HomeMy WebLinkAboutHVAC & Bldg C3-2337-0408-R-HW f11~.~./ ~l
ON THE WATER
August 27, 2008
Doug Elsbury
OPN Architects Inc
200 5`s Ave Suite 201
Cedar Rapids IA 52401-1810
Kristine Beyer
Biolife Plasma Services
101 Lake Pointe Drive
Oshkosh, WI 54904-1130
Site:
Biolife Plasma Services
101 Lake Pointe Drive
Oshkosh WI 54904
For:
Michael Zager
100 Camelot Dr
Fond du Lac, WI 54935
Plan Number: C3-2337-0408-R-H
Description: Tenant space alterations
Object Type: Building Revisions and HVAC
Class of Construction: VB -12180 Sq Ft.; Unsprinklered
Occupancy: B: Business /Office
Maximum No of Occupants: 122
City of Oshkosh
Division of Inspection Services
215 Church Avenue
PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
NOTE: All conditions of the original plan approval still apply. This review only covers revisions shown on revised
sheet All, SD-4 and HVAC plans.
Key Item(s) /Conditions:
• NEC 110.26 Spaces About Electrical Equipment. Sufficient access and working space shall be
provided and maintained about all electric equipment to permit ready and safe operation and maintenance
of such equipment. Verify that the appropriate clearances required by this section are being maintained
around all HVAC equipment including VAV's above corridor 126 that is having a hard ceiling
installed below these units.
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
T: .Utsn~it iins.T'181) (ZC:'ICL\'.C'Ultl!!?CpCiFil Viii tZC4'Jetic~^ftu'~ { z-23z"-tl-tU3 101 i~tke T't~int t7ri~e Ret'is?+it~ CSI,c~•~L (It':1C'.~Ioc
Page 1 of 2
SUBMIT:
• IMC 403.3.4 Balancing. Ventilation systems shall be balanced by an approved method. Such
balancing shall verify that the ventilation system is capable of supplying the airflow rates required by
Section 403. Balancing report required to be submitted prior to final occupancy being allowed.
Comm 61.40 (4) Supervision. Prior to the initial occupancy of a new building or addition and prior to the
final occupancy of an alteration of an existing building the supervising professional shall file a compliance
statement form SBD-9720 with this office.
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require. changes or
additions should conditions arise making them necessary for code compliance. As per state.stats 101.:12(2),, nothing in.this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence maybe made to me at the number listed below or the address on this letterhead.
Respec ,
rian Noe
Building Systems Consultant
(920) 236-5051 Monday -Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $
Fee Received $
Balance Due $
490.00
490.00
0.00
l:`.{n.neciiu,~s`.Pla~i 17eti~ies:•':c~'on2r-~enial Pi,3n Rrv?ew ^_p{i~',C'?_7 3'-ti-t(13 it}I (,ii;e Point [hire iZrt~isiu~~ (S~iig cC I11-':~C'.c1<:sc