Loading...
HomeMy WebLinkAboutFire Protection System Installation - 7/24/08201 Morris Court, P.O. Box 1316 ~. F. AHERN CO. Fond du Lac, WI 54936-1316 MECHANICAL & FIRE (920) 921-9020 p • (920) 921-8666 f PROTECTION CONTRACTORS WWW.Jfahern.com HERN July 24, 2008 Building Inspector -- Brian Noe City of Oshkosh 215 Church Avenue -- PO Box 11 Oshkosh, WI 54901 T-920/236-5051 F-920/236-1130 RE: FIRE PROTECTION ; HUNTER'S RIDGE #9 3200 ELK RIDGE OSHKOSH, WISCONSIN AHERN FIRE PROTECTI Dear Brian: Enclosed is a copy of the Fire Protection System Ir Very truly yours, AHERN FIRE PROTECTION A division of J. F. Ahern Co. Mark L. Jozefowski, MLJ/ksj Enclosure Z:\FIItE\411 DATA\490694\LCITY07-24-2008. DOC TALLATION 1 No. 490694 pr's Material and Test Certificates covering the above-referenced for vouri files. .., a ~, JUL 2 8 2008 ~..~~ la~.e~ ~~y. ~ ~~ _,~ s B th'e Midwest Since 1880 An Equal Opportunity Employer AHERN FIRE PROTECTION Contractor's Material and Test Certificate for Aboveground Piping PROCEDURE Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by the property owner or their authorized agent. All defects shall be corrected and system left in service before contractor's personnel finally leave the job. A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authori 's re uirements or local ordinances. PROPERTY NAME Hunter's Rid a Condominiums AFP Contract #: 490694 DATE: January 30, 2008 PROPERTY ADDR ESS 3200 Elk Ride Oshkosh, Wisconsin 54901 ACCEPTED BY APPROVING AUTHORITIES (NAMES) 1. Oshkosh Fire Department (Battalion Chief -- Stu Schrottky) 2. City of Oshkosh (Building Inspector -- Brian Noe) 3. State of Wisconsin -- Safety & Buildings 4. ADDRESS WI 54901 101 Court Street -- Oshkosh 1 Plans , . 2. 215 Church Avenue -- PO Box 1130 -- Oshkosh, WI 54901 3. 4. - ' INSTALLATION CONFORMS TO ACCEPTED PLANS YES ^ NO EQUIPMENT USED IS APPROVED YES ^ NO IF NO, EXPLAIN DEVIATIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ^ YES ^ NO OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? INSTRUCTIONS IF NO, EXPLAIN HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: Item No.'s 2 8 3 will 1. SYSTEM COMPONENTS INSTRUCTIONS ^ YES ^ NO ' be forwarded by AFP at closeout time 2 CARE AND MAINTENANCE INSTRUCTIONS ^ YES ^ NO . YES ^ NO 3. NFPA 25 ^ LOCATION OF SUPPLIES BUILDINGS SYSTEM Buildin #9 MAKE MODEL YEAR OF MANUFACTURE K- FACTOR QUANTITY TEMPERATURE RATING T to LF II TY2234 Res. Pendent 1/2" White 2007 4.9 62 155 De . Vikin Microfast QR VK300 Uri ht 1/2" Brass 2007 5.6 1 200 De . T CA LF II TY1334 Res. HSW 1/2" White 2007 4.2 2 155 De . SPRINKLERS PIPE AND TYPE OF PIPE Lightw all Non-Threadable~ Thinwa ll Threadable~ Black CPVC FITTINGS TYPE OF FITTINGS Grooved Threaded Mechanic al Tees: CPVC MAXIMUM TIME TO OPERATE FLOW ALARM DEVICE THROUGH TEST CONNECTION TYPE MAKE MODEL MINUTES SECONDS Water Flow Detector S stem Sensor WFD N/A EXPLAIN ANY ALARM PROBLEMS: ALARM DEVICES LOW AIR ALARM DEVICE RE TED ALA ~ TYPE MAKE MODE PRESSU - . S pROPERL Y N/A ~ P I '~ ,YES: NO EXPLAIN ANY ALARM PROBLEMS: JUL 2 S ZOOS ~;. re'` n f IlvsPtlrrl~r! s~RV~cFt; r, ~tYs?1;~ Ahern Fire Protection CENTRAL MONITORING LOCATION(S) SIGNALS RECEIVED ALARM SERVICE TYPE OR NAME OF REMOTE WATERFLOW PRESSURE LOW-AIR SERVICE DETECTOR SWITCH SUPERVISORY OTHER FLOW SUPERVISING LOCATION(S): STATION (ON-SITE) REMOTE NAME OF SERVICE: REMOTE MONITORING SERVICE ~ ~ L'('~'{'~-y~ SIGNAL NG (OFF-SITE) / - PHONE: OTHER: LOCATION(S): EXPLAIN ANY ALARM SIGNALING PROBLEMS: DRY VALVE Q.