HomeMy WebLinkAboutKitchen Exhause Hood E4-2504-0908~~I~~..tJ fl
ON THE WATER
September 24, 2008
Paul Sobieck
Temperature Systems Inc.
2200 South Ashland Ave.
Green Bay, WI 54304
Leonard Schmick
1635 W 20`~ Ave.
Oshkosh, WI 54902
Site:
Subway -Mama DeLuca's
1635 W 20~ Ave.
Oshkosh WI 54902
For:
Description: Kitchen exhaust hood system.
Object Type: Kitchen Hood Only
Plan Number: E4-2504-0908
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) /Conditions:
~ IBC 906.1 /IFC 904.11.5 Portable fire extinguisher must be located within 30 feet of travel distance of a
commercial-type cooking equipment. Per IFC 906.4 Fire extinguishers provided for the protection of
cooking grease fires shall be compatible with the automatic fire extinguishing system agent in accordance
with section 904.11.5. Verify that the required portable fire extinguisher is installed as required by
these code sections due to cooking equipment being installed.
• IBC [F] 904.11.2 System interconnection. The actuation of the fire suppression system shall
automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and
electrical supply reset shall be manual.
• IMC 507.2.1.1 Operation. Type I hood systems shall be designed and installed to automatically
activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall
occur through an interlock with the cooking appliances, by means of heat sensors or by means of other
approved methods.
• IFGC 505.1.1 Commercial cooking appliances vented by exhaust hoods. Where commercial
cooking appliances are vented by means of the Type I or II kitchen exhaust hood system that serves
such appliances, the exhaust system shall be fan powered and the appliances shall be interlocked with
the exhaust hood system to prevent appliance operation when the exhaust hood system is not
operating. Where a solenoid valve is installed in the gas piping as part of an interlock system, gas
piping shall not be installed to bypass such valve. Dampers shall not be installed in the exhaust system.
I:Iiz~.~e~;i~i~:~s1P(an 12es•irtie'•.C'omr^e+'riaJ P;ni i2es ir:ti~ "'.tr!i~`(~>4-2z~t-t-f,'f~Q$ 163 L~' =f?t(~ .a;e. fCi°;:I~c~;~ I (ne;ei Or;(v.<!c>c
Page 1 of 2
• IMC 506.3.10 Grease duct enclosure.
Exceptions: 1. The shaft enclosure provisions of this section shall not be required where a duct
penetration is protected with athrough-penetration firestop system classified in accordance with
ASTM E 814 and having an "F" and "T" rating equal to the fire-resistance rating of the assembly
being penetrated and where the surface of the duct is continuously covered on all sides from the point
at which the duct penetrates a ceiling, wall or floor to the outlet terminal with a classified and labeled
material, system, method of construction or product specifically evaluated for such purpose, in
accordance with ASTM E 2336. Exposed ductwrap systems shall be protected where subject to
physical damage. Be Aware that with the adoption of the 2006 IMC and this code referencing
ASTMS 2336, many duct wrap systems now require two layers to meet the allow for reduced
clearance to combustibles.
• 507.12 Canopy size and location. The inside lower edge of canopy-type Type I and II commercial
hoods shall overhang or extend a horizontal distance of not less than 6 inches (152 mm) beyond the
edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the
front lower lip of the hood and such surface shall not exceed 4 feet (1219mm). Plans submitted do
not include cooking equipment and hood layout Verify that the required overhang will exist when
equipment is placed under the hood.
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
SUBMIT:
• Prior to installation provide cut sheets for grease duct wrap being used to reduce clearance to combustibles
• Prior to installation provide additional information detailing how exhaust and make-up air, cooking
equipment, and fire suppression system will be interlocked as required by the above reference code section.
• Comm 61.50 (4) Supervision. Prior to the initial occupancy of an alteration the supervising professional
shall file a compliance statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence maybe made to me at the number listed below or the address on this letterhead.
Respectfull ,
Fee Required $ 230.00
an No Fee Received $ 230.00
Building Systems Consultant Balance Due $ 0.00
(920) 236-5051 Monday -Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
t -c;i; s~-i~'ia?a Rec•ie.:-'•C'r?m~mc:~t°ttt; I?:ai~ I2e~ :ri~• "_Qu;'}-,d_2jC~-E-ti&i:$ i(;3 It"'ntl~ dz?. {:itcl~Ea~ tfi~~sti CJ°,(i-_dc~r
Page 2 of 2
Fire Barrier Duct Wrap 15A
Duct Wrap Fire Protection Systems for Commercial Kitchen Grease and Chemical Exhaust
Fume Ducts ttiir~F~ ~tiSIF~ ~'~~ poi Complies with Com lies with
~+' ~O ~-" ~~ o~~a 3 NFPA 96 0
n ~~ ~~ ~ ~r ~~ Compliance ~ntemaNonal Standard
Y ` ~ a i Tsse Edition Mechenlcel Code Mechenlcal Code
~~RATOP w...u..n.v,a,.n ,.
