Loading...
HomeMy WebLinkAbout2011-Electric Electric Permit Work Card Job Address 3001 S WASHBURN ST Permit Number 144710 Create Date 1/20/2011 Owner BFO FACTORY SHOPPES LLC Contractor SUBURBAN ELECTRICAL ENGINEERING Service New Change 0 Temp • N/A Type Overhead O Underground • N/A Volts 120/208 Circuits 45 Luminaires 47 Amps 400 Switches 10 Receptacles 30 Value $25;490.00 Use /Nature Maurices (C -50) / Alterations for new tenant. - of Work Inspections: Date/Time Inspected 02/11/2011 09.15AM Type Abv Ceiling Inspector Kevin Benner approved w /cond. Re- Inspect A few box covers, LV wiring on grid (T- Stat), Speaker wiring was not installed, a couple spots where the the added ceiling ty -wires are to extended to the grid, a few troffers by the dressing rooms were not installed because the grid was not complete. Reviewed with Josh while on site. *FCN was Faxed & Emailed to John Gonnering, PM for the EC, for sign transformer access & show window receptacles. Date/Time requested: 02/09/2011 03:30 PM Notice Type: FC. - Ready Date/Time: 02/10/2011 08:30AM Access: Requested by: SUBURBAN ELECTRICAL ENGINEERING INC Phone Number: Jeremy 920- 841 -7024 O Reinspect Fee O Fee Wavied Reinspect Fee Paid Date/Time Inspected 02/16/2011 10 :45AM Type Service Inspector Kevin Benner approved 300A 42KAIC CB's / Tap box was energized at the time of inspection so I did not open the cover to inspe Faxed to WPS 2/16/2011 Date/Time requested: 02/15/2011 01:28 PM Notice Type: Ready Date/Time: 02/16/2011 10:OOAM Access: Requested by: SUBURBAN ELECTRICAL ENGINEERING INC Phone Number: Jeremy 920 - 841 -7024 0 Reinspect Fee 0 Fee Wavied Reinspect Fee Paid