HomeMy WebLinkAbout0100209-Electric
e
OSHKOSH
ON THE WATER
CITY OF OSHKOSH
No 100209
ELECTRIC PERMIT - APPLICATION AND RECORD
Job Address
3550 MOSER ST
Owner
BANNER PACKAGING INC
Create Date 03/14/2003
Contractor
ARROW ELECTRIC OF OSHKOSH
Category 653 - Industrial-Addition/Remodels
Plan
Service
10 New
480/277
0 Change
0 Temp
Volts
Circuits
Type
0
10 Overhead
0 Underground
Fixtures
18
Amps
200
Switches
0
Receptacles
Appliances
Use/Nature of Factory/ Wiring for the warehouse addition (Cold Storage).
Work
Fees: Valuation
$10,000.00
Plan Approval
$0.00
Permit Fee Paid
$180.00
Issued By:
Date 03/14/2003
U Permit Voided I
In the performance of this work I agree to perform all work pursuant to rules governing the described construction.
Signature
Date
Agent/Owner
Address
POBOX 3960 - 280 E FERNAU AVE
OSHKOSH
WI 54903 - 3960
--
Telephone Number
(920) 426-4252
v City of Oshkosh
Division of Inspection Services
P.O. Box 1130
Oshkosh, WI 54903-1130
Phone (920) 236-5050
Fax (920) 236-5084
REC E lYE D
MAR 1 0 2003
ELECTRICAL PERMI-P~mM1U)N
All information after bolœfli:l~Þr¥tJÐ[yaQP<MENT
Incomplete applications will not be processed.
~
OfHKOfH
ON THE WATER
. Application(s) and fee(s) can be brought to City Hall, Room 205 or mailed to Inspection Services, PO Box 1128,
Oshkosh WI 54903-1128. Commencing work without permìt(s) will result in fees being doubled or $100.00 plus the
normal permit fee, which ever is greater.
OR
If vou are a contractor varticžvatinf! in the Permit Fee Account Svstem and have adequate funds. check here
if VOli want this vrocessed throllf!h your account 0
DATE
JOB ADDRESS '3 ::.)56 m ó5e /t!' ð Sh¿5 Þ-¡
OWNER_ßr:)n 1"'1 el!: jJ,qL/t!!:A!:,'J/;"
CONTRACTOR /9-¿L¿;J4/ £¿eC-f-~/~
CHECK 0 ALL APPLICABLE
USE CATEGORY
. . .
DSingle Family DDuplex
.
DMulti-Famil)'
DRental
0 Commercial
SERVICE DNew
DChange
DTemporary
DNot Applicable
TYPE DOverhead
DUnderground
FILL IN THE APPROPRIATE BLANK WITH THE NUMBER
Voltsj/¡¡ô / ó?77
Phase .3
Amps ~i')
/
Receptacles #
Circuits #
Switches #
Fixtures #
CHECK 0 ALL APPLICABLE
DRange
DFan OR Blower
DMotors
DDishwasher
DFurnace
DGas Pumps
DGarbage Disposal
DAIC
0 Other
DDryer DWaterHeater
DElectric Sign
DESCRIPTION OF ALL WORK BEING DONE
sr- 7.- ð3
J;?Industrial
DNot Applicable
/<f'
VALUE (Including labor and all materials including light fixtures) $
".-a
/CJ/ ðcJð
MASTER ELECTRICIAN
/?/A"e :5~ ~t!'A!:.s;
3/02
fÎiIIt.. j commerce.wí.gov
~ i!~g n~jJ:!
