HomeMy WebLinkAbout0142480-Electric (new service) CITY OF OSHKOSH No 142480
OSHKOSH ELECTRIC PERMIT - APPLICATION AND RECORD
ON THE WATER
Job Address 3321 COUNTY RD A Owner NONWEILER INVESTMENTS LLC Create Date 08/09/2010
Contractor WITZKE ELECTRIC INC Category 651 - Industrial -New Service Plan
Service • New O Change 0 Temp 0 N/A Type 0 Overhead • Underground
Volts 277/480 Circuits Luminaires
Amps 2000 Switches Receptacles
Appliances
Use /Nature of Installation of a new service on the NE corner of the building which will back -feed the existing service and the addition of a 600A 480V
Work service for a fire -pump located on the west end of the building. *A.P. Non - Weiler * *debit acct
Fees: Valuation $75,000.00 Plan Approval $0.00 Permit Fee Paid $438.00
Issued By: Date 08/09/2010
❑ Permit Voided I Parcel Id # 1519607400
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
While the City of Oshkosh has no authority to enforce easement restrictions of which it is not a party, if you perform the work
described in this permit application within an easement, the City strongly urges the permit applicant to contact the easement
holder(s) and to secure any necessary approvals before starting such activity.
Signature Date
Agent/Owner
Address PO BOX 102 OSHKOSH WI 54903 - 102 Telephone Number (920) 235 -6572
To schedule inspections please call the Inspection Request line at 236 -5128 noting the Address, Permit Number, Type of
Inspection (i.e. Footing, Service, Final, etc.), Access into Building if Secure (how do we gain entry), your Name and Phone
Number. Unless specified otherwise, we will assume the project is ready at the time the request is received. Work may
continue if the inspection is not performed within two business days from the time the project is ready.
AUG. 9.2010 8 :50AM WITZKE ELECTRIC N0.291 P.1
City of Oshkosh
Division of Inspection Services
P.O. Box 1130
Oshkosh, WI 54903.1130 t r -\11411,,
Phone (920) 236.5050
Fax (920) 236.50,34 ' K
ON MP WA
ELECTRICAL PERMIT APPLICATION
All information after bold categories must be provided.
Incomplete applications will not be processed.
• Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI '54903.112S. Commencing work without permit(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
v u or con arrr tin a Pe it ecount Svstern, and have adequate funds. check her
i v r w hls recessed through vour account ® 0//0
DATE
JOB ADDRESSJ$Q / ei1' 7L 4
OWNS /OY.l Wet. .
CONTRACTOR \III l fzkci El eztric Inc -
CHECK LI ALL APPLICABLE
USE CATEGORY
ClSingle Family ODuplex ❑ Multi - Family ❑Rental 0Commercial ArIndustri al
SERVICE *ew ❑Temporary TYPE ❑Overhead CiNot Applicable
❑Change ❑Not Applicable underground
FILL IN THE APPROPRIATE BLANK WITH THE NYYMBER
Volts 6977 / Iiiu Receptacles # Circuits #
Phase '$
Amps Switches # Fixtures #
CHECK Lf ALL APPLICABLE
Range ❑Dishwasher ❑Garbage Disposal ❑Dryer ❑Water Heater
❑Fan OR Blower ❑Furnrnace DA/C ElElectric Sign
❑Motors CIGas Pumps ❑Other
DESCRIPTION OF ALI WORK BEING DONE ,. _5 r/1 —I,
14/ is __L._ r ,0 :irrr e.rr
iewiam, VALUE (Including labor and all materials including light fixtures) S 7.5;o°61 ` ob
BLASTER ELECTRICIAN
---_1_,,?.mt. Q—cDe,
Received Time Aug. 9. 2010 8:51AM No.2323 3v02
,
I Electric Permit Work Card
J ob Address 3321 COUNTY RD A Permit Number 142480 Create Date 8/9/2010
Owner NONWEILER INVESTMENTS LLC Contractor WITZKE ELECTRIC INC
Service . New 0 Change() Temp 0 N/A Type 0 Overhead • Underground O N/A
Volts 277/480 Circuits Luminaires
Amps 2000 Switches Receptacles Value $75,000.00
Use /Nature Installation of a new service on the NE corner of the building which will back -feed the existing service and the addition of a
of Work 600A 480V service for a fire -pump located on the west end of the building. *A.P. Non - Weiler * *debit acctapproved 1
i
i
Inspections:
Date 08/18/2010 Type Underground Inspector Adam Krause approved
Request line / Wants to know if you want to inspect the underground conduits. Trench is open. Please call Dan and let him know if
you are going to inspect.