enrrsumar~is
fUl1 USEMFYrt PFSISiNE [pIGT ASSEAeLIES oucrwxaPMarERw.;
FqI USE WIFNU:Cf4PE5S1RdiICN complan~•
052161 Report 2132A
SEE lII UfIEf.H7RY.".f PRUWICIS fRESiUP SYSTEMS
LER~2RF5tSTAfI~CF D~IRE~CTpiY~f~
P
d
t D
t ~
N
L F
~
~k 0
S
~
ro
uc
a
a ASI
1
lURY
U
RE
ANC
EC
9W9
1. Product Description
3MT"" Fire Barrier Duct Wrap 15A is a fire resistant wrap
consisting of a patented inorganic blanket encapsulated
with ascrim-reinforced foil. It is used to fire rate com-
mercial kitchen grease ducts and is a proven alternative
to 1 or 2 hour fire resistant rated shaft enclosures. This
mold resistant**, non-absestos wrap contains a safer
fiber construction" and installs easily because of its high
flexibilty and strength. 3M Fire Barrier Duct Wrap 15A is
a single layer fire resistant wrap that has passed the
UL1978 test which simulates a grease duct fire. With its
excellent insulating capabilities, it is an ideal choice for
tight spaces because it protects combustible construc-
tions at zero clearance throughout the entire enclosure
system. 3M Fire Barrier 1000 N/S, 1003 S/L and 2000+
Silicone Sealants used in combination 3M Fire Barrier
Duct Wrap 15A provide an effective firestop when the
duct penetrates fire rated walls and floors.
Features
• One layer wrap for grease ducts rated as a shaft alter-
native per UL 1978
. Zero clearance to combustible throughout the entire
enclosure system for congested spaces
. High flexibility for installation ease
• Foil encapsulated with unique center overlap seam for
blanket protection, less dust, and high wrap strength
. Widest range of penetration seal systems
. Stitched edges
• Safer fiber construction*
. Mold resistant in accordance with ASTM 01338-00" "`
`Has been demonstrated to be soluble in the lungs according to EU
guidelines 67/548/EWG, Note Q for bio persistence.
"Standard Test Method for Determining Fungi Resistance of
Insulation Materials and Facings
2. Applications
3M Fire Barrier Duct Wrap 15A is an ideal fire
resistive enclosure for commercial kitchen grease ducts.
It is a proven performance alternative to a 1 or 2 hour
fire resistant rated shaft enclosures and provides zero
clearance to combustible construction throughout the
entire enclosure system. 3M Fire Barrier 1000 N/S,
1003 S/L or 2000+ Silicone Sealant is used in combina-
tion with 3M Fire Barrier Duct Wrap 15A to firestop the
duct when the duct penetrates fire rated floors and walls.
4. Typical Physical Properties
Blanket Color: gray/green
Weight: 1.38 lbs./sq. ft. (6.73 kg/sq. m)
5. Pertormance
3M Fire Barrier Duct Wrap 15A has been tested in
accordance with the following:
ASTM C 411 ASTM C 1338
ASTM C 518 ASTM E 136
ASTM E 84 ASTM E 814
ASTM E 119 UL 1978 (Sections 12 & 13)
Surface Burning Characteristics (ASTM E 84)
Foil Encapsulated Blanket:
Flame Spread: 0
Smoke Developed: 0
Blanket:
Flame Spread: 0
Smoke Developed: 0
Thermal Conductivity
Temperature °F (°C) btu•inJ(hr.•fN•F)
500 (260) 0.417
1000 (537) 0.922
1500 (815) 1.69
1800 (982) 2.27
For technical data and properties of 3M Fire Barrier
1000 N/S, 1003 S/L and 2000+ Silicone Sealants see
separate product data sheets available from your 3M
representative or go to www.3m.com/firestop.
Grease Duct Listings
ve nc osure ys em me a om a . es n os.
Resistive Duct System Through-
Rating Penetration
System
1 or 2 hours 1 layer of 3M Fire Barrier GD 532 F 15A FS 557 W
Duct Wrap 15A , 3 in. GD 538 F 15A FS 558 F
(76 mm) perimeter and GD 547 F 15A FS 559 W
longitudinal overlaps GD 548 F 15A FS 560 F
GD 549 F 15A FS 561 F
GD 556 F 15A FS 562 W
GD 557 F 15A FS 563 W
FS 578 F
FS 579 W
3. Availability
Product Unit Size Units/ Wt./
ctn. ctn.