LOF7
>,
, ~"
Safety and Buildings
t41 NW BARSTOW ST FL 4TH
WAUKESHA WI 53188-3789
TOO #: (608) 264-8777
www.commerce.wi.gov/sb/
www.wisconsin.gov
Jim Doyle, Governor
Mary P. Burke. Secretary
July 18. 2005
JUL 2 5 2005
CUST ID No. 993852
Fee Required $
Fee Received $
Balance Due $
250.00
250.00
0.00
JIM MARTIN
WISCONSIN PUBLIC SERVICE CORP
3300 N MAIN ST
OSHKOSH WI 54901
WfSMART code: 7631
REQUEST FOR ADDITIONAL INFORMATION
SITE:
Banner Packaging
3550 Moser St
City of Oshkosh, 54901
; Fire Dept ID: 7003
FOR:
No Objects for this Transaction
Identification Numbers
Transaction ill No. 1140370
Site ill No. 584936
Please refer to both identification numbers. above,
in all corresnondence with the agency.
The submittal described above has been placed on HOLD and the review and approval is pending subject to receipt
of the ADDITIONAL INFORMATION and/or revised plans requested by this letter. Upon receipt of the additional
information and/or revised plans. the plans will be reviewed for compliance to applicable Wisconsin Administrative
Codes and Wisconsin Statutes.
The following must be corrected/revised and accompany the resubmittal:
My understanding is that you have applied for a petition for variance in order to resolve a conflict with the City of
Oshkosh. According to City officials, the work done by WPS at Banner Packaging was done without a City of
Oshkosh electrical!icense, permit and the cables were buried without inspection by the local electrical inspector. My
understanding is customer owns the c.onductors and distribution equipment. For this reason the installation is covered
by the Scope of Comm 16 and should have been installed to meet the requirements of Comm 16 and the 2002 edition
of the National Electric Code.
A petition on the type of cable used is only appropriate if you can establish an equivalency between the cable used
for the installation at Banner Packaging and the type of cable required by the Code. The National Electric Code
requires the use of Type MV cable for this type of installation. Type MV cahle is covered by Article 328 in the 2002
NEC. You have submitted copies of pages from the WPS cable purchasing specifications. No background
information on the cable actually used on the job or comparison with approved cables was included.
Please submit a complete comp'arison which includes cable specifications for the actual type of cable used on the
project. This type of information is commonly available through the cable manufacturer. Your report shall compare
the construction of the type of cable used to the applicable requirements for the manufacture of listed type MV cable.
Type MV Cable is listed to UL 1072, Medium Voltage Power Cable. A competent professional engineer should do
the comparison. Presumably the comparison will be favorable and will form the basis for establishing an equivalency
between the technical requirements of the National Electric Code and the cable you elected to use.
The City of Oshkosh has requested our assistance is determining the adequacy of the installation. This request came
as part of their response in completing the Municipal Building Inspection Recommendation form. This is a separate
issue from the cable insulation issue. You did submit a copy of the WPS cable burial depth specifications. No details
were provided on the actual burial depth at Banner Packaging and any type of supplemental protection used. No
details were submitted that indicate what type of post-installation testing WPS performed to verify the insulation
'r"
JIM MARTIN
Page 2
7118/2005
integrity. Please submit a separate report from your construction crew. Please provide details on: 1) the burial depth;
2) the relationship of burial depth to finished grade at the time of installation; 3) supplemental protection for the
cables. if any; 4) the type of backfill; 5) the details on the type and methods used to terminate the cables at the
terminals of the distribution equipment; 6) and copies of any test reports such as DC High-pot or In-line partial
discharge. Other relevant infonnation may be submitted if you think it builds the case for City acceptance of an
installation that was not inspected.
Send your resubmittal into the address listed above, unless otherwise noted, and the department will review the
resubmittal within 5 working days of receipt date. Please include a copy of this letter with your resubmittal.
If you have any questions, after reading the above COmments and related code sections cited. please call me at the
telephone number below. If the above requested information and/or plans are not received within 30 business days
of the date of this correspondence. this submittal will be returned denied. No fees will be refunded. and a new fee.
application form, and submittal of plans/specifications will be required should you desire to continue with this
project. The code in effect at the time of new submittal would apply.
Sincerely,
-;/- I /7
/1f{f)~ J^ (:;?~
Thomas J Gl y. P.E. V
Electrical Engineer. Integrated Services
(414)852-3696.
tgarvey@commerce.state.wi.us