WI 54901 -9616
STIEGLER COMPANY INC PO BOX 3644
HVAC -- GREEN BAY WI 54303 -3644
— -
Li Designer 1 _ -~
• —
P
Other - '— _
Inspector 1 Allyn Dannhoff _ __'
14648 Page 3 of 3