Nov. 29, 1990
Fred Litjens
1600 Rivermill Rd.
Oshkosh, WI 54901
Dear Fred:
RE: 2050 Winchester Ave.
Storage garage
File #Q7- 122 -1190B
Building plans have been reviewed by this office for compliance
with important code requirements. The drawings are stamped
"Construction may proceed." All items that are required to be
changed by this letter must be corrected before commencing that
part of the work. This approval is not a Building Permit.
Necessary city permits must be secured before commencing work.
You are hereby advised that the owner, as defined in Chapter
101.01(i) of the Wisconsin State Statutes, is responsible for all
code requirements not specifically cited herein. Code
requirements are set forth in Chapters 50 through 64 of the rules
of the Department of Industry, Labor and Human Relations.
The building will be inspected during construction and a final
inspection will be made after completion to insure complete
compliance with city and state codes.
The architect, professional engineer, builder or owner shall keep
at the building, as evidence of approval, one set of plans bearing
the stamp of approval.
ILHR 64.02 This approval does not include heating and ventilating.
Such plans are required to be submitted and approved prior to
installation of such equipment.
ILHR 59.13 An exit door at least 3'0" in width shall be provided
in the larger storage area.
ILHR 51.15 An exit lite shall be installed above each exit service
door.
Page Two
Nov. 29, 1990
Fred Litjens
ILHR 63.12(3) Slab on grade perimeter insulation shall be
provided. This insulation shall have a minimum R value of 5.9 and
shall extend a minimum of 48 inches horizontally around the
perimeter of the heated storage area.
ILHR 51.03(18) (19) The attic shall be separated into areas less
than 3200 square feet. Each attic area shall be accessible by a
20 inch by 30 inch access panel.
ILHR51.22 Fire extinguishers shall be provided and maintained in
each storage section.
ILHR 53 Submit a structural detail with calculations showing the
header intended over the garage door in the heated storage area.
This facility is only approved as a storage structure. Any other
use will require further review.