January 10, 2011
Norman Herman Lorri Schumann
2100 W Littleton, Blvd. Suite 200 Maurices, Inc.
Littleton, CO 80120 105 W Superior St.
Duluth, MN 55802
Dave Spring
Horizon Group Properties, Inc
5000 Hakes Drive
Muskegon, Michigan, 46441
Site: Plan Number: Q2- 3208 -0111
Maurices
3001 S Washburn St. Space C -50
Oshkosh WI 54904
For:
Description: Tenant space alterations
Object Type: Building and HVAC
Class of Construction: IIB - 6213 Sq Ft.; sprinklered
Occupancy: M: Mercantile / Retail
Maximum No of Occupants: 180
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
• IBC 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
• IBC 1011 Exit signs are required to be installed per this section
• IBC 1006.1 Means of egress illumination is required to be installed per this section
• IBC 1006.3 Means of egress emergency illumination is required to be installed per this section. All paths of egress
through The Retail Display area are required to have adequate emergency lighting to meet the performance
requirements of IBC 1006.4.
• ANSI A117.1 Fixed Side Wall Grab Bars. A vertical grab bar 18 inches minimum length shall be mounted
with the bottom of the bar located between 39 inches and 41 inches above the floor and with the center line of
the bar located between 39 inches and 41 inches from the rear wall.
• Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules under
this code and which are made to construction documents that have previously been granted approval by the
department or its authorized representative, shall be submitted to the office that granted the approval. All revisions
and modifications to plans shall be approved in writing by the department or its authorized representative prior to the
work involved in the revision or modification being carried out. A revision or modification to a plan, drawing or
specification shall be signed and sealed in accordance with Comm 61.31(1).
IT ,cia 12011 f ornr:i !Min an 'I °;4 .11 301 1 Washburn .. fi C _ r
- - 14., _ _.� LIj u:),11 I� ^ `` 11;11y d
page 1 of 2
• Comm 82.20 This plan review does not include plumbing. Prior to installation of plumbing, plans and
calculations are required to be submitted and approved if greater than 16 fixture units are being installed within a
building. This includes other tenant spaces within the same building with work occurring at the same time.
While a plumbing plan review has not been done as part of this review, the following issues were identified:
1.) Sheet M -2 detail 4 indicates that condensate drains from RTU are to be piped to floor drains.
Comm 82.38 prohibits discharge of clear water into sanitary sewer.
For any questions on these issues please contact plumbing inspector Paul Wolf (920) 236 -5052.
• MUN 30 This review does not include review for signage. Applications for and questions regarding signage
permits should be directed to Todd Muehrer — Zoning Administrator (920) 236 -5053.
SUBMIT:
• Comm 61.40 (4) Supervision. Prior to the initial occupancy of a new building or addition and prior to the final
occupancy of an alteration of an existing building the supervising professional shall file a compliance statement
form SBD -9720 with this office. Note: Submittal of a compliance statement will be considered as evidence that
the supervising professional has properly addressed all items identified in this plan review letter.
A copy of the approved plans, specifications, and this letter shall be on -site during construction. If plan index sheets were
submitted in lieu of additional full plan sets, a copy of this approval letter and index sheet shall be attached to plans that
correspond with the copy on file with the copy on file in this office.
All permits are required to be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component. The City of
Oshkosh does not take responsibility for the design or construction of the reviewed items.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Res ec ,
Brian Noe
Building Systems Consultant
(920) 236 -5051
bnoe@ci.oshkosh.wi.us
cc: Property file Fee Required $ 900.00
Fee Received $ 900.00
Balance Due $ 0.00