HomeMy WebLinkAboutBuilding P2-2994-0410 (05/10/10) City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903 -1130
W HI'J �' www.ci.oshkosh.wi.us
ON THE WATER
May 10, 2010:
James Putman
19 Waugoo Ave, Suite 200
Oshkosh, WI 54901
Ratomir Miladinovie
1209 N Main St.
Oshkosh, WI 54901
Site: Plan Number: P2 2994 - 0410
Unknown business spaces
1205 -1209 N Main St
Oshkosh WI 54901
For:
Description: Tenant space alterations
Object Type: Building only
Class of Construction: VB - 3215 Sq Ft.; Unsprinklered
Occupancy: B: Business
NOTE: There are to be no residential uses of this property without additional plan review and approval.
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) / Conditions:
• IBC 906.1 / IFC 906.3 The maximum travel distance allowed to a fire extinguisher is 75 feet.
• IBC 1011 Exit signs are required to be installed per this section
• IBC 1006.3 Means of egress illumination is required to be installed per this section. All paths of egress are required
to have adequate emergency lighting to meet the performance requirements of IBC 1006.4. Existing means of
egress emergency lighting is permitted to be maintained in compliance with the code in effect at the time of
construction. Any altered path of egress, or new path of egress, and any new emergency lighting being installed
is required to comply with current code requirements.
• IBC 1210.1 Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard,
nonabsorbent surface that extends upward onto the walls at least 6 inches (152 mm).
• IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of
goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed
throughout the building or facility, accessible counters shall also be dispersed.
• IBC 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and
in the minimum number shown in Table 2902.1. Plans do not show the required service sink for each tenant
space. Provide service sink that is accessible to all tenant spaces, or provide a service sink in each tenant
space.
• IBC 2902.1 / Table 2902 Drinking water is required to be provided. No drinking fountain is shown on plans
drinking water is required to be provided in conformance with this code.
IaInspections\Plan Revie;v»U I0\P2 -2994 -0410 1209 N Main St Bldg Only dm;
Page 1 of 2
II I
• Comm 61.30(3) — This approval does not include heating, ventilating or air conditioning. The owner should be
reminded that HVAC plans, calculations and appropriate fees are required to be submitted for review and approval
prior to installation. The State of Wisconsin, Safety and Buildings division offers a number of worksheets and
checklists for Commercial Building Code at http: // commerce. wi. gov /SB /SB- CommBldgPlanRevInfo.html that may
assist you in preparing this submittal. Building Designer should coordinate with HVAC designer to avoid problems
with clearance to combustibles, dampers etc. The submitted HVAC plans shall match the approved building plans.
Building Designer is requested to provide complete set of Plans, Energy Calculations and Building Plan Review
Letter to the HVAC Designer to help coordinate review. Note as per Comm 2.10 installation of HVAC without
approved plans could result in double fees.
• Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve rules under
this code and which are made to construction documents that have previously been granted approval by the
department or its authorized representative, shall be submitted to the office that granted the approval. All revisions
and modifications to plans shall be approved in writing by the department or its authorized representative prior to the
work involved in the revision or modification being carried out. A revision or modification to a plan, drawing or
specification shall be signed and sealed in accordance with Comm 61.31(1).
SUBMIT:
• IBC 1006.3 Means of egress illumination is required to be installed per this section. All paths of egress through
The Retail Display area are required to have adequate emergency lighting to meet the performance requirements
of IBC 1006.4. Provide complete emergency lighting plan showing compliance with these requirements
prior to installation of emergency lighting system. A copy of the City of Oshkosh Policy on Emergency
Lighting is attached to this letter.
• Comm 61.40 (4) Supervision. Prior to the initial occupancy of a new building or addition and prior to the final
occupancy of an alteration of an existing building the supervising professional shall file a compliance statement
form SBD - 9720 with this office. Note: Submittal of a compliance statement will be considered as evidence that
the supervising professional has properly addressed all items identified in this plan review letter.
A copy of the approved plans, specifications, and this letter shall be ! on -site during construction. If plan index sheets were
submitted in lieu of additional full plan sets, a copy of this approval', letter and index sheet shall be attached to plans that
correspond with the copy on file with the copy on file in this office.
All permits are required to be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component. The City of
Oshkosh does not take responsibility for the design or construction of the reviewed items.
Inquiries concerning this correspondence may be made to me at the number listed below or the address on this letterhead.
Respec..- `■
Brian Noe
Building Systems Consultant
(920) 236 -5051
bnoe @ci.oshkosh.wi.us
cc: Property file Fee Required $ 400.00
Fee Received $ 400.00
Balance Due $ 0.00
I: \Inspections \Plan Review \2010 \P2 -2994 -0410 1209 N Main St Bide Onl■.doc