HomeMy WebLinkAbout0143643-Electric Electric Permit Work Card
Job Address 1020 -1142 S KOELLER ST Permit Number 143643 Create Date 10/13/2010
Owner KOELLER ONE LLC Contractor STIEGLER COMPANY INC
Service ( ) New Change 0 Temp • N/A Type -) Overhead 0 Underground • N/A
Volts 480 / 277 Circuits 30 Luminaires 175
Amps 1000 Switches 12 Receptacles 100 Value $47,000.00
Use /Nature COMM/ 1118 S Koeller St/ Hobby Lobby/ Interior Remodel to include moving the existing wall between the sales area and
of Work back rooms, new lounge, restrooms, classroom and frameroom. * *check #48351
Inspections:
Date/Time Inspected 11/02/2010 12:OOAM Type Reinspect Inspector Kevin Benner
Fax request /Reinspect above ceiling.
LV wiring to be completed. Existing wiring to the frame shop will be removed when the new frame shop is availabe, speaker to be lowered to
the new ceiling, FA wiring to be completed.
Date/Time requested: 11/01/2010 11:07 AM Notice Type: Ready Date/Time: 11/02/2010 12:OOAM
Access:
Requested by: STIEGLER COMPANY INC - Ron Klossner Phone Number: 920 - 494 - 0224
' ` Reinspect Fee 0 Fee Wavied 0 Reinspect Fee Paid
Date/Time Inspected 11/03/2010 12:OOAM Type Final Inspector Kevin Benner approved w /cond.
Fax request/ Electrical requirements are correct
Emergency Illumination to be added. (less that .10fc at the floor in the hot spot)
Date/Time requested: 11/01/2010 11:07 AM Notice Type: Ready Date/Time: 11/03/2010 08:OOAM
Access:
Requested by: STIEGLER COMPANY INC - Ron Klossner Phone Number: 920 -494 -0224
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Electric Permit Work Card
Job Address 1020 -1142 S KOELLER ST Permit Number 143643 Create Date 10/13/2010
Owner KOELLER ONE LLC Contractor STIEGLER COMPANY INC
Service 0 New ) Change 0 Temp • N/A Type ` ; Overhead u Underground • N/A
Volts 480 / 277 Circuits 30 Luminaires 175
Amps 1000 Switches 12 Receptacles 100 Value $47,000.00
Use /Nature COMM/ 1118 S Koeller St/ Hobby Lobby/ Interior Remodel to include moving the existing wall between the sales area and
of Work back rooms, new lounge, restrooms, classroom and frameroom. * *check #48351
Inspections:
Date/Time Inspected 10/20/2010 12:OOAM Type Consultation Inspector Kevin Benner
Discussed the emergency illumination with the Building Inspector, G.0 & Kyle from the E.C.
Date/Time requested: 10/20/2010 00:00 AM Notice Type: Ready Date/Time: 10 /20/2010 12:OOAM
Access:
Requested by STIEGLER COMPANY INC Phone Number
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 10/28/2010 12:OOPM Type Abv Ceiling Inspector Kevin Benner not approved
Fax request
Date/Time requested: 10/27/2010 01:33 PM Notice Type: FC Ready Date/Time: 10/28/2010 12:00PM
Access: Enter thru back of building
•
Requested by: STIEGLER COMPANY INC - Ron Phone Number: 920- 494 -0224
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 11/01/2010 12:OOPM Type Consultation Inspector Kevin Benner not approved
IFieid Request from Kyle / Emergency Illumination test
Not ready
Date/Time requested: 10/28/2010 00:00 PM Notice Type: Ready Date/Time: 11/01/2010 07:28AM
Access:
Requested by: STIEGLER COMPANY INC Phone Number:
O Reinspect Fee ` Fee Wavied ❑ Reinspect Fee Paid
Electric Permit Work Card
Job Address 1020 -1142 S KOELLER ST Permit Number 143643 Create Date 10/13/2010
Owner KOELLER ONE LLC Contractor STIEGLER COMPANY INC
Service 0 New 0 Change Temp • N/A Type 00 Overhead 0 Underground • N/A
Volts 480 / 277 Circuits 30 Luminaires 175
Value $47,000.00
Amps 1000 Switches 12 Receptacles 100
Use /Nature COMM/ 1118 S Koeller St/ Hobby Lobby/ Interior Remodel to include moving the existing wall between the sales area and
of Work back rooms, new lounge, restrooms, classroom and frameroom. * *check #48351 approved w /cond.
Inspections:
Date/Time Inspected 10/15/2010 12:OOAM Type Rough In Inspector Kevin Benner approved
Fax request
South three offices only on the east side of the building
Date/Time requested: 10/13/2010 11:53 AM Notice Type: Ready Date/Time: 10/15/2010 08:OOAM
Access: '.Enter thru back of building
Requested by: The Stiegier Co - Ron Klossner Phone Number: 920 - 494 -0224 •
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 10/19/2010 02:30PM Type Rough In Inspector Kevin Benner approved
Fax request / Rough for rest of remodel minus the janitor closet area
Reviewed with Kyle from the E.C. while on site
Date/Time requested: 10/18/2010 09:12 AM Notice Type: Ready Date/Time: 10/18/2010 09 :36AM
Access: iBack of building
Requested by: STIEGLER COMPANY INC - Ron Klossner Phone Number: 920 - 494 -0224
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected Type Rough In Inspector Kevin Benner approved
Field Request from Kyle
Janitor closet area
Date/Time requested: 10/19/2010 08:22 AM Notice Type: Ready Date/Time: 10/20/2010 08:22AM
Access:
Requested by: STIEGLER COMPANY INC Phone Number: 920 -494 -0224 Ron Klossner
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid •
•
�e erELECTRICAL CONTRACTORS AND COMMUNICATIONS SERVICES
February 15, 2011 RECEI
D
FEB 1 8 2011
DEPARTMENT OF
City of Oshkosh COMMUNITY DEVELOPMENT
INSPECTION SERVICES DIVISION
Inspection Services Division
PO Box 1130
Oshkosh, WI 54903
Attn: Kevin Brenner / Electrical Inspector
RE: Hobby Lobby / Koeller One LLC
1118 S. Koeller St.
Building Permit #143152
Electrical Permit #143643
Dear Kevin,
Stiegler Electric has inspected the installation of emergency ballasts in existing
fluorescent fixtures, providing an illuminated path of egress, and found the installation
completed by others acceptable.
The wire methods, grounding, fixture disconnects, ballast installation, and extension of
the night light circuit were examined and found NEC compliant.
Stiegler Electric considers this project completed and the electrical permit closed out.
i (4._(.4...„,,
Sincer- ,
Mr. Ron Klossner, President
pjj
The Stiegler Company, Inc. • PO. Box 3644 • Green Bay, WI 54303 • 920/494 -0224 • Fax: 920/494 -4473