3M fire Barrier Roll 1.5 in.x 24 in. x 20 ft. 1 53 lbs.
Duct Wrap 15A (38mm x 60,9cm x 609 cm) 24 kg
3M fire Barrier Roll 1.5 in. x 48 in. x 20 ft. 1 106 lbs.
Duct Wrap 15A (38mm x t 2t cm x 609 cm) 48 kg
Chemical Exhaust Fume Duct
Resistive ( I Duci System I Through-
Rating Penetration
or z Hours 7 layer of sm rare tiarner cru5uur ~or+ rs ao~ uv ioH
Duct Wrap 15A , 3 in. CFD501 F 15A FS 558 F 15A
(76 mm) perimeter and FS 559 W 15A
longitudinal overlaps FS 560 F 15A
FS 561 F 15A
FS 562 W 15A
FS 563 W 15A
FS 578 F 15A
FS 579 F 15A
Product Approvals
Product Approvals
ICC ES Compliance Legacy Report 2161
ICC ES Compliance Legacy Report 2132A
New York City MEA; 147-01-M
California State Fre Marshall; 2440-0941:110
Code Compliance
3M Fire Barrier Duct Wrap 15A complies with
requirements of the following codes:
NFPA 96, 1998 Edition
1997 Standard Mechanical Code
1998/2000 International Mechanical Code
1999 BOCA National Building Code
1999 Standard Building Code
This is only a partial list of code compliance. For the
latest code and approval information go to
www.3m.com/firestop or speak to your authorized 3M
distributor or sales representative at (800) 328-1687.
6. Installation Techniques
3M Fire Barrier Duct Wrap 15A system should be
installed in accordance with the following installation
instructions.
Material and Equipment
• 3M Fire Barrier Duct Wrap 15A blanket, 1-112 in.
(38 mm) thick, 24 in. (60 cm) or 48 in. (121 cm) wide,
20 ft. (609 cm) standard length. The 48 in. (121 cm)
wide blanket helps to minimize waste.
. Aluminum foil tape.
. Minimum 3/4 in. (19 mm) wide filament tape.
• Carbon steel or stainless steel banding material,
minimum 1/2 in. (12,7 mm) wide, minimum 0.015 in.
(0,38 mm) thick, with steel banding clips.
. Hand banding tensioner, crimping tool, and banding
cutter.
. Minimum 12 gauge copper-coated steel insulation
pins; galvanized steel or stainless speed clips,
minimum
1-1/2 in. (38 mm) square or 1-1/2 in. (38 mm) dia.
round, or equivalent sized insulated cup-head pins;
capacitor discharge stud gun.
. Access door hardware: four galvanized steel thread
rods, 1/4 in. (6 mm) diameter by 4-1/2 in. to 5 in. long
(114 mm to 127 mm) with 1/4 in. (6 mm) wing nuts
and 1/4 in. (6 mm) washers: 4 in. (102 mm) long
steel hollow tubing to fit threaded rods.
. Minimum 4.0 Ib. (1,8 kg) density mineral wool or
scrap pieces of 3M Fire Barrier Duct Wrap 15A.
• 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+
Silicone Sealant.
Storage: The 3M Fire Barrier Duct Wrap 15A and 3M
Fire Barrier 1000 N/S, 1003 S/L and 2000+ Silicone
Sealants must be stored in a dry warehouse
environment. Pallets should not be stacked.
Preparatory Work: 3M Fire Barrier Duct Wrap 15A is
installed with common tools, such as knives, handers
and capacitor discharge guns for applying insulation
pins. In order to install the duct firestop system, the
surfaces of all the openings and penetrating items need
to be clean, dry, frost free and free of dust.
Method: To minimize waste, 3M Fire Barrier Duct
Wrap 15A material should be rolled out tautly before
measuring. General instructions for installing the 3M
Fire Barrier Duct Wrap 15A include aone-layer wrap
construction applied directly to the duct. The 3M Fire
Barrier Duct Wrap 15A blanket is wrapped around the
perimeter of the duct and is cut to a length to overlap
itself not less than 3 in. (76 mm). The overlap made by
adjacent blankets forms the "longitudinal" overlap.
Aluminum foil tape is used to seal all cut edges of the
blanket and any tears in the foil scrim.
