HomeMy WebLinkAbout1997-Building #E6-71-697 CITY HALL
215 Church Avenue
P. O. Box 1130
Oshkosh, 9 0 2 -1130 0 City o f O
54902-1130
W E H
June 10, 1997
Lourdes Academy Richard Kempinger .
110 N. Sawyer St. Box 2903
Oshkosh, WI 54901 Oshkosh, WI 54903
RE: Interior Alterations
110 N. Sawyer St.
File # E6 -71 -697
Dear Sir:
Building plans have been reviewed by this office for compliance with
important code requirements. The drawings are stamped "Construction may
proceed." All items that are required to be changed by this letter must
be corrected before commencing that part of the work. This approval is
not a Building Permit. Necessary city permits must be secured before
commencing work.
You are hereby advised that the owner, as defined in Chapter. 101.01(i)
of the Wisconsin State Statutes, is responsible for all code requirements
not specifically cited herein. Code requirements are set forth in
Chapters 50 through 64 of the rules of the Department of Industry, Labor
and Human Relations.
The building will be inspected during construction and a final inspection
will be made after completion to insure complete compliance with city and
state codes.
The architect, professional engineer, builder or owner shall keep at the
building, as evidence of approval, one set of plans bearing the stamp of
approval.
Heating and ventilating plans have been reviewed by this office for
compliance with important code requirements. All items that are required
to be changed by this letter, must be corrected before commencing that
part of the work. This approval is not a Heating Permit. Necessary city
permits must be secured before commencing work.
Note: Initial plans received in March, 1997. This review was
conducted using the pre 4 -1 -97 Building Code.
ILHR 51.15 Add exit lights in room 25, existing Locker Room to direct
occupants to the exits.
ILHR 56.03 Smoke Detection shall be provided in the basement corridors,
if not already present. If this must be added, then it must
be interconnected with the fire alarm pull system and visual
strobes must be added per ILHR 69, ADAAG 4.1.6 (1) (b).
ILHR 56.19 Fire alarm pull stations shall be provided at the exits from
the basement level, if not already provided.
Si erel,
A lyn - f
Direc • of Inspect •n Services
cc:LE /HZ