Per your request a final building inspection was made at 1085
Laager Lane on February 1, 1994. The following items were found to
be in noncompliance:
ter ILHR 22.07, caulk around the natural gas entrance pipe
into the dwelling.
(/Per ILHR 21.04, maximum step to grade at all exterior doors
shall not exceed 8 inches. Rear patio door can be pinned, or a
temporary step installed.
a r ILHR 21.25(2), install a wall stud directly under the break
in.the top plate on the garage west wall. V e r ILHR 21.32, the fireplace hearth extension must comply with
the manufacturers listing. (16 inches out in front, and at least
8 'riches extended to the sides)
Per ILHR 21.22, secure the posts to the I- beams.
All above items must be corrected, and final inspection called for
within 30 days of this notice in order to secure the certificate of
occupancy. Please call 236 -5051 if you have any further questions
in this matter.