HomeMy WebLinkAbout0139348-Electric (interior remodel) Electric Permit Work Card
Job Address 1402 MOUNT VERNON ST Permit Number 139348 Create Date 12/28/2009
Owner ADAPTIVE PROPERTIES LLC Contractor LEWINS ELECTRIC
Service 0 New 0 Change 0 Temp • N/A Type 0 Overhead 0 Underground • N/A
Volts Circuits Luminaires
Amps Switches Receptacles Value $5,000.00
Use /Nature Davis Painting* / Paint booth wirring, Lighting for spray area, remodel office & bathroom(s) remodel, replace some existing
of Wort( electrical panels from corrosionCN
Inspections:
Date/Time Inspected 01/22/2010 12:OOAM Type Consultation Inspector Kevin Benner CN
The electrical concerns were being addressed by the E.C. and we did not have any differences of opinions.There were some additional
concerns about some hazardous location issues with reference to Davis Painting's areas.
Date/Time requested: 01/20/2010 10:13 AM Notice Type: Ready Date/Time: 01/22/2010 09:30AM
Access:
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561 Randy
O Reinspect Fee 0 Fee Wavied Reinspect Fee Paid
Date/Time Inspected 03/15/2010 12:OOAM Type Rough In Inspector Kevin Benner approve
The wall switch in the water heater closet did not have the piping installed because they were waiting for the wall to be completed for
the install. All other wiring was approved. Callled Randy while I was on site to discuss.
Date/Time requested: 03/12/2010 07:57 AM Notice Type: Ready Date/Time: 03/12/2010 12:58PM
Access:
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561 Randy
O Reinspect Fee 0 Fee Wavied J Reinspect Fee Paid
Date/Time Inspected 04/20/2010 12:OOAM Type Consultation Inspector Kevin Benner not apps
Emergency Illumination in paint booth areallot ready. We also reviewed the paint booth installation requirements and we discussed the
luminaire wiring methods and gas bonding
Date/Time requested: 04 /20/2010 07:34 AM Notice Type: Ready Date/Time: 04/20/2010 09:15AM
Access:
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561 Randy
O Reinspect Fee 0 Fee Wavied fl Reinspect Fee Paid
Electric Permit Work Card
Job Address 1402 MOUNT VERNON ST Permit Number 139348 Create Date 12/28/2009
Owner ADAPTIVE PROPERTIES LLC Contractor LEWINS ELECTRIC
Service 0 New 0 Change° Temp • N/A Type 0 Overhead 0 Underground • N/A
Volts Circuits Luminaires
Amps Switches Receptacles Value $5,000.00
Use /Nature Davis Painting* / Paint booth wirring, Lighting for spray area, remodel office & bathroom(s) remodel, replace some existing
of Work electrical panels from corrosion
Inspections:
Date/Time Inspected 04/23/2010 12:OOAM Type Consultation Inspector Kevin Benner not appi
Meet Adam Krause & Randy on site to review for a Final Inspection for this area in the PMGrounding done w/ self- tapping sheet metal
screws, luminaires hard wired with cords, Ex. Fan not listed for CI1 Div.1. completion of other work.
Date/Time requested: 04/22/2010 01:31 PM Notice Type: Ready Date/Time: 04/23/2010 07:33AM
Access:
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561 Randy
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 04 /23/2010 12:OOAM Type Consultation Inspector Adam Krause CN
Date/Time requested: 04/23/2010 12:08 PM Notice Type: Ready Date/Time: 04/23/2010 12:08PM
Access:
Requested by: LEWINS ELECTRIC Phone Number:
O Reinspect Fee 0 Fee Wavied Reinspect Fee Paid
Date/Time Inspected 04/23/2010 12:OOAM Type Final Inspector Adam Krause not appi
Not ready
Date/Time requested: 04/23/2010 12:28 PM Notice Type: Ready Date/Time: 04/23/2010 12:28PM
Access:
Requested by: LEWINS ELECTRIC Phone Number:
O Reinspect Fee 0 Fee Wavied LJ Reinspect Fee Paid
Electric Permit Work Card
Job Address 1402 MOUNT VERNON ST Permit Number 139348 Create Date 12/28/2009
Owner ADAPTIVE PROPERTIES LLC Contractor LEWINS ELECTRIC
Service New 0 Change() Temp • N/A Type 0 Overhead 0 Underground • N/A
Volts Circuits Luminaires
Amps Switches Receptacles Value $5,000.00
Use /Nature Davis Painting* / Paint booth wirring, Lighting for spray area, remodel office & bathroom(s) remodel, replace some existing
of Work electrical panels from corrosion
Inspections:
Date/Time Inspected 04/28/2010 12:OOAM Type Re Final Inspector Kevin Benner not appi
REQUEST LINE / READY FOR A FINAL INSPECTION/ ID OCPD's, ID the locations of the disconnects for the panels, breaker blank,
MUA disconnect height, MUA grounding, gas pipe bonding, sheet metal screws used for grounding, Dept. approval for the paint booth
ex . fan. Reviewed with Randy while on site.. fan. Reviewed with Randy while on site.
Date/Time requested: 04/26/2010 06:49 AM Notice Type: Ready Date/Time: 04/26/2010 08:22AM
Access: CALL RANDY FOR ACCESS
Requested by: LEWINS ELECTRIC - Randy Phone Number: (920) 540 -2561
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 07/12/2010 12:OOAM Type Re Final Inspector Kevin Benner not appi
ID OCPD's, ID the locations of the disconnects for the panels, breaker blank, MUA disconnect height, MUA grounding, gas pipe
bonding, Dept. approval for the paint booth ex. fan
Date/Time requested: 07/09/2010 08:14 AM Notice Type: Ready Date/Time: 07/09/2010 08:14AM
Access: Call Randy to schedule
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid
Date/Time Inspected 07/28/2010 12:OOAM Type Consultation Inspector Kevin Benner CN
Review concerns with the cities Comm. Dev. Director Allen Davis
Date/Time requested: 07/26/2010 00:00 PM Notice Type: Ready Date/Time: 07/28/2010 08:42AM
Access:
Requested by: LEWINS ELECTRIC Phone Number: 540 -2561
O Reinspect Fee 0 Fee Wavied ❑ Reinspect Fee Paid