HomeMy WebLinkAboutHVAC (duct work) F2-2536-0908-H~~I~J / n
ON THE WATER
October 8, 2008
Michael Hams
Merwin Heating
PO Box 68
Fond du Lac, WI 54936-0065
Ron Detjen
Osh Inc
PO Box 2366
Oshkosh, WI 54903
Site:
Impro Med Inc
304 Ohio St.
Oshkosh WI 54902
Plan Number: F2-2536-0908-H
For:
Description: HVAC ductwork on North portion of Building
Object Type: HVAC only
Class of Construction: ITIB - 7680 Sq Ft.; Unsprinklered
Occupancy: B: Business Office , S: Storage
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Per discussion with Designer on 10/8/08 the following revisions or modification will be made to address issues
identified in plan review:
1. Additional return air transfer grills will be added to balance air from RTU being supplied to the
rooms off the corridor.
2. An additional supply diffuser from RTU-4 providing 300cfm will be provided in the corridor.
3. RTU identified as RTU-6 is actually RTU-5, and the unidentified RTU is RTU-6.
Key Item(s) /Conditions:
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
~:'~.~J3~7t,tj:i)?'.~',~'i.~n i2eti~ie.ti'~.Ccan=rer~•ial 1',i3~ itevi.u~'_OE)';`~.~^-253b-~ ,ng_;i. =04 Cllti<~ St Ti~~.~,t ~ t~nl;~.ciF.c
Page 1 of 2
SUBMIT:
• IMC 403.3.4 Balancing. Ventilation systems shall be balanced by an approved method. Such
balancing shall verify that the ventilation system is capable of supplying the airflow rates required by
Section 403. Balancing report required to be submitted prior to final occupancy being allowed.
• Comm 61.40 (4) Supervision. Prior to the initial occupancy of a new building or addition and prior to the
final occupancy of an alteration of an existing building the supervising professional shall file a compliance
statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence maybe made to me at the number listed below or the address on this letterhead.
Respec 1
rian oe
Building Systems Consultant
(920) 236-5051 Monday -Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $ 320.00
Fee Received $ 320.00
Balance Due $ 0.00
`~i~:;~eci~+a,-s'~!'IanRe.~ie«~~.Ca~7~-~~~~ia! 3~'i,tn i?~~ci~~;-^ttU~i`.F"_ ~i,i6-~`3p8-il ;ti4(3his:3 fit' (I~~,~i~ ~:~~>>1s.<I<;c
Page 2 of 2