Introduction
Li Required for Occupancy Occupancy Commercial
At the request of the building owner an inspection of the replacement furnaces installed under permits # 134271 and 131816
was made on Monday April 19th, 2010.The following violations were noted at that inspection.
Item # 1 Code IMC 307.1 Comm 82.38 Compliance No Compliance Date 05/19/2010 IMMEDIATELY
Description The condensate from the furnaces is required to be discharged to a proper sanitary drain. These fumaces have been piped to discharge to a
foundation drain sump pit.Provide proper code compliant discharge point for furnace condensate.
04/19/2010
Last
Updated
Item # 2 Code IMC 306.1 Compliance No Compliance Date 05/20/2010 IMMEDIATELY
Description The filter opening on the return of the furnaces is too close to the electrical connection of the furnace to allow for the removal and replacement
of the furnace filters without damaging the filter. — Provide filter opening that allows for clearance to remove filters, or relocate electrical
04/20/2010 connection to allow for replacement of furnace filters without dmaging filters.
Last
Updated
15975 Page 1 of 2
INSPECTION SERVICES DIVISION ROOM 205 CITY OF OSHKOSH
DEPARTMENT OF COMMUNITY DEVELOPMENT 215 CHURCH AVE
OSHKOSH CORRECTION NOTICE PO Box 1130
ON THE WATER
OSHKOSH WI 54903 -1130
Issue Date 4/19/2010 Compliance Date 5/19/2010 Compliance No
Address 510 DOCTORS CT
Name Address City State Zip Code
Sent to a Owner MERCY MEDICAL CENTER OSH INC PO BOX 3370 OSHKOSH WI 54903 -3370
_J Required for Occupancy Occupancy Commercial
Introduction
At the request of the building owner an inspection of the replacement furnaces installed under permits # 134271 and 131816
was made on Monday April 19th, 2010.The following violations were noted at that inspection.
Item # 3 Code IMC 304.1 Compliance No Compliance Date 05/20/2010 IMMEDIATELY
Description The exhaust and intake pipes form the furnaces were not glued. The owner has corrected most of this piping, however there remain portions
that are not properly glued. — Verlfy that all portions of piping have been properly glued and supported.
04/20/2010
Last
Updated
Summary Please arrange for a reinspection when corrections have been made.
Violations must be corrected and approved within 30 days unless otherwise noted. Call for reinspections prior to concealment
and /or occupancy. Upon completing the corrections, the owner /contractor /agent must sign and date at the bottom of this notice
and return it to the Inspection Services Division by the Compliance Date of 5/19/2010
Office hours for obtaining permits are Monday through Friday 7:30 -8:30 a.m. and 12:30 -1:30 p.m. or by appointment. To schedule
inspections please call the I spection Request line at 236 -5128 noting the address, permit number (when applicable), and the
nature of what need l inspected.
Signature ��,/ Date , //26A
Inspected by: Brian Noe 236 -5015 bnoe@ci.oshkosh.wi.us
I hereby certify the violations listed on this report have been corrected in compliance with the applicable codes.
Print Name Company
Signature Date
Also Sent to: U Bldg
u Elec -
u HVAC CONDON TOTAL COMFORT PO BOX 184 RIPON WI 54971 -184
U Plbg _
Designer
Li Other -
12ej Inspector Kevin Benner