Building plans have been reviewed by this office for compliance
with important code requirements. The drawings are stamped
"Construction may proceed." All items that are required to be
changed by this letter must be corrected before commencing that
part of the work. This approval is not a Building Permit,
Necessary city permit must be secured before commencing work,
You are hereby advised that the owner, as defined in Chapter
101.01(i) of the Wisconsin State Statutes, is responsible for all
code requirements not specifically cited herein. Code require-
ments are set forth in Chapters 50 through 64 of the rules of the
Department of Industry. Labor and Human Relations.
The building will be inspected during construction and a final
inspection will be made after completion to insure complete
compliance with city and state codes.
The architect, professional engineer, builder or owner shall keep
at the building, as evidence of approval, one set of plans bear-
ing the stamp of approval.
Heating and ventilating plans have been reviewed by this office
for compliance with important code requirements. All items that
are required to be changed by this letter must be corrected
before commencing that part of the work. This approval is not a
Heating Permit. Necessary city permits must be secured before
commencing work,
ILHR 51.03, Table 51.03-A All exterior walls must be at least 6
inch masonry and must also be 1 hour rated.
. _
| |
Page Two
( /
Jul, 17, 1991
AGM Architecture
lLHK 5l.02i15} Decorative combustible trim shall be limited to 10
percent of the wall surface within any 100 lineal feet. it would
not appear that the combustible siding is backed bo masnnro also.
Due to the two aforementioned items this building cannot he
classified as type 58, but mao be reclassified as twpe 8
ILHR 54.14 The HVAC contractor shall state in a letter the name
and mode/ number of the equipment to be installed. This is to
verify that the furnace is direct oent/sealed combustion.
1LHR 51.16 If this building is subject to the presence of oh\l-
d the
,c" c np�n shall be provided with intermediate
rails to prevent passage of a 6 inch diameter sphere.
Sincerely,
ALLYN DANNHOFF
(
Chief Building Inspector
AD:mr