STANDARD WORKSHEET
STATE ENERGY CODE COMPLIANCE
CUSTOMER: D. VIERTHALER FAB: 41059 MODEL: BROOKVILLE
LOCATION: OSHKOSH STATE: WIS. DATE: 2-09-84
DEALER: C. CULBERTSON CALCULATED BY RMR
APPROVED PER: INITIAL__XXX___ CHANGE ORDER_______ FINA L_______
ASSEMBLY | AREA(A) U UxA
(S.F.) VALUE
IVLT. I INS. AREA % .93 0 .019 .00
}CLG. 1FRAME AREA % .07 .00 .022 .00
CLG./ ___} INSUL. 1ADDT'L INSUL. 0 .00
ROOF !FLAT *AREA% .93|STANDARD >> 1346.64 .019 25.
PANEL:ICLG. i FRAME |ADDT'L INSUL. .00 .00
90 % -10 %_____I *AREA% .07|STANDARD 101.36 .022 2.23
TRUSS:|OTHERI
. 00
93%-7%1 1 } TOTALS 1448 ///// 27.82
1 2 1 AVE.U-VAL.(UxA)/A FROM LINE 1 ////// .0192 //////
3 I REQUIRED U-VALUE 7/1/1/ .029 //////
_� _________________________________________________________________
I SLIDERS/DOUBLE HUNG 155.3 .3 46.59
W I CASEMENTS/AWNING 77.1 .34 26.21
} D i BAY .36 .00
W 1 PICTURE .36 .00
S. I OTHER .00
E i ;
----- .00
X 3 } STEEL 2-E1 4 .139 5.70
P R | PATIO 45.1 .37 16.
O | 8 | FRENCH .00
S ! ]
____ OTHER .00
E J 1 . 07 .00
D ISTD � `
. �m�o���/�u �n >> 926.08 .042 38.90
|WA�L ' FRAM I N �
~ ��-= ' 163.43 .073 11.93
W '_____� RING J A } F } WINDOW� ��
�4 �� � > 146.67 .056 8.21
- K� ^~
X12 13.5 .5 6.75
L I O W i DOORS
0 .00
L 7 U A i OTHER � c�r l �/ .690
S I N L I OTHER
' .00
} D.L | FOUND. W � _L � )} 103.83 .154 15.99
} I OTHER ` DP- =-
. 00
f 4 1 TOTALS . 1672 ///// 176.97
I 5 I AVE.U-VAL. (UxA)/A FROM LINE 4 ////// .1058 //////
i 6 REQUIRED U-VALUE ////// .13 //////
!| _ ________
|FLOOR} - ---------
. 00
FLOORSiAREA I
. 00
OVER ' �
--- -- .00
UNH'TD 7 1 TOTALS .00 ///// .00
AREAS ; 8 1 AVE. U-VAL. (UxA)/A FROM LINE 4 //////ERROR //////
} 9 i REQUIRED U-VALUE ////// //////
t _____�______________________________________________
FDN. I AREA I }> 5� �------ �� ---------
� ERM �(1 3' 0"} 528. 00 '--� ~~^^'
^ .00
Era OW | ONLY) }
. 00
GRADE ! �
---------- .00
(WIS. 10 � TOTALS
^ 528.00 ///// 59.14
ONLY) | 11 ! AVE.U FROM LINE 10 ////// .112 //////
1 12 ) REQUIRED U-VALUE ////// .20 //////
,} ___________________________________________
!IF LINE 2 IS MORE THAN LINE 3, OR 5 IS MORE THAN ~' ----- OR " ~ MORE
�� ------------
/THAN 9, OR 11 IS MORE THAN 12, COMP.THE FOLLOWING TOTAL ENVELOPE ^ METHOD
____________
1 13 1 ACT. BTUH (LINES 1+4+7) (T.D.)+(LINE 10) (T---�T----- )
i T.D. 85 T.D.BASM'T 58 20807 BTUH
E 14 i AREA(LINE 1)x U 3)(T.0.) 3569 BTUH
TN M �
O V E i 15 ! AREA(LINE 4)x U-VALUE(LINE 6) (T.D.) 18476 BTUH
7 i
A L. H 16 I AREA(; IME 7) x U-VAL UE(LINE 9) (T.D.) 0 BTUH
LOO 1
P D 17 i AREA(LINE 10)x U 12)(T.D. BASM'T) 6072 BTU-
..--- !
