lemq ,r S tate of Wisconsin Department of Industry, Labor and Human Relations
SAFETY BUILDINGS DIVISION
November 27, 1 98 t 201 E. Washington Avenue
P.O. Box 7969
File Number E-009532 Madison, Wisconsin 53707
STEPHEN GRIES ROIJ LEICHTFUSS
1233 SOUTH COMMERCIAL STREET 325 NORTH SAWYER STREET
NEENAH, WI 54956 OSHKOSH, WI 54901
aD�► RE: APARTMENT
RON LEICHTFUSS
8 -UNIT
11 CIt-IARRONJ PLACE
OSHKOSH County of WINNEBAGO
Plan Number 89 -11- 0122 -B
Volume: 111,575 cubic feet
Suprv. Professional, Building: STEPHEN GRIES
Firm Project No: 555
Your Building plans have been conditionally approved.
The plans have been reviewed for compliance with the code reouirements set
forth in Chapter ILHR 50 -64 of the rules of the department. Construction may
proceed subject to local regulations, but all items that are reouired to be
changed by this letter must be corrected before commencing that part of the
work.
This plan has not been reviewed for compliance with Chapters ILHR 82 -86, the
plumbing rules of the department.
You are hereby advised that the owner, as defined in s. ILHR 101.01 (2)(e) of
the Wisconsin State Statutes, is responsible for all code reouirements not
specifically cited herein.
The building will be inspected during and after construction. The owner
shall notify the state building inspector and the local officials before
taking possession of the building.
ILHR 50.15 EVIDENCE OF APPROVAL. The architect, professional engineer,
designer, builder or owner shall keep at the building, one set of plans.
ILHR 64.02 This review does not include heating, ventilation and air
conditioning.
ILt3R 50.12 Truss plans and calculations along with the proper fees and Plan
Approval Application Form (SB -118) shall be submitted to this office and
approved prior to installation of that component. All component plan
Application forms for buildings greater than 50,000 cubic feet in volume shall
include the name of the building or component designer and be SIGHED by the
supervising professional of the project.
SBD -6928 (R. 10/87)
v tit
State of Wisconsin Department of Industry, Labor and Human Relations
SAFETY BUILDINGS DIVISION
201 E. Washington Avenue
P.O. Box 7969
STEPHEN GRI ES Madison, Wisconsin 53707
November 27, 1989
Page 2
ILHR 53.11(4)(c) Provide for additional snow load on office roof due to
changes in roof elevations. Provide calcs in truss plans.
ILHR 51.16(5)(c) Stairs include platforms; rooms under stairs and platforms
are not permitted.
ILHR 53.63(1) Detail 2/4 wall intersects with floor system and with bottom
chord of truss, and FIRE STOPPING is required at these locations to
prevent spread of fire through concealed spaces.
ILHR 57.17 FIRE ALARM is rewired with pull stations per ILHR 51.24(4).
ILIiR 57.16(1)(b) (c) Smoke detectors are required at head of open stairs
and in sleeping areas.
ILHR 51.14 Provide safety glass in hazardous impact areas.
This building is classified as No. 8, wood frame construction.
Sincerely,
Duane E. Peterson
Plan Examiner
(608) 266-7849
DEP:vs:1229
cc: State Building Inspector: R -3 Ochs (414) 929 -3167 Friday
.building Inspector, OSHKOSH
SBD -6928 (R. 10 /87)