HomeMy WebLinkAboutFinal (electric) - 03/19/2001 INSPECTION SERVICES DIVISION
0 DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 03/19/2001 Compliance Date 04/18/2001 Compliance No
Address 2480 MINERVA ST Inspected By Brian Noe
Name Address City State Zip Code
Sent to IJ Owner I RONALD W RONSON 2480 MINERVA ST OSHKOSH WI 54901 -1546
U Contractor HOEHNE ELECTRIC 621 E ONTARIO ST OMRO WI 54963 -
U Other MARC'S REMODELING OSHKOSH WI -
IJ Inspector
u Required for Occupancy Occupancy SFR Notice • First 0 Final 0 Other
Introduction At the time a final inspection was made on 2/15/01 it was agreed that the numerous electrical violations would be
addressed by the electrical contractor who had a permit for the remodeling that was done.As of this date the
following violations have not been corrected to our knowledge
Item # 1 Code NEC 410 Compliance No Compliance Date 04/18/2001 IMMEDIATELY
Description The lights located under the bar do not meet clearance requirements and are not installed per there listing
requirements.
Item # 2 Code Comm 16 Compliance No Compliance Date 04/18/2001 IMMEDIATELY
Description The GFCI adjacent to the bar is not properly functional @@
Item # 3 Code NEC 240 -83 Compliance No Compliance Date 04/18/2001 IMMEDIATELY
Description All cirrcuit breakers in the new sub panel are required to be properly tabled. @@
Item # 4 Code NEC 300 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The floating rec box for the wash machine is requird to be properly installed. All electrical equiptment is required to
be properly suported, and secured. @@
Item # 5 Code NEC Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The feeder cable for the sub panel is required to be properly secured
Page 1 of 4
�1 INSPECTION SERVICES DIVISION
( /�. DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 03/19/2001 Compliance Date 04/18/2001 Compliance No
Address 2480 MINERVA ST Inspected By Brian Noe
Name Address City State Zip Code
Sent to 12.1 Owner RONALD W RONSON 2480 MINERVA ST OSHKOSH WI 54901 -1546
u Contractor I HOEHNE ELECTRIC 621 E ONTARIO ST OMRO WI 54963 -
2J Other MARC'S REMODELING OSHKOSH WI -
L J Inspector
HI Required for Occupancy Occupancy SFR Notice 0 First 0 Final 0 Other I
Introduction At the time a final inspection was made on 2/15/01 it was agreed that the numerous electrical violations would be
addressed by the electrical contractor who had a permit for the remodeling that was done.As of this date the
following violations have not been corrected to our knowledge
Item # 6 Code NEC Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The cable feeding the dryer receptacle is not properly installed
Item # 7 Code NEC 300 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The flouresent light is not properly wired - no connector installed on fixture where cable enters.
Item # 8 Code NEC 300 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description All cable are required to be secured within 12 inches of entering the main service panel @@
Item # 9 Code NEC 110-16 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description Code required working clearance is required to be provided in front of service and sub panel. Min 3 feet in
front. @@
Item # 10 Code NEC 300-4 Compliance No Compliance Date 04/20 /2001 IMMEDIATELY
Description NM cable is not permitted to be stappled to the bottom of floor joists unless provided with physical protection.
Page 2 of 4
INSPECTION SERVICES DIVISION
10 DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 03/19/2001 Compliance Date 04/18/2001 Compliance No
Address 2480 MINERVA ST Inspected By Brian Noe
Name Address City State Zip Code
Sent to H Owner RONALD W RONSON 2480 MINERVA ST OSHKOSH WI 54901 -1546
U Contractor HOEHNE ELECTRIC 621 E ONTARIO ST OMRO WI 54963 -
U Other MARC'S REMODELING OSHKOSH WI -
u Inspector
Li Required for Occupancy Occupancy SFR Notice • First O Final O Other
Introduction At the time a final inspection was made on 2/15/01 it was agreed that the numerous electrical violations would be
addressed by the electrical contractor who had a permit for the remodeling that was done.As of this date the
following violations have not been corrected to our knowledge
Item # 11 Code NEC Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The receptacle to for the water softner is not properly wired and has damage to the UFcable supplying it, and no
cover plate. @@
Item # 12 Code NEC 220 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description Service Toad calc is required to show the addition of the sub panel has not increased the load beyond code
allowable load for the exisiting service. @@
Item # 13 Code NEC 110-26 Compliance No Compliance Date 04 /20/2001 IMMEDIATELY
Description The dryer vent is not permitted within the dedicated space for the service and sub panel.
Item # 14 Code Comm 21.08 Compliance No Compliance Date 04/20 /2001 IMMEDIATELY
Description All penetrations in floor are required to be firestopped. @@
Page 3 of 4
el) INSPECTION SERVICES DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 03/19/2001 Compliance Date 04/18/2001 Compliance No
Address 2480 MINERVA ST Inspected By Brian Noe
Name Address City State Zip Code
Sent to Owner RONALD W RONSON 2480 MINERVA ST OSHKOSH WI 54901 -1546
U Contractor HOEHNE ELECTRIC 621 E ONTARIO ST OMRO WI 54963 -
u Other I MARC'S REMODELING OSHKOSH WI -
u Inspector
U Required for Occupancy Occupancy SFR Notice • First 0 Final 0 Other
Introduction At the time a final inspection was made on 2/15/01 it was agreed that the numerous electrical violations would be
addressed by the electrical contractor who had a permit for the remodeling that was done.As of this date the
following violations have not been corrected to our knowledge
Item # 15 Code NFPA 54 Compliance No Compliance Date 04/20/2001 IMMEDIATELY
Description The unused gas line is required to be capped. @@
Summary
Please make corrections and call for a reinspection prior to compliance dates. If you have any questions I can be
reached at (920) 236 -5051.
DEFICIENCIES MUST BE CO; • - CT AND APPROVED BEFORE CONCEALMENT. CALL (920) 236 -5050 FOR INSPECTION.
Signature • _ Date (._34I /)
•