There are three (3) approved installation
techniques for installing the 3M Fire Barrier Duct
Wrap 15A (See Figure 1):
1. Telescoping 3 in. (76 mm) Overlap Wrap
With the telescoping overlap wrap method, each
blanket overlaps one adjacent blanket, and each
blanket has one edge exposed and one edge covered
by the next blanket as shown in Figure 1. The visible
edges of the perimeter overlaps all point in the same
direction.
2. Checkerboard 3 in. (76 mm) Overlap Wrap
With the 3 in. (76 mm) checkerboard overlap wrap
method, blankets with both edges exposed alternate
with blankets with covered edges, as shown in Figure
1. The visible edges of the perimeter overlaps
alternate their directions and appear on every other
blanket.
3. Butt Joint With Collar
With the butt joint and collar method, adjacent
blankets are butted tightly together and 6 in. (152 mm)
wide collar of 3M Fire Barrier Duct Wrap is centered
over the joint, overlapping each blanket by 3 in.
(76 mm) minimum as shown in Figure 1.
In all three overlap techniques the perimeter overlap
can occur at any location on the duct.
The blanket is mechanically attached to the duct by
steel banding or by welded insulation pins and clips for
all three installation methods listed above.
For Banding Only (See Figure 1)
Filament tape can be used to temporarily hold the blan-
ket in place until the banding is applied. The steel
banding is applied around the duct 1-1/2 in. (38 mm)
from each edge of the blanket, and maximum
10-1/2 in. (26,7 cm) centers. The banding is placed
around the material and tightened so as to sufficiently
hold the 3M Fire Barrier Duct Wrap 15A in place
against the duct, compressing the foil but not cutting
the foil.
Additional Pinning to Prevent Sagging of the Wrap:
For Ducts 24 in. (60 cm) and larger in width,
additional pins are needed to support the blanket on
the bottom horizontal surface and on the outside face
of a vertical duct run. Space pins a maximum of
10-1/2 in. (26,7 cm) apart in the direction of the
blanket width, and a maximum of 12 in. (30 cm) apart
in the direction of the blanket length. Refer to
paragraph below for more information on Mechanical
Fastening with Pins.
For Mechanical Fastening with Pins Only
Insulation pins are welded to the duct in the centers of
the overlaps a minimum of 1-1/2 in. (38 mm) from each
edge of the blanket, and spaced a maximum of 10-1/2
in. (26,7 cm) on center along perimeter
overlap, and a maximum of 10-1/2 in. (26,7 mm) on
center along longitudinal overlaps. The blanket is
impaled over the pins and held in place by galvanized
speed clips. Insulation pins that extend beyond the
blanket wrap shall be turned down to eliminate sharp
points. Insulated cup-head pins can be used at the
same spacing requirements of the insulation pins.
NOTE: Support hangar systems do not need to be
wrapped provided the hangar rods are at least a
minimum of 3/8 in. (9,53 mm) diameter and spaced a
maximum of 60 in. (152 cm) on center along the length
of the duct. Use a minimum 2 in. x 2 in. x 1/4 in.
(50 mm x 50 mm x 6,35 mm) steel angle steel support
channel or SMACNA equivalent support system.
Access Door Installation (See Figure 2)
Four galvanized steel threaded rods, 1/4 in. diameter
(6,35 mm) by 4-1/2 in. to 5 in. long (114 mm to
127 mm) are welded to the duct at the corners of the
door opening. Four steel tubes, each 3 in. (76 mm)
long, are placed over the rods to act as protection for
the 3M Fire Barrier Duct Wrap 15A when fastening the
door. Four insulation pins are welded to the door panel
for installation of the blanket. One layer of 3M Fire
Barrier Duct Wrap 15A is cut approximately the same
size as the access panel and impaled over the insula-
tion pins on the panel. It is essential that this layer fit
tightly against the wrap surrounding the access door
opening with no through openings. A second layer of
3M Fire Barrier Duct Wrap 15A is cut so as to overlap
the first layer by a minimum of 1 in. (25,4 mm). The
second layer is impaled over the pins and both layers
are locked in place with galvanized speed clips. Pins
that extend beyond the outer layer of 3M Fire Barrier
Duct Wrap 15A shall be turned down to avoid sharp
points on the door.
The insulated door panel is placed over the threaded
rods and held in place with washers and wing nuts.
The details are shown in Figure 2.
Penetrations (See Figure 3)
When the duct penetrates a fire rated wall, ceiling or
floor, an approved firestop system must be employed.
Figure 3 illustrates a typical condition.
