HomeMy WebLinkAboutFire Protection System Installation - 7/24/08201 Morris Court, P.O. Box 1316
~. F. AHERN CO. Fond du Lac, WI 54936-1316
MECHANICAL & FIRE (920) 921-9020 p • (920) 921-8666 f
PROTECTION CONTRACTORS WWW.Jfahern.com
HERN
July 24, 2008
Building Inspector -- Brian Noe
City of Oshkosh
215 Church Avenue -- PO Box 11
Oshkosh, WI 54901
T-920/236-5051
F-920/236-1130
RE: FIRE PROTECTION ;
HUNTER'S RIDGE #9
3200 ELK RIDGE
OSHKOSH, WISCONSIN
AHERN FIRE PROTECTI
Dear Brian:
Enclosed is a copy of the
Fire Protection System Ir
Very truly yours,
AHERN FIRE PROTECTION
A division of J. F. Ahern Co.
Mark L. Jozefowski,
MLJ/ksj
Enclosure
Z:\FIItE\411 DATA\490694\LCITY07-24-2008. DOC
TALLATION
1
No. 490694
pr's Material and Test Certificates covering the above-referenced
for vouri files.
..,
a ~,
JUL 2 8 2008
~..~~ la~.e~ ~~y. ~ ~~ _,~ s
B
th'e Midwest Since 1880
An Equal Opportunity Employer
AHERN FIRE PROTECTION
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by the property owner or their authorized agent. All
defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving
authori 's re uirements or local ordinances.
PROPERTY NAME Hunter's Rid a Condominiums AFP Contract #: 490694 DATE: January 30, 2008
PROPERTY ADDR ESS 3200 Elk Ride Oshkosh, Wisconsin 54901
ACCEPTED BY APPROVING AUTHORITIES (NAMES)
1. Oshkosh Fire Department (Battalion Chief -- Stu Schrottky)
2. City of Oshkosh (Building Inspector -- Brian Noe)
3. State of Wisconsin -- Safety & Buildings
4.
ADDRESS
WI 54901
101 Court Street -- Oshkosh
1
Plans ,
.
2. 215 Church Avenue -- PO Box 1130 -- Oshkosh, WI 54901
3.
4. -
' INSTALLATION CONFORMS TO ACCEPTED PLANS YES ^ NO
EQUIPMENT USED IS APPROVED YES ^ NO
IF NO, EXPLAIN DEVIATIONS
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION ^ YES ^ NO
OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT?
INSTRUCTIONS IF NO, EXPLAIN
HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES:
Item No.'s 2 8 3 will 1. SYSTEM COMPONENTS INSTRUCTIONS ^ YES ^ NO
' be forwarded by AFP
at closeout time 2 CARE AND MAINTENANCE INSTRUCTIONS ^ YES ^ NO
. YES ^ NO
3. NFPA 25 ^
LOCATION OF SUPPLIES BUILDINGS
SYSTEM Buildin #9
MAKE MODEL YEAR OF
MANUFACTURE K-
FACTOR QUANTITY TEMPERATURE
RATING
T to LF II TY2234 Res. Pendent 1/2" White 2007 4.9 62 155 De .
Vikin Microfast QR VK300 Uri ht 1/2" Brass 2007 5.6 1 200 De .
T CA LF II TY1334 Res. HSW 1/2" White 2007 4.2 2 155 De .
SPRINKLERS
PIPE AND TYPE OF PIPE Lightw all Non-Threadable~ Thinwa ll Threadable~ Black CPVC
FITTINGS TYPE OF FITTINGS Grooved Threaded Mechanic al Tees: CPVC
MAXIMUM TIME TO OPERATE
FLOW ALARM DEVICE THROUGH TEST CONNECTION
TYPE MAKE MODEL MINUTES SECONDS
Water Flow Detector S stem Sensor WFD
N/A
EXPLAIN ANY ALARM PROBLEMS:
ALARM
DEVICES LOW AIR ALARM DEVICE RE TED
ALA
~
TYPE MAKE MODE PRESSU
-
.
S pROPERL
Y
N/A ~
P
I
'~
,YES:
NO
EXPLAIN ANY ALARM PROBLEMS: JUL 2 S ZOOS
~;.
re'` n
f
IlvsPtlrrl~r! s~RV~cFt; r, ~tYs?1;~
Ahern Fire Protection
CENTRAL MONITORING
LOCATION(S) SIGNALS RECEIVED
ALARM SERVICE
TYPE OR
NAME OF REMOTE
WATERFLOW PRESSURE
LOW-AIR
SERVICE
DETECTOR SWITCH
SUPERVISORY OTHER
FLOW
SUPERVISING LOCATION(S):
STATION
(ON-SITE)
REMOTE NAME OF SERVICE:
REMOTE MONITORING
SERVICE
~
~
L'('~'{'~-y~
SIGNAL NG (OFF-SITE) /
-
PHONE:
OTHER: LOCATION(S):
EXPLAIN ANY ALARM SIGNALING PROBLEMS:
DRY VALVE Q.O.D.
MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO.
DRY PIPE TIME TO TRIP WATER TRIP POINT AIR TIME WATER ALARM
OPERATING THROUGH TEST
'
°
PRESSURE AIR PRESSURE
PRESSURE REACHED TEST OPERATED
TEST
CONNECTION
'
OUTLET°'°
PROPERLY
MIN. SEC. PSI PSI PSI MIN. SEC. YES NO
WITHOUT
O.O.D.
WITH
Q.O.D.
