October 21, 2010
Mr. Mike Kortz
Progressive Electrical Services
571 Marcella Street
Kimberly, WI 54136 -1760
Re: FVTC Oshkosh
Dear Mike,
Enclosed is the report for the Square D low voltage circuit breaker that was tested at the new Fox Valley Technical
College building located in Oshkosh, WI. The following is a summary of the field tests performed and findings.
Low Voltage Circuit Breaker:
Secondary Injection Test: This test ensures proper calibration of all functions of the solid statetrip
unit. All results were acceptable.
Ground Fault System Test: This test is used to verify the proper operation of the ground fault system.
It was performed using the primary current injection method on the service disconnect circuit breaker.
All results were acceptable.
All of the equipment tested passed both the visual/mechanical inspections and the electrical tests performed. The
equipment was found to be operational and within applicable standards and manufacturer's tolerances.
Thank you for allowing Square D Services to meet the electrical needs of the Fox Valley Technical College and
Progressive Electrical Services. If you have any questions or concerns regarding the enclosed test reports or work
performed please feel free to contact me anytime at 920 -585 -0362.
Regards,
f .
r
Terry Michels
Square D Sr. Field Service Representative
Email: Terry. Michels @US.Schneider - Electric.com
Fill SQUARE I:3 Services Division
=-i Schgeider Eiecc.-c_ LV Circuit Breaker
1-888-778-2733
(Manually Operated)
REFERENCE INFORMATION
Contact Name: TOM OLSON 920-540- FSR: Terry Michels Job No: 29174940-001
4055
Customer Site: FOX VALLEY TECH Customer Ref No: DBID: 21-270420
FOR PROGRESSIVE
Date: October 21, 2010
4200 POBEREZNY
ROAD
OSHKOSH, WI 54902
IDENTIFICATION
- ,
Sub Station Location: Main Customer Asset ID: Service Disconnect
Sub ID: Main Circuit ID: Main
NAMEPLATE DATA
Manufacture: Manufacture Date: Serial No: Type: ' , Z
Square D 2010 N/A RKF3620044A
Frame Size: Rated Amps: Sensor Rating: Rating Plug 2000 Amps 2000 Amps 2000 Amps 2000 Amps' i -
Fuse Type: Fuse Manufacture: Fuse Model/Catalog No: Fuse Rating;'
Unfused N/A
Trip Unit Type: Trip Curve No: Interrupt Rating: MountinU:
Micrologic 6.0A 613-5 65 KA Fixed
Number of Operations: Number of Operations:
INSPECTION CHECKLIST
ITEM AS LEFT ITEM AS LEFT
Blown Fuse Indicator (BFI): Not Applicable Switch Condition: Acceptable -'
Interlocks: Acceptable Primary Disconnects: Acceptable
Over-Travel Stops: Not Applicable Secondary Disconnects: Acceptable
Mechanical Wear: Acceptable Ground Contacts: Acceptable
Mechanical Lubrication: Acceptable Main Contacts: Acceptable
Intermediate Contacts: Not Applicable Arcing Contacts: Acceptable
Trip Free Test: Acceptable Pri.Current Path Lubrication: Acceptable
Manual Close Test: Acceptable Arc Chutes: Acceptable
Spring Discharge: Not Applicable Interphase Barriers: Acceptable
Insulated Linkages/Bracing: Acceptable Gap / Wipe Settings: Not Applicable
Contact Alignment / Not Applicable
Sequence:
Test Report, 29174940 - 001 3.
OVER CURRENT PROTECTION - TRIP UNIT DATA
Test Equipment ID: FFTS -803 Calibration Date: 1/19/10 FSR: 803
Manufacture: Square D Trip Device Serial #: N/A Style: Micrologic 6.0A
Battery Status As Found: Pass As Left: Pass
Settings
CT Coil Ratings: 2,000 CT Tap Ratings: 2,000 Rating Plug: 2,000
As As As Left I *2T As As As Left I *2T
Found Tested Setting ON Found Tested Setting ON
Setting Setting Setting Setting
Long Time Pickup 1 1 1 Instantaneous Pickup 2 2 2
Long Time Delay .5 .5 .5 Ground Fault Pickup 500 500 500
Short Time Pickup 1.5 1.5 1.5 Ground Fault Delay .1 .1 .1 Yes
Short Time Delay .1 .1 .1 Yes
TRIP UNIT TIMING TEST (measured Ian Secor.>,ds)
Trip Device Test Current Specified Range Phase A Phase B Phase C
Function Amps
Amp Range Minimum Maximum As Found As Left As Found As Left As Found As Left
Long Time 2,667 12 20 14.38 14.38 r 14.38
Short Time 3,500 4 6 5.201 5.201 5.201
Instantaneous 5,000 0.01 0.065. 0:037 0.037 ' ..: 0.037
Ground Fault 1,000 0.1 .., 0.2 04137 0.137 0.137
. . .- NOTES .
GF system tested utilizing primary injection method. Test results are as follows:
No Trip Test: Passed
Trip Test: Tripped at 503 amps , „ .
Test Report, 29174940 - 001 4.