HomeMy WebLinkAbout0140443-Electric (2000 amp outdoor service) Electric Permit Work Card
Job Address 339 W 20TH AVE Permit Number 140443 Create Date 4/12/2010
Owner OSHKOSH CORPORATION Contractor BEEZ ELECTRIC INC
Service New 0 Change° Temp 0 N/A Type 0 Overhead • Underground 0 N/A
Volts 277/480 Circuits Luminaires
Amps 2000 Switches Receptacles Value $35,000.00
Use /Nature JND / Installing new outdoor 2000 amp service. **debit acct
of Work
Inspections:
Date 04/19/2010 Type Underground Inspector Kevin Benner approved
Discussed driving the ground rods in lieu of laying them in the trench
Date/Time requested: 04/19/2010 06:54 AM Notice Type: Ready Date/Time: 04/19/2010 11:00 AM
Access: Eric Folsky will be on site
Requested by: BEEZ ELECTRIC INC Phone Number: 379 -5601 Rob
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 04/29/2010 Type Service Inspector Kevin Benner approved w /cond.
Inspection was requested to install a 400A disconnect on an existing buss duct. The electrical contractor is requesting that the utility
• isconnect the service in leiu of shutting down the service disconnect. Because this installation is on the load sidethe service disconnect an
inspection will not be required before the service is re- energized by the utility. Faxed to WPS 4/29/10
Date/Time requested: 04/29/2010 12:42 PM Notice Type: Ready Date/Time: 05/01/2010 12:00 PM
Access:
Requested by: BEEZ ELECTRIC INC Phone Number: 920 - 379 -5601 Rob Jones
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date 05/28/2010 Type Service Inspector Kevin Benner approved
REQUEST LINE / READY FOR A SERVICE INSPECTION
Need confirmation from Sq.D that the MCB has a max. setting of 800A (2000A device) 65KAIC. Reviewed with Rob Jones & Eric Folsky.
44/10 12:10 PM Received confirmation of the MCB setting & Rob stated that hewould seal the cover over the adjusting means of the CB I
immediately. APPROVED TO ENERGIZE. FAXED TO WPS 6/5/10. Scheduled for switch -over 6/6/10.
Date/Time requested: 05/24/2010 03:21 PM Notice Type: Ready Date/Time: 05/28/2010 00:00
Access:
Requested by: BEEZ ELECTRIC INC - Rob Phone Number: (920) 379 -5601
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
SQUARE D
Schneider Electric
110 Packerland Drive, Suite C -2
Green Bay, WI 543 -4
y, 03 861
Phone (920) 494 -3313 Fax (859)- 372 -1830 May 27, 2010
RE: OSHKOSH TRUCK
Shipping Building
pp g Id ng
1901 Osborne Street
Oshkosh, WI 54902
SUBJECT: SQUARE D FO #28179635
Hello,
This is to confirm that the ground fault trip 9 on the Square D /PowerPact RK
2000AS /800AT utility breaker located within the service entrance switchboard
was tested on 5/27/2010. The test was performed in accordance with NEC
230.95(C).
With the ground fault trip set to .500 amperes on the breaker, 1000A of
ground fault current was injected.
The breaker properly tripped g P p Y PP ed due to the
ground fault current in . 10,R seconds.
Additionally, a Time Current Coordination Study was conducted to determine the
optimum TCC settings of the type RK main circuit breaker. Results of the study
are included with this document. The TCC dials on the RK main circuit breaker
have been set based on the results of the TCC Study. Using the full function test
kit S33595, it was determined that the microprosser based trip unit is operational
and within calibration.
Regards,
SQUARE D COMPANY
eiir�v a CW/ - RC 6
R. C. Batson
Senior Executive Field Engineer
•
1
UTIL -0001
CBL -0001
T
) PD -0001, MCB
- SQUARE D
RK
Sensor/Trip 2000.0 A
Settings
LTPU /LTD (A 0.4 -1.0 x S) 0.4 (800A); 24
STPU (1.5 -10 x LTPU) 10 (8000A)
STD (0 -0.4) 0.4 (I ^2t In)
INST (2 -15 x S) 6 (12000A) y} PD -0003, 400A LC
) PD -0002, MCB GFP SQUARE D
SQUARE D LC
RG Sensor/Trip 400.0 A
Sensor /Trip 1600.0 A Settings
Settings Thermal Curve
GFPU (500- 1200A) A (500A) INST HI (4000A)
GFD (0 -0.4) 0.1 (I ^2t In)
MDP
480 V
Isc 3P 60188 A
Project: OSHKOSH TRUCK SHIPPING BLDG 28179635
Scenario: Base Project
LV Breakers
Description Frame /Sensor /Plug Settings
SQUARE D RK 2500.0A Phase
Powerpact R- Framc, 6.OA /P /H 2000.0A LTPU /LTD (A 0.4 -1.0 x S) 0.4 (800A); 24
LSI, 600- 2500A, UL STPU (1.5 -10 x LTPU) 10 (8000A)
STD (0 -0.4) 0.4 (1 ^21 In)
INST (2 -15 x S) 6 (12000A)
SQUARE D R 2 A
Q G 500.0 Phase
Powerpact R- Frame, 6.0A/P /H 1600.0A GFPU (500- 1200A) A (500A)
GF, 1600- 2500AS, UL GFD (0 -0.4) 0.1 (1 ^21 In)
SQUARE D LC 400.0A Phase
LC 400.0A Thermal Curve
300 -600A INST HI (4000A)
Page 1
CURRENT IN AMPERES
1000 ,,
. O i
tki k PD- 0001 % , MCB \ ►
1 1 S
100 0.
PD -0002, MCB GFP c � • t
i � �
F.' \ .
PD -0003, 400A LC X t 0- c,
I 4`0
0
10
Co
�y
4.
ki
o rn
1 % z
9 w rn
o' r 0
�j � O
'e: Z
46
i w
. a,
i : yi:•i ii0a i• .�i� •i �+y i iOe �Oi ��� a %O � i• ; i
(� 6•iiii0 O)••O a4� ` 0•4•ii►�• , ie'a04 ;
0.10 �iiligii 0 � i ai a�0°i i•�ii`%i i%•`a�•'�i,'O�'� iI
aa0m$:4��•�o�s $::: 1: a te .
.
•
•
0.01
�V
0.5 1 10 100 1K 10K 100K
TCC OTC 28179635.tcc Ref. Voltage: 480V Current in Amps x 1