HomeMy WebLinkAboutElectric - 10/18/1996 0 CODE ENFORCEMENT DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 10/18/96 Compliance Date 11/17/96 IMMEDIATELY Compliance No
Address 2840 BRADLEY ST Inspected By John Sullivan
Name Address City State Zip Code
Sent to I>< Owner PARK PLAZA OSHKOSH P 0 BOX 234 OSHKOSH WI 54902 -0234
Contractor
U Other Park Plaza Oshkosh P 0 Box 234 Oshkosh wi 54902 -0234
U Inspector
ix Required for Occupancy Occupancy Factory Notice i First O Second O Final 0 Other
Introduction At an Occupancy Inspection the following corrections have been noted:
Item 1 Code Chapter 11 32 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description Electrical Permits Are Required.
Item 2 Code Chapter 11 22 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description All Electrical Work Shall Be Done By A Licensed Electrical Contractor.
Item 3 Code NEC 422 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description All electric heat circuits,electric water heater circuits shall have satety disconnect devices installed.
Item 4 Code NEC 110 22 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description All circuits shall have the proper identification to indicate its purpose.
Item 5 Code NEC 110 12(a) Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description Unused openings in boxes,raceways,auxilary gutters,cabinets,equipment cases,or housings shall be effectively
closed or sealed.
Page 1 of 2
el) CODE ENFORCEMENT DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date 10/18/96 Compliance Date 11/17/96 IMMEDIATELY Compliance No
Address 2840 BRADLEY ST Inspected By John Sullivan
Name Address City State Zip Code
Sent to N Owner PARK PLAZA OSHKOSH P O BOX 234 OSHKOSH WI 54902 -0234
u Contractor
u Other Park Plaza Oshkosh P 0 Box 234 Oshkosh wi 54902 -0234
Li Inspector
XI Required for Occupancy Occupancy Factory Notice le First O Second O Final 0 Other
Introduction At an Occupancy Inspection the following corrections have been noted:
Item 6 Code NEC 430 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description Walls have been built around the sprinkler pumps,disconnects are required to be within sight of the motors and
controllers.
Item 7 Code NEC 305 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description Disconnect and remove all unused wiring.
Item 8 Code NEC 110 -12 (a) Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description Install circuit breakes or breaker tillers in the unused openings.
Item 9 Code ILHR 16.45 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description All exit lights shall be working and on when this building is occupied.
Item 10 Code ILHR 16.45& 5 Compliance No Compliance Date 11/17/96 IMMEDIATELY
Description 1 his building may require emergency lighting,contact me with a floorplan of the building.
Page 2 of 2
CODE ENFORCEMENT DIVISION
DEPARTMENT OF COMMUNITY DEVELOPMENT
OSHKOSH CITY OF OSHKOSH, WISCONSIN
ON THE WATER CORRECTION NOTICE
Issue Date Compliance Date Compliance
Address Inspected By
Name Address City State Zip Code
Sent to
Occupancy Notice
Introduction
Summary 1.The Licensed Electrical Contractor shall contact me for an Electrical Permit before any electrical work is
done.The Contractor shall call for a final inspection.
DEFICIENCIES MUST BE CORRECTED AND APPROVED BEFORE CONCEALMENT. CALL (414) 236 -5050 FOR INSPECTION.
Signature Date /0 %1176
Page 2 of 2