HomeMy WebLinkAboutHVAC 72-B-1619 (02/19/1973) r State of Wisconsin DEPARTMENT OE INDUSTRY, LABOR, and HUMAN RELATIONS
February 19, 1973 2209
y MADISON, w'ISCONSIN 53701
PLEASE REPLY TO:
INDUSTRIAL SAFETY BUILDING DIVISION
E -1223
Badger Metals, Inc. Office Factory
P. 0. Box 1131 Thilmany Pulp Paper Co., Owner
221 East Atlantic Street 47--- Essst --8- Avenue
Appleton, Wisconsin 54911 Oshkosh, Winnebag&...County
Plan File 72 -B -1619
One inspection paid
Heating A ye nl i! 7 B 4 I a I "Conditionally 11 I
g plans ihe above prciec have been Stamped, Condi ionally Approved See Correspon-
dence" and two or more copies of plans are being returned to you.
1. No exceptions.
X 2. Controls shall be provided so that no less than the minimum air supply and exhaust be maintained
during period of occupancy. See Ind 59.22(1).
See 12 below Ind 59.41
3. Provide tempered outside air supply. See Ind 59.24(7), Ind 59.40, Ind 59.41.
4. Provide exhaust ventilation. See Ind 59.48, Ind 59.49, Ind 59.52.
5. The design and construction of airways. See Ind 59.69.
6. Kitchen range hoods and ducts connected to range hoods. See Ind 59.49.
7. Installation of unit heaters, suspended furnaces and duct heaters. See Ind 59.66.
8. Provide furnace room enclosure. See Ind 54.13, Ind 55.29, Ind 56.15, Ind 57.20, Ind 57.50.
9. Outside air intake. See Ind 59.60.
10. Determine whether or not the structural members carrying heating and /or ventilating equipment
are adequate.
11. Design of chimneys: See Ind 52.10 and Ind 59.67.
X Ind 59.50 Blower of unit supplying rooms 1, 3 and 6 must
12. Other exceptions: be interlocked with Exhaust V270 in Room 6.
Ind 59.53 Minimum tempered air and exhaust factory area
is 2336 CFM. Interlock mens and womens toilet with make -up
unit (1576 CFM) and provide and interlock additional exhaust
of 760 to satisfy air balance.
Ind 59.41 Six air changes also applies to occupancies referred
to above.
WJP:amt :82/13 DIVISION OF INDUSTRIAL SAFETY AND BUILDINGS
cc: District 4 -5
v/Ed Reimer, Bldg. Insp.
By
Thilmany Pulp Paper Walter J. Powell, P.E.
Kaukauna Assistant Chief Engineer
Wisconsin 54130
SB -94