HomeMy WebLinkAboutElectric - 12/11/1995 CODE ENFORCEMENT DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 12/11/95 Compliance Date 1/10/96 Compliance No
Address 1105 LAAGER LN Inspected By John Sullivan
Name Address City State Zip Code
Sent X Owner CLASSIC HOMES Oshkosh WI 54901 -0000
to
X Contractor SCHOMMER ELECTRIC N 164 Two Mile Rd. Appleton WI 54915 -
u Other
u Inspector
X Required for Occupancy Occupancy Notice 0 First 0 Second O Final 0 Other
Introduction Nec 110 - 16(a) Working clearances.
Item # 0 Code Compliance Compliance Date
Description
Summary Provide the proper working clearance at the electrical service ,and call for a re inspection.
DEFICIENCIES MUST BE CORRECTED AND APPROVED BEFORE CONCEALMENT. CALL (414) 236 -5050 FOR INSPECTION.
Signature T �� ✓ /' /44 #--- Date / 2- /i I /j
Page 1 of 1
Iv
IAEI Analysis of 1993 National Electrical Code
F
Section 110 -16(a) F
Structural ceiling or 25 ft. (384 -4) C
Exclusively
<- dedicated space
Front 384 -4 Side e
1 1 F Width of e
equipment Working Space C
but not less minimum 6 ft. 6 in.
than 30 in. Except existing
F� Electrical dwelling units
s 200A or less. e
Equipment
Working Space
clear and Depth of C
extends from working space
floor or platforms , not less than
to 6 ft. 6 in. Wall Table 110- 16(a).
lit C
Floor or working platform
e.
e
,
Section 110- 16(a), Working Clearances. F ,,
This section has been revised to add The work space shall be clear and c %
extend from the floor or platform to the height required by this section."
This change will require that the work space be clear for a width C
of not less than 30 inches or the width of the equipment, whichever is C
greater, and extend from the floor to a height not Less than 6 -1/2 feet. See
€ p.,
Section 110- 16(f).
C
•.k t