IF NO, EXPLAIN:
OPERATION: ^ PNEUMATIC ^ ELECTRIC ^ HYDRAULIC
PIPING SUPERVISED ^ YES ^ NO DETECTING MEDIA SUPERVISED ^ YES ^ NO
DOES VALVE OPERATE FROM THE MANUAL TRIP, REMOTE, OR BOTH CONTROL STATIONS? ^ YES ^ NO
IS THERE AN ACCESSIBLE FACILITY IN EACH IF NO, EXPLAIN
DELUGE & CIRCUIT FOR TESTING?
PREACTION ^ YES ^ NO
VALVES
DOES EACH CIRCUIT DOES EACH CIRCUIT
OPERATE SUPERVISION
OPERATE VALVE MAXIMUM TIME TO
MAKE
MODEL
LOSS ALARM?
RELEASE? OPERATE RELEASE
YES NO YES NO MINUTES SECONDS
LOCATION & MAKE & MODEL SETTING STATIC PRESSURE RESIDUAL PRESSURE FLOW RATE
PRESSURE FLOOR (FLOWING)
REDUCING INLET OUTLET INLET OUTLET FLOW
VALVE TEST PSI PSI PSI PSI GPM
° MEASURED FROM TIME INSPECTORS TEST CONNECTION IS OPENED.
° NFPA 13 ONLY REQUIRES THE 60-SECOND LIMITATION IN SPECIFIC SECTIONS.
2
Ahern Fire Protection
HYDROSTATIC Hydrostatic tests shall be made at not less than 200 psi (13.6 bar) for two (2) hours or 50 psi (3.4 bar) above static pressure in
excess of 150 psi (10.2 bar) for two (2) hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All
TEST aboveground piping leakage shall be stopped.
DESCRIPTION
PNEUMATIC: Establish 40-psi (2.7 bar) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours. Test pressure
tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 bar) in 24 hours.
ALL PIPING HYDROSTATICALLY TESTED AT PSI (,_Bar) for HRS. IF NO, STATE REASON
DRY PIPING PNEUMATICALLY TESTED ^ YES ^ NO
EQUIPMENT OPERATES PROPERLY ^ YES ^ NO
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM
SILICATE OR DERIVATIVES OR SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED
FOR TESTING SYSTEMS OR STOPPING LEAKS?
YES ^ NO
DRAIN READING OF GAUGE LOCATED NEAR WATER RESIDUAL PRESSURE WITH VALVE IN TEST
TEST SUPPLY TEST CONNECTION:~
PSI (
Bar) CONNE
_
..__
CTION OPEN WIDE:(n~ pSl (_Bar)
TESTS UNDERGROUND MAINS AND LEAD IN CONNECTIONS TO SYSTEM RISER(S) TO OTHER EXPLAIN
BE FLUSHED BEFORE CONNECTION MADE TO SPRINKLER P
IPING.
VERIFIED BY COPY OF THE CONTRACTOR'S MATERIAL AND TEST
CERTIFICATE FOR UNDERGROUND PIPING. ^ YES ^ NO
FLUSHED BY INSTALLER OF UNDERGROUND SPRINKLER PIPING ^ YES ^ NO
it I'UwDER-DRIVEN FASTENERS ARE USED IN CON
CRETE, HAS
REPRESENTATIVE SAMPLE TESTING BEEN SATISF IF NO, EXPLAIN
ACTORILY COMPLETED?
^ YES ^ NO
BLANK NUMBER USED LOCATIONS
TESTING
O NUMBER REMOVED
GASKETS
WELDED PIPING YES ^ NO
IF YES...
Do you certify as the sprinkler contractor that welding procedures used complied with the minimum
regwrements of AWS B2.1, ASME Section IX Welding and Brazing Quaycations, or other applicable
qualification standard as required by the AHJ?
YES ^ NO
WELDING with the m nlmumtrall uirem~ents of AWS B21, ASME Section~IX ~We/diner atnd Brazined in accordance
9 g Qualifications
or oth
li
q
'~ YES ^ NO
,
er app
cable
ualification standard as required by the AHJ?
Do you certify that the welding was conducted incompliance with a documented quality control
procedure to ensure that (1) all discs are retrieved; (2) that openings in piping are smooth
that sla
d
,
g
completed wel
ds are free from cracks,tln(COmp ete fusioln,~surface porposity greate~t man 1%1a6e
ch4) ~y
y'E' ' ES ^ NO
n
diameter, undercut deeper than the lesser of 25% of the wall thickness or 1/32 inch; and (5) completed
circumferential butt weld reinforcement does not exceed 3/32 inch?
CUTOUTS DO YOU CERTIFY THAT YOU HA
DISCS) VE A CONTROL FEATURE TO ENSURE THAT ALL
CUTOUTS (DISCS ARE RETRIEVED? ES ^ NO
HYDRAULIC NAMEPLATE PROVIDED
DATA YES ^ NO IF NO, EXPLAIN
NAMEPLATE
REMARKS DATE LEFT IN SERVICE
WITH ALL CONTROL VALVES OPEN:
~
NAME OF SPRINKLER CONTRACTOR
~ °~ ~ _~~
AHERN FIRE PROTECTION, 201 MORRIS COURT -- FOND DU LAC, WI 54935
TESTS WITNESSED BY
AUTHORITIES HAVING JURISDICTION (SIGNED) TITLE
SIGNATURES DATE
THE PROPERTY OWNER OR THEIR AUTHORIZED AGENT (SIGNED) TITLE
DATE
FOR SPRINKLER T CTOR (SIGNED) TITLE DATE
~
r=t'1'~k+~l ~~ ~7',~ ~'
ADDITIONAL EXP NS N TES:
~-~ ~ ~
~
17
i
~~
.. -at '
3