Building plans and heating and ventilation plans for the above project have
been stamped, "Couditionally Approved--See Correspondence," and two or more
copies are being returned under separate cover. You are hereby advised that
the designer is responsible for all code requirements not specifically brought
to your attention. The code requirements are set forth in Chapters 50 to 59
of the ,:wles of the Department.
Ind 50.11 une set of plans bearing the stamp of approval shall be kept at the
building site.
Ind 51.15 (b) Protect west wall of vestibule 101 if sill is less than 24 inches
high. Provide glaas doors with a push bar or plate inside and outside.
Ind 50.10 Please submit typical footing and foundation wall calculations. It
is noted that the specifications rqquire the fabricator of the wood trusses to
submit calculations and obtain approval of this department. The situation also
applies to precast concrete floor systems. Calculations and/or Wisconsin state
approval number for the trusses and the precast concrete shall be submitted and
approval obtained prior to their installation in the building.
Ind 53.09 (8) The maximum allowable span for an 8 inch concrete block wall is
25 feet. The designer shall submit calculations showing that the load beariu„
8 inch concrete block wall in the basement will not be overstressed.
Irion, Reinke & Associates, Inc. -2- July 16, 1970
Ind 53.20 (3) Frame superstructure of this building shall be securely anchored
to the foundation.
Ind 52.58 Dry wall in rooms 108 and 109 shall be 5/8 inch thick.
Ind 52.59 (4) Doors 6, 7 and 12 shall be 32 inches wide. Grab bars shall be
provided in each toilet room.
Ind 54.12 (6) The watercloset in the mans toilet room shall have a self- rising
seat.
Ind 22.18 Provide a restroom with a cot or couch. The womens lounge is not
acceptable for this purpose.
Ind 59.41 (7) Outside air and recirculated air shall be filtered.
Ind 59.60 (6) The minimum size of the combustion air intake shall be 100 square
inches.
Sincerely yours,
Clyde Bryant
Plan Examiner
CB : cv