To firestop the wrapped duct, follow the installation
parameters detailed in the following Omega Point
Laboratories, Inc. systems:
FS 557 W, FS 558 F, FS 559 W, FS 560 F, FS 561 F,
FS 562 W, FS 563 W, FS 578 F, FS 579 W.
Other Applications
More details on the installation of the product can
be found in the 3M Product Data and Installation
Instruction Manual (98-0400-5054-8).
7. Maintenance
No maintenance is required when installed in
accordance with the 3M Installation Instructions. Once
installed, if any section of the 3M Fire Barrier Duct
Wrap 15A is damaged so that the blanket is damaged,
Figure 1
3M Fire Barrier Duct Wrap 15A Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Telescoping Wrap Technique With Banding For Ducts 24 inches (60,9 cm) or Less
Telescoping Overlap Wrap Option
Cross Sectional View
3" (76 mm) , 3" (76 mm)
t-t/2" (38 mm)' ~ I t-7/2" (38 mm)
~. ~ (~ }I--hI-I{--
\~\ ~ 21" (53,3 cm) Typ.
``!1
Checkerboard Overlap Wrap Option
Cross Sectional View
t-1/<^" (38 mm)~-y ..(~_~ 1-7/2" (38 mm)
~--~-. ~- -L l~~
\ 21" (53,3 cm) Typ.
~~ \ ~`t
Fes- ~
Butt Joint With Collar Option
Cross Sectional View
1. One Layer 3M Fire Barrier Duct Wrap 15A
2. Steel Banding 1/2 in. (13 mm) Wide Min. Typical
3. 3 in. (76 mm) Min. Lon itudinal Overla
4. 3 in. (76 mm) Min. Perimeter Overlap
System integrity is limited by quality of installation.
6" (152 mm)
3" (76 mm)~~
1-1/2" (38 mm I t-t/2" (38 mm)
t U...........t.\' ~
,~ -~-,
6
the following procedures will apply:
. The damaged section should be removed by cutting
the steel banding or removing the clips holding it in
place.
. Anew section of the same dimension should be cut
from a roll of 3M Fire Barrier Duct Wrap 15A, either
24 in. (60,9 cm) or 48 in. (121 cm) wide.
. The new section should be placed and fitted
ensuring the same overlap that existed previously.
. The steel banding should be placed around the
material and tensioned so as to sufficiently hold the
3M Fire Barrier Duct Wrap 15A in place.
or
e0
r
s
is
1. Access Hole
2. 1/4 in. (6 mm) Dia. All Threaded Rods
3. Access Cover - 16 Gau e
4. Insulation Pins -Welded
5. First Layer 3M Fire Barrier Duct Wrap 15A Cut
Same Size As Cover
6. Second Layer 3M Fire Barrier Duct Wrap 15A
with 1 in. (25mm) Overlap On All Sides
7. Speed Clips
8. Aluminum Tape Covering All Exposed Edges
9. S ool Pieces For Threaded Rods
10. 1/4 in. (6mm) Diameter Wing Nuts
System integrity is limited by quality of installation.
. If the blanket has not been damaged but the foil has
ripped, seal the rips with aluminum foil tape.
8. Purchase Information
3M Fire Barrier products are available through a
network of nationwide distributors. For information on
where to buy, go to www.3m.com/firestop.
9. Safe Handling Information
Consult Material Safety Data Sheet prior to
handling and disposing of 3M Fire Barrier Duct
Wrap 15A.
mm)
mm)
1. Floor/Ceilin or Wall Assembl
2. Duct
3A. One La er 3M Fire Barrier Duct Wra 15A
38 Bandin or Pinnin
3C. Packin Material
3D. 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+
Silicone Sealant For Wall Assembly Apply
Sealant To Both Sides of Wall
System integrity is limited by quality of installation.
Warranty and Limited Remedv. This product will be free from defects in material and manufacture for a period of ninety (90) days from date of
purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OR MERCHANTIBILITY OR
FITNESS FOR A PARTICULAR PURPOSE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable
for user's method of application. If this 3M product is proved to be defective within the warranty period stated above, your exclusive remedy and
3M's sole obligation shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the product.
Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damages arising from the use of this 3M prod-
uct, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including
warranty, contract, negligence or strict liability.
~~`
]Building Safety Solutions Department
3M Center 223-2S-24
St. Paul, MN 55144-1000 Printed in U.S.A.
Phone 800-328-1687 Bolger 6080547
® 3M 2006 98-0400-5066-2 (Aug. 2006)
Fax 888-362-2737
www.3m.com/firestop
Figure 2
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Access Door System
Figure 3
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Through Penetration Systems
4-1/2 inch (11,4 cm) Concrete Floor or Wall