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. DRY PIPE TIME TO TRIP WATER TRIP POINT AIR TIME WATER ALARM OPERATING THROUGH TEST ' ° PRESSURE AIR PRESSURE PRESSURE REACHED TEST OPERATED TEST CONNECTION ' OUTLET°'° PROPERLY MIN. SEC. PSI PSI PSI MIN. SEC. YES NO WITHOUT O.O.D. WITH Q.O.D. IF NO, EXPLAIN: OPERATION: ^ PNEUMATIC ^ ELECTRIC ^ HYDRAULIC PIPING SUPERVISED ^ YES ^ NO DETECTING MEDIA SUPERVISED ^ YES ^ NO DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS? ^ YES ^ NO IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN DELUGE & CIRCUIT FOR TESTING? PREACTION ^ YES ^ NO VALVES DOES EACH CIRCUIT DOES EACH CIRCUIT OPERATE SUPERVISION OPERATE VALVE MAXIMUM TIME TO MAKE MODEL LOSS ALARM? RELEASE? OPERATE RELEASE YES NO YES NO MINUTES SECONDS LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE PRESSURE FLOOR (FLOWING) REDUCING INLET OUTLET INLET OUTLET FLOW VALVE TEST PSI PSI PSI PSI GPM ° MEASURED FROM TIME INSPECTORS TEST CONNECTION IS OPENED. ° NFPA 13 ONLY REQUIRES THE 60-SECOND LIMITATION IN SPECIFIC SECTIONS. 2 Ahern Fire Protection HYDROSTATIC Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for two (2) hours or 50 psi (3.4 bar) above static pressure in excess of 150 psi (10.2 bar) for two (2) hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All TEST aboveground piping leakage shall be stopped. DESCRIPTION PNEUMATIC: Establish 40-psi (2.7 bar) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours. ALL PIPING HYDROSTATICALLY TESTED AT PSI (,_Bar) for HRS. IF NO, STATE REASON DRY PIPING PNEUMATICALLY TESTED ^ YES ^ NO EQUIPMENT OPERATES PROPERLY ^ YES ^ NO DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM SILICATE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR STOPPING LEAKS? YES ^ NO DRAIN READING OF GAUGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST TEST SUPPLY TEST CONNECTION:~ PSI ( Bar) CONNE _ ..__ CTION OPEN WIDE:(n~ pSl (_Bar) TESTS UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER(S) TO OTHER EXPLAIN BE FLUSHED BEFORE CONNECTION MADE TO SPRINKLER P IPING. VERIFIED BY COPY OF THE CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING. ^ YES ^ NO FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING ^ YES ^ NO it I'UwDER-DRIVEN FASTENERS ARE USED IN CON CRETE, HAS REPRESENTATIVE SAMPLE TESTING BEEN SATISF IF NO, EXPLAIN ACTORILY COMPLETED? ^ YES ^ NO BLANK NUMBER USED LOCATIONS TESTING O NUMBER REMOVED GASKETS WELDED PIPING YES ^ NO IF YES... Do you certify as the sprinkler contractor that welding procedures used complied with the minimum regwrements of AWS B2.1, ASME Section IX Welding and Brazing Quaycations, or other applicable qualification standard as required by the AHJ? YES ^ NO WELDING with the m nlmumtrall uirem~ents of AWS B21, ASME Section~IX ~We/diner atnd Brazined in accordance 9 g Qualifications or oth li q '~ YES ^ NO , er app cable ualification standard as required by the AHJ? Do you certify that the welding was conducted incompliance with a documented quality control procedure to ensure that (1) all discs are retrieved; (2) that openings in piping are smooth that sla d , g completed wel ds are free from cracks,tln(COmp ete fusioln,~surface porposity greate~t man 1%1a6e ch4) ~y y'E' ' ES ^ NO n diameter, undercut deeper than the lesser of 25% of the wall thickness or 1/32 inch; and (5) completed circumferential butt weld reinforcement does not exceed 3/32 inch? CUTOUTS DO YOU CERTIFY THAT YOU HA DISCS) VE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS (DISCS ARE RETRIEVED? ES ^ NO HYDRAULIC NAMEPLATE PROVIDED DATA YES ^ NO IF NO, EXPLAIN NAMEPLATE REMARKS DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: ~ NAME OF SPRINKLER CONTRACTOR ~ °~ ~ _~~ AHERN FIRE PROTECTION, 201 MORRIS COURT -- FOND DU LAC, WI 54935 TESTS WITNESSED BY AUTHORITIES HAVING JURISDICTION (SIGNED) TITLE SIGNATURES DATE THE PROPERTY OWNER OR THEIR AUTHORIZED AGENT (SIGNED) TITLE DATE FOR SPRINKLER T CTOR (SIGNED) TITLE DATE ~ r=t'1'~k+~l ~~ ~7',~ ~' ADDITIONAL EXP NS N TES: ~-~ ~ ~ ~ 17 i ~~ .. -at ' 3