HomeMy WebLinkAboutFinal (electric) - 10/23/1997 CODE ENFORCEMENT DIVISION
�. DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 10/23/97 Compliance Date 11/22/97 IMMEDIATELY Compliance No
Address 105 ROLLING GREEN CIR Inspected By John Sullivan
Name Address City State Zip Code
Sent to Q9 Owner CONTEMPORARY HOMES INC 2755 ALGOMA BLVD Oshkosh WI 54901 -0000
Q9 Contractor SCHOMMER ELECTRICAL CON N 164 TWO MILE ROAD APPLETON WI 54915 -
X Other P & S Plumbing P O Box 2153 Appleton Wi 54913 -2153
H Inspector
N Required for Occupancy Occupancy Single Family Notice .-) First O Second 0 Final 0 Other
Introduction At a final inspection the following corrections have been noted:
Item # 1 Code NEC 384-4 Compliance No Compliance Date 11/22/97 IMMEDIATELY
Description 1 he plumbing pipes above & below the electnal service shall be removed.See the enclosed drawings and please
call 236 -5046 for a re- inspection.
Summary See the enclosed code requirements.
DEFICIENCIES MUST BE CORRECTED AND APPROVED BEFORE CONCEALMENT. CALL (414) 236 -5050 FOR INSPECTION.
Signature ' Date / 0/L 3/7
Page 1 of 1
•
•
Article 384 — Switchboards and Panelboards
–\
A
t,,
Structural in.
ceiling OK 0 =mil - 1 - - Imisma
M
iiiii� • 4 r i • I Iiii WWI iWd UM MI Via
IV
OK _ Fixture
Suspended ■ • 1
ceiling T •
Section
AgiA
110 -16 Panel
working
61/2 ft space
minimum /
S ection
110 -16
space , -
Side view Front view " "'
Figure 384 -2. This figure illustrates the "working clearance" zone of the dedicated space required in front of the panelboard by Seta
110 -16. This is working space. Section 384- 4(a)(2) emphasizes that no equipment, electrical or otherwise, is allowed in the work sett
See Figure 384 -3 for additional space required by Section 384 -4.
A ir
I A 9 4A l
Structural
ceiling OK
I ./ %
OK Mr Fixture
Suspended — • •_______.
%------
ceiling
44 e
0 Exclusively
dedicated Panel
space
, j
j
Side view Front view
Figure 384 -3. This figure illustrates the "width and depth" zone of the dedicated space required over and under the panelboard b
Section 384- 4(a)(1). This space is for the cables, raceways, etc., that run to and from the panelboard.
•
sufficient space shall be provided to permit installation of con- Between BoBottom ttom Minimum of
ductors in the enclosure. The wiring space shall not be less than Enclosure and Busbsn
shown in the following table where the conduit or raceways enter Their Supports, or Otla
or leave the enclosure below the busbars, their su pports, or other Conductors Obstructions (InchMl
obstructions. The conduit or raceways, including their end fittings, Insulated busbars, their supports,
shall not rise more than 3 in. (76 mm) above the bottom of the or other obstructions 8 (203 mm)
Noninsulated busbars
enclosure. 10 (254 m
358 NATIONAL ELECTRICAL CODE HANDBOOK 1996
I.
Article 384 — Switchboards and Panelboards
Structural 1••
ceiling OK Q Imow -1 - - mix■,
MEM
T OK i11111 Fixture
Suspended I • •
ceiling r,r ,
Section
110 -16
(To Panel O •
working o_
61/2 ft space
minimum
S ection
110 -16
space
A
Side view Front view
Figure 384 -2. This figure illustrates the "working clearance" zone of the dedicated space required in front of the panelboard by Sec&,
110 -16. This is working space. Section 384- 4(a)(2) emphasizes that no equipment, electrical or otherwise, is allowed in the work spiel
See Figure 384 -3 for additional space required by Section 384-4.
ceiling OK � - - -.
ceilin O
AMiiii 1/iiiiM �iiii� %ilia ■W Iii �� 1 SiWii
T OK j Fixture ' / � // A
Suspended ■ ■
ceiling r
reA e A
Exclusively Panel
dedicated
space
II A
Side view Front view
Figure 384 -3. This figure illustrates the "width and depth" zone of the dedicated space required over and under the panelboard b
Section 384- 4(a)(1). This space is for the cables, raceways, etc., that run to and from the panelboard.
Minimum Spacing
sufficient space shall be provided to permit installation of con- Between Bottom of
ductors in the enclosure. The wiring space shall not be less than Enclosure and Busbar
shown in the following table where the conduit or raceways enter Their Supports, or OW
or leave the enclosure below the busbars, their su pports, or other Conductors Obstructions (Inchesf
-
obstructions. The conduit or raceways, including their end fittings, Insulated busbars, their supports,
shall not rise more than 3 in. (76 mm) above the bottom of the or other obstructions 8 (203 mm)
enclosure. Noninsulated busbars 10 (254 mM)
358 NATIONAL ELECTRICAL CODE HANDBOOK 1996