HomeMy WebLinkAbout2008-HVAC D9-2488-080801HKQIH
ON THE WATER
August 14, 2008
Brad Noah
Temperature Systems Inc
P.O. Box 12088
Green Bay, WI 54307-2088
Tod-Mar
434 Main St.
Oshkosh, WI 54901
Site:
Stolley Photography
436 N Main St
Oshkosh WI 54901
For:
Description: Tenant space alterations
Object Type: HVAC only
Occupancy: M: Mercantile /Retail
City of Oshkosh
Division of Inspection Services
215 Church Avenue
', PO Box 1130
Oshkosh WI 54903-1130
www.ci.oshkosh.wi.us
', Plan Number: D9-2488-0808
The submittal described above has been reviewed for conformance with applicable Wisconsin Administrative Codes and
Wisconsin Statutes. The submittal has been CONDITIONALLY APPROVED. The owner, as defined in Chapter
101.01(10), Wisconsin Statutes, is responsible for compliance with all code requirements
Key Item(s) /Conditions:
• IMC 307.1 Liquid combustion by-products of condensing appliances shall be collected and discharged to
an approved plumbing fixture or disposal area.
• IMC 401.4.1 Intake openings. Mechanical and gravity outdoor air intake openings shall be located a
minimum of 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such
as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks, except as otherwise
specified in this code. Where a source of contaminant is located within 10 feet (3048 mm) horizontally
of an intake opening, such opening shall be located a minimum of 2 feet (610 mm) below the
contaminant source. Caution on location of fresh air intake along parking lot /alley.
Comm 61.31(4) Revisions to approved plans. All proposed revisions and modifications which involve
rules under this code and which are made to construction documents that have previously been granted
approval by the department or its authorized representative, shall be submitted to the office that granted the
approval. All revisions and modifications to plans shall be approved in writing by the department or its
authorized representative prior to the work involved in the revision or modification being carried out. A
revision or modification to a plan, drawing or specification shall be signed and sealed in accordance with
Comm 61.31(1).
1:`;ifiis~+et~,;ol.s`.I'lan 12ei~irw.'•.C'!?!3)-e:'t!<t? I'!:sn i<eti;e41'.^_(1,)~;'..I)'i-^_~i?~;-(tgQR.;j.:'y ~.tain S~ lif'.~('t)rh~.<1c~~
Page 1 of 2
SUBMIT:
• IMC 403.3.4 Balancing. Ventilation systems shall be balanced by an approved method. Such
balancing shall verify that the ventilation system is capable of supplying the airflow rates required by
Section 403. Balancing report required to be submitted prior to final occupancy being allowed.
• Comm 61.40 (4) Supervision. Prior to the initial occupancy of a new building or addition and prior to the
final occupancy of an alteration of an existing building the supervising professional shall file a compliance,
statement form SBD-9720 with this office..
A copy of the approved plans, specifications, and this letter shall be on-site during construction. All permits are required to
be obtained prior to commencement of work.
In granting this approval the City of Oshkosh Inspection Services Department reserves the right to require changes or
additions should conditions arise making them necessary for code compliance. As per state stats 101.12(2), nothing in this
review shall relieve the designer of the responsibility for designing a safe building, structure, or component.
Inquiries concerning this correspondence maybe made to me at the number listed below or the address on this letterhead.
Resp ',
Brian Noe
Building Systems Consultant
(920) 236-5051 Monday -Friday 7:30 A.M. to 8:30 A.M and 12:30 A.M to 1:30 P.M.
bnoe@ci.oshkosh.wi.us
cc: Property file
Fee Required $ .230.00
Fee Received $ 230.00
Balance Due $ 0.00
?:`:hap~~ti~~ ~s11'(an Retiirv:'.C::`t,tn;;-.r~ia3 i',~n te~ieu• =Qu~':(.1i3-"_d6j-{t~{tg .i. - !4 ~yttrn Si 1lV.~' (:?-1t~.tioti
Page 2 of 2