} 18 1 "BUDGET" (LINES 14+15+16+17) 28117 BTUH
}__
ALTER ASSEM-
!IF LINE 13 IS MORE THAN LINE 18, ASSEMBLIES AS REQUIRED SO
!LINE 13 DOES NOT EXCEED LINE 18
�
___________-________________________________
WICK HOMES
STANDARD WORKSHEET
HEAT LOSS/FURNACE SIZING CALCULATIONS
CUSTOMER: D. VIERTHALER DEALER: C. CULBERTSON FAB:41089 DATE: 2-09-84
------------------------------------------------------------------------------
TOTAL HEAT LOSS (BTUH)= HOUSE + INFILTRATION + VENTILATION + BELOW GRADE LOSS
T.D. = THE TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR DESIGN TEMPERATURE
AND THE EXTERIOR DESIGN TEMPERATURE
INT. TEMP. 70 - EXT. TEMP. OF -15 =T.D. OF 85 DEG.
T.D. = THE TEMPERATURE DIFFERENCE BETWEEN THE INTERIOR DESIGN TEMPERATURE
BSM'T AND THE AVERAGE GROUND TEMPERATURE OUTSIDE THE FOUNDATION WALL.
AVG. TEMP.= 40 + -15 EXT. DES. TEMP.= 12.5 DEG.
DIVIDE BY 2
INT. TEMP. 70 - AVG. TEMP. 12.5=T.D.BM'T 57.5 DEG.
HOUSE BTUH LOSS:
(UxA) = THE SUM OF LINES 1 4, AND 7 ON THE STATE ENERGY CODE COMPLIANCE
WORKSHEET.
(UxA) = LINE 1 27.8 + LINE 4 177.0+ LINE 7 0 = 204.8
BTUH LOSS = (UxA) (T.D.) 204.79x 85= 17407 BTUH
INFILTRATION: .6 AIR CHANGE IN THE HOUSE PER HOUR + BSM'T. AIR CHANGE
(.25: . 50: .75; 1) (CU. FT. LIVING SPACE) (T.D.) (.018)
ABOVE GRADE: .6 11584 85 .018= 10634 BTUH
BELOW GRADE: .25 10860 85 .018= 4154 BTUH
VENTILATION AIR: FRESH AIR AT 25 (C! R 100) CFM OR
25CFM(60) (T.D.) (.018)
1500 85 .018= 2295 BTUH
DUCT LOSS: (UNCONDITIONED SPACES) BTUH CARRIED IN DUCT x LOSS FACTOR
0 0 = 0 BTUH
F8UNDATION PERIMETER BTUH LOSS: (WIS. ONLY)
FIRST 3'-0" BELOW GRADE
(UxA LINE 10)(T.D.BSM'T) 59.14 57.5= 3401 BTUH
BELOW GRADE FOUNDATION (CONDITIONED SPACES LESS FOUNDATION
PERIMETER LOSS)
CONSTRUCTION U-VALUE AREA T.D.BSM'T
0 BTUH
8"CONC.W/1" STYRO .112 704 57.5= 4534 BTUH
57.5= 0 BTUH
0 BTUH
BASEMENT FLOOR LOSS:(CONDITIONED SPACE)
(U TEMP.-40
.023 1448 30= 999 BTUH
TOTAL HEAT LOSS: ----------
43424 BTUH
FURNACE SIZE**
SELECTED FURNACE TOTAL CAL. HEAT LOSS= 43424 BTUH
580S-075-201 % ALLOWABLE OVERSIZE
FUEL: NAT. GAS LIMIT = .15 6514 BTUH
INPUT: 75M BTUH
OUTPUT: 57M BTUH ALLOWABLE FURN. SIZE= 49937 BTUH
_ ____________________________________________
**WHEN SUPPLIED BY WICK HOMES, THE FURNACE SIZE SHALL NOT EXCEED --------- UL
HEAT LOSS PLUS THE STATE OVERSIZZNG LIMIT, WHENEVER APPROPRIATE CARRIER AIR
CONDITIONING CORP. EQUIPMENT IS AVAILABLE OR TO BE COMPATIBLE WITH THE
APPROPRIATE SIZE AIR CONDITIONER OR HEAT PUMP INSTALLATION.