■
I
i
L
Date/Time requested: 08/17/2010 03:06 PM Notice Type: Ready Date/Time: 08/17/2010 03:06 PM
Access: —
Requested by: WITZKE ELECTRIC INC - Dan Phone Number: 379 - 4
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 10/01 /2010 Type Service Inspector Kevin Benner — t�� approved
QUAKED conducting GFP test this morning .
eviewed with Charlie & Dan while on site. 65KAIC MCB
Faxed to WPS 10/4/10
Date/Time requested: 09/30/2010 07:46 AM Notice Type: Ready Date/Time: 09/3 07:46 AM
Access: Open
- - - - - -- - - --
Requested by: WITZKE ELECTRIC INC - Dan Phone Number: 379 -4967
0 Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
•
SQARE LD Services Division
Schneider Electric LV Circuit Breaker
,RVIUMf a New his. -mu `f '," kJ 1- 888 - 778 -2733
(Manually Operated)
REFERENCE INFORMATION
Contact Name: FSR: LARRY AKSTULEWICZ Job No: 29106562 -001
Customer Site: WITZKE ELECTRIC Customer Ref No: 0224189 DBID: 21- 284160
C/O A P NONWEILER
CO. Date: September 30, 2010
3321 NORTH SHORE
DRIVE
OSHKOSH, WI 54903
IDENTIFICATION
Sub Station Location: North Main Service Customer Asset ID:
Sub ID: Main Circuit ID: Main
NAMEPLATE DATA
Manufacture: Manufacture Date: Serial No: Type:
Square D 10363 06411117170001 RK2000
Frame Size: Rated Amps: Sensor Rating: Rating Plug:
2000 Amps 2000 Amps 2000 Amps 2000 Amps
Fuse Type: Fuse Manufacture: Fuse Model /Catalog No: Fuse Rating:
Square D
Trip Unit Type: Trip Curve No: Interrupt Rating: Mounting:
Micrologic 6.0A n/a 65 KA Fixed
Number of Operations: Number of Operations:
INSPECTION CHECKLIST
ITEM AS LEFT ITEM AS LEFT
Blown Fuse Indicator (BFI): Not Applicable Switch Condition: Acceptable
Interlocks: Not Applicable Primary Disconnects: Not Applicable
Over - Travel Stops: Not Applicable Secondary Disconnects: Not Applicable
Mechanical Wear: Not Applicable Ground Contacts: Acceptable
Mechanical Lubrication: Not Applicable Main Contacts: Tested
Intermediate Contacts: Not Applicable Arcing Contacts: Not Applicable
Trip Free Test: Acceptable Pri.Current Path Lubrication: Not Applicable
Manual Close Test: Acceptable Arc Chutes: Not Applicable
Spring Discharge: Not Applicable Interphase Barriers: Not Applicable
Insulated Linkages /Bracing: Acceptable Gap / Wipe Settings: Not Applicable
Contact Alignment / Acceptable
Sequence:
Test Report, 29106562 - 001 4.
INSPECTION NOTES
Generic Note Ground Fault sytem was primary injected with 510 amps, Main circuit breaker GF set at 500 amps,
tripped with a time of 0.129 seconds. Ground Fault system operates as designed.
INSULATION RESISTANCE TEST
Test Equipment ID: Calibration Date: 1/10 FSR: 7072 Test Voltage: 500
Megger
Tests are performed with breaker Tests are performed with breaker
CLOSED and all unenergized poles grounded OPEN and all unenergized poles grounded
AS FOUND AS LEFT AS FOUND AS LEFT
AToB 90GS2 KS2 ALINE TO LOAD 1.5TS2 K
AToC 127GS2 KS2 B LINE TOLOAD 1.5TS2 KS2
BToC 129G12 K12 CLINE TO LOAD 1.5TS2 KS2
A TO GROUND 53.2 G S2 K E2
B TO GROUND 56.3 G 12 K 0 TEMPERATURE 60 °F °F
C TO GROUND 61.7 G E2 K E2 HUMIDITY 55 % %
CONTROL WIRING TEST
Test Voltage: Kv As Found: As Left:
CONTACT RESISTANCE TEST
Test Equipment ID: Ductor Calibration Date: 1/10 FSR: 7072
THROUGH PRIMARY DISCONNECT FINGERS AND /OR BYPASS PRIMARY DISCONNECT FINGERS AND /OR FUSES
FUSES (IF APPLICABLE) (OR NO PRIMARY DISCONNECT FINGERS AND /OR FUSES)
AS FOUND AS LEFT AS FOUND AS LEFT
PHASE A PHASE A 20 p S2
PHASE B PHASE B 19 p 12
PHASE C PHASEC 16NS2
OVER CURRENT PROTECTION - TRIP UNIT DATA
Test Equipment ID: FFTS Calibration Date: 1/10 FSR: 7072
Manufacture: Square D Trip Device Serial #: 6.0A Style: Micrologic
Battery Status As Found: Pass As Left: Pass
Settings
CT Coil Ratings: CT Tap Ratings: Rating Plug: 2,000
As As As Left I *2T As As As Left I *2T
Found Tested Setting ON Found Tested Setting ON
Setting Setting Setting Setting
Long Time Pickup 1 1 1 Instantaneous Pickup 2 2 2
Long Time Delay .5 .5 .5 Ground Fault Pickup A A A
Short Time Pickup 1.5 1.5 1.5 Ground Fault Delay .1 .1 .1 Yes
Short Time Delay .1 .1 .1 Yes
Test Report, 29106562 - 001 5.
TRIP UNIT TIMING TEST (measured in Seconds)
Trip Device Test Current Specified Range Phase A Phase B Phase C
Function Amps
Amp Range Minimum Maximum As Found As Left As Found As Left As Found As Left
Long Time 2,667 10 15 13.88 13.88 13.88
Short Time 3,500 3 8 5.106 5.106 5.106
Instantaneous 5,000 0.005 0.05 0.036 0.036 0.036
Ground Fault 1,000 0.05 0.5 0.131 0.131 0.131
Test Report, 29106562 - 001 6.